hit counter script

Electrical Data Hcat Te 0011÷0121 / Hcan Te 0071÷0121 - Eco HCAT TE 0011 Use And Maintenance Manual

Cooling only air cooled condensing units and heat pumps with axial fans
Table of Contents

Advertisement

Voltage must be within a tolerance of ±10%
of the rated power supply voltage for the unit (for
three phase units, the unbalance between the phas-
es must not exceed 3%). If this is not the case, con-
tact the electricity supply company.
For electrical connections, use double insulation
cable in conformity with legislation in force in the
country concerned.
Install, if possible near the unit, an appropriate pro-
tection device to isolate the unit from the mains sup-
ply. This should have a delayed characteristic curve,
contacts opening by at least 3 mm and an adequate
interruption and differential protection capacity.
ELECTRICAL DATA HCAT TE 0011÷0121 / HCAN TE 0071÷0121
Size
Electrical power
supply (V-Ph-Hz)
0011
230~50
0021
230~50
0025
230~50
0031
230~50
0041
230-3~50
0051
230-3~50
0061
230-3~50
0091
230-3~50
0121
230-3~50
0011
400-3N~50
0021
400-3N~50
0025
400-3N~50
0031
400-3N~50
0041
400-3N~50
0051
400-3N~50
0061
400-3N~50
0071
400-3N~50
0091
400-3N~50
0101
400-3N~50
0121
400-3N~50
F.L.I.
Absorbed power
F.L.A.
Absorbed current
L.R.A. Compressor start-up current
HCAT TE - HCAN TE
Compressors
F.L.I.
F.L.A.
L.R.A.
(kW)
(A)
(A)
1,7
7,7
47
2,1
9,8
61
2,5
11,6
76
2,9
13,7
100
3,4
14,4
98
4,2
18,5
139
4,9
20,3
172
7,5
29,7
230
10,7
36,8
340
1,7
3,1
24
2,1
3,8
32
2,5
4,6
40
2,9
5,2
46
3,4
6,2
50
4,2
8,0
66
4,9
8,7
74
6,31
12,04
99
7,77
14,13
123
8,93
16,23
127
10,93
18,92
167
If this device is not visible from the electrical
panel of the unit, it should be lockable.
An efficient earth connection is obligatory.
Failure to earth the appliance absolves the manufac-
turer of all liability for damage.
In the case of three phase units, ensure the
phases are connected correctly.
Do not use refrigerant pipes to earth the
unit.
Rated values (1)
Fans
F.L.I.
F.L.A.
F.L.I.
(kW)
(A)
(kW)
0,15
0,64
1,9
0,15
0,64
2,3
0,15
0,64
2,7
0,15
0,64
3,1
0,15
0,64
3,6
0,30
1,28
4,5
0,30
1,28
5,2
0,70
3,40
8,2
1,40
6,80
12,1
0,15
0,64
1,9
0,15
0,64
2,3
0,15
0,64
2,7
0,15
0,64
3,1
0,15
0,64
3,6
0,30
1,28
4,5
0,30
1,28
5,2
0,70
3,40
7,01
0,70
3,40
8,47
1,40
6,80
10,33
1,40
6,80
12,33
(1)
Outside air temperature 35°C - Room temperature 27°C, 50% RH.,
values refer to the lower rated voltage (50Hz).
(2)
These values should be used to dimension protection switches and power
cables.
Total
Max. values (2)
F.L.A.
F.L.I.
(A)
(kW)
7,9
2,5
10,0
3,2
11,8
3,8
14,3
4,9
15,0
6,0
19,8
8,3
21,6
8,9
33,1
13,7
43,6
19,5
3,7
2,5
4,0
3,2
5,3
3,8
5,9
4,3
6,9
5,9
9,3
7,6
10,0
8,2
15,44
9,6
17,53
10,6
23,03
12,8
25,72
15,5
English 04/03
F.L.A.
(A)
12,1
15,4
18,0
23,7
19,1
26,3
28,3
44,4
63,8
4,5
5,8
6,8
7,7
10,7
13,7
14,8
18,4
21,3
27,3
32,2
11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents