Page 3
Contents Technical Manual Chapters 1. Description of Operation 2. Settings, Configuration & Instruments 3. Performance Specification 4. Data Communications 5. Installation 6. Commissioning and Maintenance 7. Applications Guide...
Page 5
Software Revision History 2015/11 2662H85001 R8b-7c EN100+ compatibility. Additional ‘46IT’ and ‘51’ element time multiplier steps incorporated. 2013/01 2662H85001 R7c-7b Revised file handling during shutdown 2012/08 2662H85001 R7b-7a Addition of optional IEC 61850 communication protocol and Ethernet. (Requires hardware Compatible with H/W CC 2010/02 2662H80001 R4c-3 Revisions to: VT ratio settings, 87BD 1st bias slope limit setting incre-...
Limited. No part of this document shall be reproduced or modified or stored in another form, in any data retrieval system, without the permission of Siemens Protection Devices Limited, nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent.
Chapter 1) 7SR242 Duobias Description Of Operation Section 1: Introduction This manual is applicable to the following relays: 7SR242 Multi-Function 2-Winding Transformer Protection Relay The 7SR242 relay integrates the protection and control elements required to provide a complete transformer protection.
Chapter 1) 7SR242 Duobias Description Of Operation Section 2: Hardware Description General The structure of the relay is based upon the Multi-function hardware platform. The relays are supplied in either size E8, E10 or E12 cases (where 1 x E = width of approx. 26mm). The hardware design provides commonality between products and components across the 7SR2 range of relays.
Chapter 1) 7SR242 Duobias Description Of Operation Front Cover With the transparent front cover in place the user only has access to the and TEST/RESET buttons, allowing all areas of the menu system to be viewed, but preventing setting changes and control actions. The only ‘action’...
Page 23
Chapter 1) 7SR242 Duobias Description Of Operation Relay Information Above the LCD three labels are provided, these provide the following information: 1) Product name and order code. 2) Nominal current rating, rated frequency, voltage rating, auxiliary dc supply rating, binary input supply rating, configuration and serial number.
Page 24
Chapter 1) 7SR242 Duobias Description Of Operation ‘TRIP’ LED This red LED is steadily illuminated to indicate that a user selectable function has operated to trip the circuit breaker. Functions are assigned to the ‘Trip’ LED using the OUTPUT CONFIG>Trip Contacts setting.
Chapter 1) 7SR242 Duobias Description Of Operation Current Inputs In total eight current inputs are provided on the Analogue Input modules. Terminals are available for both 1A and 5A inputs. CT ratios are input by the user in the CT/VT CONFIG menu.
Chapter 1) 7SR242 Duobias Description Of Operation Binary outputs (Output Relays) Relays are fitted with 6 or 14 binary outputs. All outputs are fully user configurable and can be programmed to operate from any or all of the available functions.
Chapter 1) 7SR242 Duobias Description Of Operation Figure 2-3 Binary Output Logic 2.10 Virtual Input/Outputs The relays have 16 virtual input/outputs, these are internal logic states. Virtual I/O is assigned in the same way as physical Binary Inputs and Binary Outputs. Virtual I/O is mapped from within the INPUT CONFIG > INPUT MATRIX and OUTPUT CONFIG >...
Chapter 1) 7SR242 Duobias Description Of Operation 2.11 Self Monitoring The relay incorporates a number of self-monitoring features. Each of these features can initiate a controlled reset recovery sequence. Supervision includes a power supply watchdog, code execution watchdog, memory checks by checksum and processor/ADC health checks.
Chapter 1) 7SR242 Duobias Description Of Operation Section 3: Protection Functions Current Protection: Differential Protection Comprises both biased differential and high-set differential elements. The fundamental frequency current is measured with the line CT inputs. These line currents are both multiplied and vector corrected before being applied to the current differential elements.
Chapter 1) 7SR242 Duobias Description Of Operation 3.1.2 Overall Biased Differential (87BD) Figure 3-1 Biased Differential Characteristic Figure 3.1-1 illustrates the biased differential characteristic. Within the relay the fundamental frequency RMS line currents are modified by the ICT Multiplier and ICT Connection settings (see 3.1.1) before being applied to the biased differential elements.
Chapter 1) 7SR242 Duobias Description Of Operation 3.1.3 87HS Figure 3-3 Differential Highset Characteristic Figure 3.1-3 illustrates the differential highset characteristic. Within the relay the fundamental frequency RMS line currents are modified by the ICT Multiplier and ICT Connection settings (see 3.1.1) before being applied to the differential highset elements.
Chapter 1) 7SR242 Duobias Description Of Operation Current Protection: Phase Overcurrent (51, 50) The optional phase overcurrent elements have a common setting to measure either fundamental frequency RMS or True RMS current: True RMS current: 51/50 Measurement = RMS Fundamental Frequency RMS current: 51/50 Measurement = Fundamental 3.2.1 Instantaneous Overcurrent Protection (50)
Chapter 1) 7SR242 Duobias Description Of Operation 3.2.2 Time Delayed Overcurrent Protection (51) Optionally two time delayed overcurrent elements are provided, each can be selected to either winding 1 or winding 2. 51-n Setting sets the pick-up current level. A number of shaped characteristics are provided. An inverse definite minimum time (IDMT) characteristic is selected from IEC, ANSI or user defined curves using 51-n Char.
Chapter 1) 7SR242 Duobias Description Of Operation Current Protection: Derived Earth Fault (50N, 51N) The earth current is derived by calculating the sum of the measured line currents. These optional elements utilise RMS current values of the fundamental frequency (50 or 60Hz).
Chapter 1) 7SR242 Duobias Description Of Operation 3.3.2 Time Delayed Derived Earth Fault Protection (51N) Optionally two time delayed derived earth fault elements are provided, each can be selected to either winding 1 or winding 2. 51N-n Setting sets the pick-up current level.
Chapter 1) 7SR242 Duobias Description Of Operation Current Protection: Measured Earth Fault (50G, 51G) The earth current is measured directly via dedicated current analogue inputs. These optional elements utilise either RMS or Fundamental current values as defined by the 51G/50G Measurement setting (MEASURED E/F menu).
Chapter 1) 7SR242 Duobias Description Of Operation 3.4.2 Time Delayed Measured Earth Fault Protection (51G) Optionally two time delayed measured earth fault elements are provided, each can be selected to either winding 1 or winding 2. 51G-n Setting sets the pick-up current level.
Chapter 1) 7SR242 Duobias Description Of Operation Current Protection: High Impedance Restricted Earth Fault (64H) Two high impedance restricted earth fault elements are provided, one for each transformer winding The relay utilises fundamental current measurement values for this function. The single phase current input is derived from the residual output of line/neutral CTs connected in parallel. An external stabilising resistor must be connected in series with this input to ensure that this element provides a high impedance path.
Chapter 1) 7SR242 Duobias Description Of Operation Open Circuit (46BC) Optionally two open circuit elements are provided, each can be selected to either winding 1 or winding 2. The element calculates the ratio of NPS to PPS currents. Where the NPS:PPS current ratio is above 46BC Setting an output is given after the 46BC Delay.
Chapter 1) 7SR242 Duobias Description Of Operation Current Protection: Negative Phase Sequence Overcurrent (46NPS) Optionally four NPS current elements are provided – 2 x 46IT and 2 x 46DT. Each element can be selected to either winding 1 or winding 2.
Chapter 1) 7SR242 Duobias Description Of Operation Current Protection: Under-Current (37, 37G) Optionally two under-current elements are provided for both line and measured earth current, each can be selected to either winding 1 or winding 2. Each phase has an independent level detector and current-timing element. 37-n Setting sets the pick-up current.
Chapter 1) 7SR242 Duobias Description Of Operation Current Protection: Thermal Overload (49) Optionally a phase segregated thermal overload element is provided, this can be selected to either winding 1 or winding 2. The thermal state is calculated using the measured True RMS current.
Chapter 1) 7SR242 Duobias Description Of Operation 3.10 Voltage Protection: Over Fluxing (24) Optionally, three over fluxing elements are provided – 2 x 24DT and 1 x 24IT Char elements. The 24DT Elements have a DTL characteristic. 24DT Setting sets the pick-up level and 24DT Delay the follower time delay.
Chapter 1) 7SR242 Duobias Description Of Operation 3.11 Voltage Protection: Under/Over Voltage (27/59) Optionally four under/over voltage elements are provided. The relay utilises fundamental voltage measurement values for this function. 27/59-n Setting sets the pick-up voltage level for the element.
Chapter 1) 7SR242 Duobias Description Of Operation 3.12 Voltage Protection: Neutral Overvoltage (59N) Optionally two Neutral Overvoltage (or Neutral Voltage Displacement) elements are provided. One of the elements can be configured to be either definite time lag (DTL) or inverse definite minimum time...
Chapter 1) 7SR242 Duobias Description Of Operation 3.13 Voltage Protection: Under/Over Frequency (81) Optionally six under/over frequency elements are provided. Frequency elements are blocked if the measured voltage falls below the 81 U/V Guard setting. The sense of the element (under-frequency or over-frequency) is set by the 81-n Operation setting.
Chapter 1) 7SR242 Duobias Description Of Operation Section 4: Control & Logic Functions Quick Logic The ‘Quick Logic’ feature allows the user to input up to 16 logic equations (E1 to E16) in text format. Equations can be entered using Reydisp or at the relay fascia.
Chapter 1) 7SR242 Duobias Description Of Operation Figure 4-1 Sequence Diagram showing PU/DO Timers in Quick Logic (Counter Reset Mode Off) When the count value = En Counter Target the output of the counter (En) = 1 and this value is held until the initiating conditions are removed when En is instantaneously reset.
Chapter 1) 7SR242 Duobias Description Of Operation Section 5: Supervision Functions Circuit Breaker Failure (50BF) Two CB Fail elements are provided – one element per winding. Each circuit breaker fail function has two time delayed outputs that can be used for combinations of re-tripping or back-tripping.
Chapter 1) 7SR242 Duobias Description Of Operation Trip/Close Circuit Supervision (74TCS/74CCS) The relay provides six trip and six close circuit supervision elements, all elements are identical in operation and independent from each other allowing 6 trip and 6 close circuits to be monitored.
Chapter 1) 7SR242 Duobias Description Of Operation Inrush Detector (81HBL2) Inrush detector elements monitor the line currents. The inrush detector can be used to block the operation of selected elements during transformer magnetising inrush conditions. The 81HBL2 Bias setting allows the user to select between Phase, Sum and Cross methods of measurement: Phase Each phase is inhibited separately.
Chapter 1) 7SR242 Duobias Description Of Operation Over Fluxing Detector (81HBL5) Over fluxing detector elements monitor the line currents. The over fluxing detector can be used to block the operation of differential protection (87BD/ 87HS) elements. The 81HBL5 Bias setting allows the user to select between Phase, Sum and Cross methods of measurement:...
Chapter 1) 7SR242 Duobias Description Of Operation Section 6: Other Features Data Communications Two communication ports, COM1 and COM2 are provided as standard. RS485 connections are available on the terminal blocks at the rear of the relay (COM1). A USB port, COM 2, is provided at the front of the relay for local access using a PC.
Chapter 1) 7SR242 Duobias Description Of Operation Maintenance 6.3.1 Output Matrix Test The feature is available from the Relay fascia and allows the user to operate binary outputs or LEDs assigned to relay functions. Any protection function which is enabled in the setting menu will appear in the Output Matrix Test.
Chapter 1) 7SR242 Duobias Description Of Operation Data Storage 6.4.1 General The relay stores three types of data records: relay event records, analogue/digital waveform records and fault data records. These data records are backed up in non-volatile memory and are permanently stored even in the event of loss of auxiliary d.c.
Chapter 1) 7SR242 Duobias Description Of Operation 6.4.4 Fault Data Records Measured quantities for the last 100 relay trip fault records are stored with time and date of trip. The HMI LCD can display the latest 10 fault records with time and date of trip, measured quantities and LED status.
Chapter 1) 7SR242 Duobias Description Of Operation Operating Mode The relay has three operating modes, Local, Remote and Out of Service. The following table identifies the functions operation in each mode. The modes can be selected by the following methods: SYSTEM CONFIG>RELAY MODE setting, a Binary Input or Command...
Chapter 1) 7SR242 Duobias Description Of Operation Real Time Clock Time and date can be set either via the relay fascia using appropriate commands in the System Config menu, via the data comms channel(s) or via the optional IRIG-B input.
Page 67
Limited. No part of this document shall be reproduced or modified or stored in another form, in any data retrieval system, without the permission of Siemens Protection Devices Limited, nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent.
Chapter 2) 7SR242 Duobias Settings, Configuration & Instruments Guide Section 1: Introduction Relay Menus And Display All relay fascias contain the same access keys although the fascias may differ in appearance from model to model. The basic menu structure is also the same in all products and consists of four main menus, these being, Settings Mode - allows the user to view and (if allowed via the settings mode password) change settings in the relay.
Chapter 2) 7SR242 Duobias Settings, Configuration & Instruments Guide Operation Guide 1.2.1 User Interface Operation The basic menu structure flow diagram is shown in Figure 1.2-2. This diagram shows the main modes of display: Settings Mode, Instrument Mode, Fault Data Mode and Control Mode.
Chapter 2) 7SR242 Duobias Settings, Configuration & Instruments Guide Settings Display The Settings Mode is reached by pressing the READ DOWN button from the relay identifier screen. Once the Settings Mode title screen has been located pressing the READ DOWN button takes the user into the Settings mode sub-menus.
Page 75
Chapter 2) 7SR242 Duobias Settings, Configuration & Instruments Guide DIFFERENTIAL METERS This is the sub-group that includes all the meters that are associated with Current TEST/RESET allows access to this sub-group to view W1 Line Displays Winding 1 Input 3 Phase currents Nominal RMS values &...
Page 76
Chapter 2) 7SR242 Duobias Settings, Configuration & Instruments Guide CURRENT METERS This is the sub-group that includes all the meters that are associated with Current TEST/RESET allows access to this sub-group to view W1 Primary Displays the 3 phase currents Primary RMS values 0.00kA...
Page 77
Chapter 2) 7SR242 Duobias Settings, Configuration & Instruments Guide VOLTAGE METERS This is the sub-group that includes all the meters that are associated with Voltage TEST/RESET allows access to this sub-group to view Voltage Meters Displays the Voltage RMS values Pri (Ph-Ph) 0.00kV...
Page 79
Chapter 2) 7SR242 Duobias Settings, Configuration & Instruments Guide MAINTENANCE METERS This is the sub-group that includes all the meters that are associated with Maintenance TEST/RESET allows access to this sub-group to view CB1 Manual Close Displays the CB manual opening and closing times...
Page 80
Chapter 2) 7SR242 Duobias Settings, Configuration & Instruments Guide GENERAL ALARM METERS This is the sub-group that includes all the meters that are associated with the Binary inputs TEST/RESET allows access to this sub-group to view General Alarms Displays the state of General Alarm...
Page 81
Chapter 2) 7SR242 Duobias Settings, Configuration & Instruments Guide BINARY OUTPUT METERS This is the sub-group that includes all the meters that are associated with the Binary Outputs TEST/RESET allows access to this sub-group to view BO 1-8 ---- ---- Displays the state of DC binary Outputs 1 to 8.
Chapter 2) 7SR242 Duobias Settings, Configuration & Instruments Guide QUICK LOGIC METERS to view E 1-8 E 9-16 E1 Equation TMR 0-0 CNT 0-1 En Equation Fault Data Mode The Fault Data Mode sub menu lists the time and date of the previous ten protection operations. The stored data about each fault can be viewed by pressing the TEST/RESET button.
Chapter 2) 7SR242 Duobias Settings, Configuration & Instruments Guide Section 2: Setting the Relay Using Reydisp Reydisp Evolution software provides a pc tool which can be used for programming of protection configuration and settings and the mapping of hardware input and outputs using a graphical interface. It is supplied with additional tools for configuration of serial communication protocol data objects, configuration of text for international language support and programming of user specific time current curves.
Chapter 2) 7SR242 Duobias Settings, Configuration & Instruments Guide 2.1.2 Rear RS485 connection Figure 2-2 RS485 connection to PC 2.1.3 Optional rear fibre optic connection Figure 2-3 Fibre Optic Connection to PC Sigma devices have a 25 pin female D connector with the following pin out.
Chapter 2) 7SR242 Duobias Settings, Configuration & Instruments Guide 2.1.6 Optional Rear EN100 Ethernet Module (COM3) The optional ethernet interface is primarily provided for support of IEC 61850 protocol. Support for IEC 870-5-103 is also provided over this interface to allow connection with Reydisp Evolution and Reydisp Manager software for interrogation, editing and download of relay settings and other data.
Chapter 2) 7SR242 Duobias Settings, Configuration & Instruments Guide 2.1.7 Configuring Relay Data Communication Using the keys on the relay fascia scroll down the settings menu’s into the ‘communications’ menu. All of the below settings may not be available in all relay types. Reydisp software is compatible with IEC60870-5-103 protocol.
Chapter 2) 7SR242 Duobias Settings, Configuration & Instruments Guide Setting name Range Default Units Notes Setting is only visible when DNP3 Destination 0 … 65534 a port protocol is set to Address DNP3. Setting is only visible when DNP3 Application 5, 6 ...
Page 89
Limited. No part of this document shall be reproduced or modified or stored in another form, in any data retrieval system, without the permission of Siemens Protection Devices Limited, nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent.
Chapter 3) 7SR242 Duobias Performance Specification Section 1: Common Functions General 1.1.1 CE Conformity This product is CE compliant to relevant EU directives. 1.1.2 Reference 1.1.2.1 Accuracy Reference Conditions This product has been tested under the following conditions, unless specifically stated otherwise.
Chapter 3) 7SR242 Duobias Performance Specification Energising Quantities 1.2.1 Auxiliary Power Supply 1.2.1.1 Rating Nominal Operating Range 30, 48, 110, 220 VDC 24 to 290 VDC 1.2.1.2 Burden Battery loading can be estimated from the following approximate figures: Attribute Watts...
Chapter 3) 7SR242 Duobias Performance Specification 1.2.2 AC Current Nominal Measuring Range 1, 5 A Phase and earth 80 x In 50, 60Hz 47 to 62Hz Note. 1 A and 5 A nominal inputs are user selectable on each model.
Chapter 3) 7SR242 Duobias Performance Specification 1.2.3 AC Voltage Nominal Operating Range 40 to 160 V Up to 270 V 50, 60Hz 47 to 62Hz 1.2.3.1 Burden Attribute Value AC Burden 0.1 VA at 110 V 1.2.3.2 Thermal Withstand Overload Period...
Chapter 3) 7SR242 Duobias Performance Specification 1.2.4 Binary (Digital) Outputs Contact rating to IEC 60255-0-2 Attribute Value Carry continuously 5A AC or DC for 0.5 s 20A AC or DC Make and carry (L/R 40 ms and V 300 V) for 0.2 s...
Chapter 3) 7SR242 Duobias Performance Specification Functional Performance 1.3.1 Instrumentation Instrument Value Reference Typical accuracy Current 0.1In to 2.0In 1 % or 1 % In Voltage 0.1Vn to 1.2Vn 1 % or 1 % Vn 1.3.2 Data Communication 1.3.2.1 USB Data Communication Interface...
Chapter 3) 7SR242 Duobias Performance Specification Environmental Performance 1.4.1 General 1.4.1.1 Temperature IEC 60068-2-1/2 Type Level Operating range -10 C to +55 C Storage range -25 C to +70 C 1.4.1.2 Humidity IEC 60068-2-78 Type Level Operational test 56 days at 40 C and 93 % relative humidity 1.4.1.3...
Chapter 3) 7SR242 Duobias Performance Specification 1.4.2 Emissions IEC 60255-25 1.4.2.1 Radiated Radio Frequency Type Limits at 10 m, Quasi-peak 30 to 230 MHz 40 dB( V/m) 230 to 10000 MHz 47 dB( V/m) 1.4.2.2 Conducted Radio Frequency Limits Type...
Page 105
Chapter 3) 7SR242 Duobias Performance Specification 1.4.3.5 Electrical Fast Transient / Burst Immunity IEC 60255-22-4 Class A (2002) Type Level Variation Case, Aux Power & I/O 4.0 kV 10 % RS485 Metallic Comms 2.0 kV No data loss 1.4.3.6 Surge Immunity...
Chapter 3) 7SR242 Duobias Performance Specification 1.4.4 Mechanical 1.4.4.1 Vibration (Sinusoidal) IEC 60255-21-1 Class I Type Level Variation Vibration response 0.5 gn Vibration endurance 1.0 gn 1.4.4.2 Shock and Bump IEC 60255-21-2 Class I Type Level Variation Shock response 5 gn, 11 ms...
Chapter 3) 7SR242 Duobias Performance Specification 2.13.6 Operate and Reset Time (59NIT) Attribute Value Starter operate time ( 2xVs) 65 ms, 20ms basic 5 % or 65 ms char = IDMTL Operate time char = DTL 1 % or 40ms...
Chapter 3) 7SR242 Duobias Performance Specification 74TCS/CCS Trip/Close Circuit Supervision 3.2.1 Reference Parameter Value Delay setting 0, 0.02…60 s 3.2.2 Operate and Reset Time Attribute Value Element basic operate time 30ms 10ms basic Operate time following delay 1 % or...
Chapter 3) 7SR242 Duobias Performance Specification 3.4 81HBL5 Overfluxing Detector 3.4.1 Reference Parameter Value Setting (Ratio of 5th Harmonic current to 0.10, 0.11... 0.5 Fundamental component current) 3.4.2 Operate and Reset Level Attribute Value Operate level 100 % I, 4 % or...
Page 139
No part of this document shall be reproduced or modified or stored in another form, in any data retrieval system, without the permission of Siemens Protection Devices Limited, nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent.
Page 143
Chapter 4 - 7SR242 Duobias · Data Communications Definitions 1. Introduction This section describes how to use the Communication Interface with a control system or interrogating computer. The interface is compatible with control and automation systems using industry standard communications protocols DNP3 , IEC 60870-5-103 , IEC 61850 and MODBUS-RTU.
Chapter 4 - 7SR242 Duobias · Data Communications Definitions 2. Physical Connection 2.1 Introduction The relay provides one “Front” USB communication interface (Com2) located on the fascia and one RS485 (Com1) located on the “Rear” as standard. An additional module may be fitted as an ordering option to provide extra rear serial port(s) or two Ethernet channels.
Page 147
Chapter 4 - 7SR242 Duobias · Data Communications Definitions The 2-wire RS485 communication port is located on the rear of the relay and can be connected using a suitable RS485 120 Ohm screened twisted pair cable. The RS485 electrical connection can be used in a single or multi-drop configuration. The RS485 master must support and use the Auto Device Enable (ADE) feature.
Page 149
Chapter 4 - 7SR242 Duobias · Data Communications Definitions • Receiver sensitivity. The light power at the receiver must be above the sensitivity of the receiver in order that effective communication can occur. • A 3dB safety margin is usually allowed after the budget calculation is performed.
Chapter 4 - 7SR242 Duobias · Data Communications Definitions RS232 to Fibre Optic Converter RS232 straight through cable Computer or Control System 62.5/125µm fibre optic with ST USB or 9 pin male connectors 25 pin male D connector D connector Fig.
Page 153
Chapter 4 - 7SR242 Duobias · Data Communications Definitions Setting Name Range/Options Default Setting Notes The protocol used COM3 IEC60870-5-103 to communicate on IEC60870-5-103 the standard RS485 Protocol MODBUS-RTU connection. DNP3 An address within the range of the relevant COM3...
Page 155
Chapter 4 - 7SR242 Duobias · Data Communications Definitions Ethernet – EN100-E Ethernet – EN100-O Ch 1 Ch 2 Ch 1 Ch 2 LED yellow LED yellow LED green LED green EN100 Module – RJ45 Interface EN100 Module – Duplex-LC Interface Green LED (Physical Link) Off –...
Chapter 4 - 7SR242 Duobias · Data Communications Definitions 3. IEC 60870-5-103 Definitions 3.1 Introduction This section describes the IEC 60870-5-103 protocol implementation in the relays. This protocol is used for the communication with Reydisp software and can also be used for communication with a suitable control system.
Chapter 4 - 7SR242 Duobias · Data Communications Definitions 3.3 Application Service Data Unit (ASDU) Type The Application Service Data Unit (ASDU) column of the “Information Number and Function” table lists the possible ASDUs returned for a point. ASDU #...
Page 161
Chapter 4 - 7SR242 Duobias · Data Communications Definitions Description ASDU 187 Quick Logic E6 1 SE, GI 188 Quick Logic E7 1 SE, GI 189 Quick Logic E8 1 SE, GI 190 Quick Logic E9 1 SE, GI 191 Quick Logic E10...
Page 163
Chapter 4 - 7SR242 Duobias · Data Communications Definitions Description ASDU 8 LED 8 1 SE, GI 9 LED 9 1 SE, GI 10 LED 10 1 SE, GI 11 LED 11 1 SE, GI 12 LED 12 1 SE, GI...
Page 165
Chapter 4 - 7SR242 Duobias · Data Communications Definitions Description ASDU 16 51-2 2 SE, GI 17 50-2 2 SE, GI 18 51N-2 2 SE, GI 19 50N-2 2 SE, GI 20 51G-2 2 SE, GI 21 50G-2 2 SE, GI...
Page 167
Chapter 4 - 7SR242 Duobias · Data Communications Definitions Description ASDU 128 CB2 Total Trip Count 4 SE 129 CB2 Delta Trip Count 4 SE 63 General Trip 2 SE, GI 64 Trip L1 2 SE, GI 65 Trip L2...
Chapter 4 - 7SR242 Duobias · Data Communications Definitions 4. MODBUS Definitions 4.1 Introduction This section describes the MODBUS-RTU protocol implementation in the relays. This protocol is used for communication with a suitable control system. This protocol can be set to use any or all of the relays hardware interfaces (USB, Fibre Optic, RS232 and RS485).
Chapter 4 - 7SR242 Duobias · Data Communications Definitions Address Value 30002 2400 On reception these two registers should be interpreted in the correct order as IEEE754 floating point representation. 4.2.2 FP_32BITS_3DP The FP_32BITS_3DP is a 32 bit integer fixed point value, containing 3 decimal places of information. It is used to send a real value to 3 decimal places as an integer.
Chapter 4 - 7SR242 Duobias · Data Communications Definitions Byte Content FUN INF DPI RT L F# L F# H ms L Event Type 2 Format. Byte Content FUN INF Meas ms L Event Type 4 Format. 4.2.6 EVENTCOUNT The EVENTCOUNT register contains the current number of events in the relay's event buffer.
Chapter 4 - 7SR242 Duobias · Data Communications Definitions 4.3 Point List The information shown below is the default configuration. This can be modified using the Communications Configuration Editor tool, refer section 9 for details. 4.3.1 Coils (Read Write Binary values)
Page 181
Chapter 4 - 7SR242 Duobias · Data Communications Definitions Address Name 10612 LED 12 10613 LED 13 10614 LED 14 10615 LED 15 10616 LED 16 10617 LED 17 10618 LED 18 10619 LED 19 10620 LED 20 10621 LED 21...
Chapter 4 - 7SR242 Duobias · Data Communications Definitions Address Name 12843 User Output 12 12844 User Output 13 12845 User Output 14 12846 User Output 15 12847 User Output 16 12848 User Output 17 12849 User Output 18 12850 User Output 19...
Chapter 4 - 7SR242 Duobias · Data Communications Definitions Address Name Format Mult Description 31200 W2 Primary Ia FP_32BITS_3DP 1.000000 W2 Primary Ia A 31202 W2 Primary Ib FP_32BITS_3DP 1.000000 W2 Primary Ib A 31204 W2 Primary Ic FP_32BITS_3DP 1.000000 W2 Primary Ic A...
Page 189
Chapter 4 - 7SR242 Duobias · Data Communications Definitions Address Name Format Mult Description 41216 W2 Nominal Ic FP_32BITS_3DP 1.000000 W2 Ic xIn 41218 W2 Line Ia FP_32BITS_3DP 1.000000 W2 Line Ia xIn 41220 W2 Line Ib FP_32BITS_3DP 1.000000 W2 Line Ib xIn...
Page 193
Chapter 4 - 7SR242 Duobias · Data Communications Definitions DNP V3.0 DEVICE PROFILE DOCUMENT (Also see the DNP 3.0 Implementation Table in Section 5.2, beginning on page 56). Sequential File Transfer Support: File Transfer Support Append File Mode Custom Status Code Strings...
Chapter 4 - 7SR242 Duobias · Data Communications Definitions 5.3.5 Analog Inputs The following table lists Analog Inputs (Object 30). It is important to note that 16-bit and 32-bit variations of Analog Inputs, Analog Output Control Blocks, and Analog Output Statuses are transmitted through DNP as signed numbers.
Chapter 4 - 7SR242 Duobias · Data Communications Definitions Analog Inputs Static (Steady-State) Object Number: 30 Change Event Object Number: 32 Analog Input Deadband: 34 Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input with Flag) or 2 (16-Bit Analog Input with Flag)
Chapter 4 - 7SR242 Duobias · Data Communications Definitions 7. IEC61850 Protocol Support 7.1 Introduction The relay can optionally be provided with IEC61850 comms. For further details refer to the following publications: • Model Implementation Conformance Statement (MICS) • Protocol Implementation Conformance Statement (PICS) •...
Chapter 4 - 7SR242 Duobias · Data Communications Definitions 8. Serial Modems 8.1 Introduction The communications interface has been designed to allow data transfer via modems. A suitable Modem can be connected directly to the Relay's serial interface, for example RS232, RS485 or fibre-optic port where fitted.
Chapter 4 - 7SR242 Duobias · Data Communications Definitions 9. Configuration The data points and control features which are possible within the relay is fixed and can be transmitted over the communication channel(s) protocols in the default format described earlier in this document. The default data transmitted is not always directly compatible with the needs of the substation control system and will require some tailoring;...
When connecting relays in an optical ring architecture, the data must be passed from one relay to the next, therefore when connecting in this method all relays must have the Data Echo ON. EN100 Siemens' Ethernet communications module supporting IEC61850, available in optical and electrical versions. Ethernet A computer networking technology.
Page 229
Chapter 4 - 7SR242 Duobias · Data Communications Definitions Appendix 1 The operating mode of the device is set via the setting, or through a command sent to a communications port. There are four options; Local, Remote, Local or Remote and Service.
Page 231
Limited. No part of this document shall be reproduced or modified or stored in another form, in any data retrieval system, without the permission of Siemens Protection Devices Limited, nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent.
If damage has been sustained a claim should be immediately be made against the carrier, also inform Siemens Protection Devices Limited and to the nearest Siemens agent, using the Defect Report Form in the Maintenance section of this manual.
Chapter 5) 7SR242 Duobias Installation Guide Disposal The Relay should be disposed of in a manner which does not provide a threat to health or the environment. All laws and regulations specific to the country of disposal should be adhered to.
Chapter 5) 7SR242 Duobias Installation Guide Section 2: Equipment Operating Conditions General Safety Precautions Current Transformer Circuits The secondary circuit of a live CT must not be open circuited. Non-observance of this precaution can result in injury to personnel or damage to equipment.
Page 239
Chapter 5) 7SR242 Duobias Installation Guide 254.5 Optional ethernet 216.5 comms module Case Earth connection Typical when fitted SIDE VIEW FRONT VIEW 25mm MIN CLEARANCE FOR TERMINAL WIRING 70mm MIN CLEARANCE FOR F/O COMMS CABLE 75mm MIN CLEARANCE BELOW EN100 MODULE...
Chapter 5) 7SR242 Duobias Installation Guide Fixings 3.2.1 Crimps M4 Ring tongued crimps with 90 bend are recommended for connection to the standard M4 terminal screws and RS485 port connections. 3.2.2 Panel Fixings Typical mounting screw kit per Relay) Consists of 4 off M4x10mm Screws...
Page 243
Chapter 5) 7SR242 Duobias Installation Guide E8 STANDARD COMMS + ADDITIONAL PORTS USB FRONT PORT, 2 x RS485 (SEE NOTE 2), IRIG B E8 STANDARD COMMS + ADDITIONAL PORTS USB FRONT PORT, RS485 (SEE NOTE 2), RS232, IRIG B Notes 1) Recommended terminations are pre-insulated &...
Chapter 5) 7SR242 Duobias Installation Guide Section 6: Data Comms Connections RS485 Connection The RS485 communication port terminals are located on the rear of the relay and can be connected using a suitable RS485 120 screened twisted pair cable. The RS485 electrical connection can be used in a single or multi-drop configuration. When used with Reydisp the RS485 master must support and use the Auto Device Enable (ADE) feature.
Chapter 5) 7SR242 Duobias Installation Guide Optional Fibre Optic Connections Where fitted rear Data Comms ports 3 and 4 comprise Fibre–Optic ST™ (BFOC/2.5) bayonet connectors-4 per product. 62.5 / 125 m glass fibre is recommended for all lead lengths. When installing fibre, ensure that the fibres’ bend radii comply with the recommended minimum for the fibre used- typically 50mm is acceptable.
Chapter 5) 7SR242 Duobias Installation Guide Optional Additional RS485 Connections The additional (optional) RS485 communication port is located at the rear of the relay and can be connected using a suitable RS485 120 ohm screened twisted pair cable. The RS485 electrical connection can be used in a single or multi-drop configuration. When used with Reydisp the RS485 master must support and use the Auto Device Enable (ADE) feature.
Chapter 5) 7SR242 Duobias Installation Guide Additional (Optional) Ethernet Connection for IEC 61850 Rear Ethernet Comms port Ch 1 and Ch 2 comprises Fibre–Optic Duplex LC connectors or electrical RJ45 connectors. When installing fibre, ensure that the fibres’ bend radii comply with the recommended minimum for the fibre used- typically 50mm is acceptable, 62.5 / 125 m glass fibre is recommended for all distances.
Page 255
Limited. No part of this document shall be reproduced or modified or stored in another form, in any data retrieval system, without the permission of Siemens Protection Devices Limited, nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent.
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide Section 1: Common Functions Overview Commissioning tests are carried out to prove: Equipment has not been damaged in transit. Equipment has been correctly connected and installed. Prove characteristics of the protection and settings which are based on calculations.
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide 1.2.3 Test Equipment Required test equipment is: Secondary injection equipment with integral time interval meter Primary injection equipment A d.c. supply with nominal voltage within the working range of the relay's d.c. auxiliary supply rating A d.c.
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide 1.2.5 Applying Settings The relay settings for the particular application should be applied before any secondary testing occurs. If they are not available then the relay has default settings that can be used for pre-commissioning tests. See the Relay Settings section of this manual for the default settings.
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide Tests 1.3.1 Inspection Ensure that all connections are tight and correct to the relay wiring diagram and the scheme diagram. Record any deviations. Check that the relay is correctly programmed and that it is fully inserted into the case. Refer to ‘Section 2: Settings and Instruments’...
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide AC Energising Quantities Voltage and current measurement for each input channel is displayed in the Instrumentation Mode sub-menus, each input should be checked for correct connection and measurement accuracy by single phase secondary injection at nominal levels.
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide Binary Inputs The operation of the binary input(s) can be monitored on the ‘Binary Input Meters’ display shown in ‘Instruments Mode’. Apply the required supply voltage onto each binary input in turn and check for correct operation.
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide Binary Outputs A minimum of six output relays are provided. Two of these have change over contacts, BO2 & BO3, one has a normally closed contact, BO1 and the remainder have normally open contacts.
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide Section 2: Protection Functions This section details the procedures for testing each protection function of the 7SR24 relay. These tests are carried out to verify the accuracy of the protection pick-ups and time delays at setting and to confirm correct operation of any associated input and output functionality.
Page 270
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide Particular care should be taken when testing overcurrent functions that the thermal rating of the current inputs is not exceeded. It should be considered that where several overlapping elements are used simultaneously, the overall protection operate time may be dependent on the operation of different individual elements at the various levels of applied current or voltage.
Page 272
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide Secondary testing of the bias characteristic will be greatly simplified by the use of automated numeric protection test equipment such as the Omicron CMC256. This equipment can be programmed using setting which match those of the relay to test for accuracy over the whole operating range and give a clear easy to use graphical display of relay performance against the specified characteristic.
Page 273
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide 2.1.1.2 Results for testing 87BD with 2 current sources 87BD I 87BD 1 W1 C NITIAL URRENT ETTING LOPE ETTING 0.00 1.00 1.50 2.00 2.50 W2 Current (x I 0.10 0.10 1.11 1.66...
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide 2.1.2 Primary Injection Testing Primary injection is recommended to prove the relay connections, CT polarity and settings before putting the protection scheme into service. Primary injection is essential to fully prove the connections of the Biased Differential and REF protections.
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide 2.1.4 Definite Time Overcurrent (50) If DTL setting is small, gradually increase current until element operates. If DTL is large apply 0.9x setting, check for no operation, apply 1.1x setting, check operation...
Page 277
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide 2.1.5.1 Element Blocking The Phase Overcurrent elements can be blocked by Binary Input Inhibit and Inrush Detector operation. This functionality should be checked. Element BI Inhibits Inrush Detector 51-1 51-2 50-1 50-2 2.1.5.2 ANSI Reset...
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide 2.2.1 Definite Time Overcurrent (50N) If DTL setting is small, gradually increase current until element operates. If DTL is large apply 0.9x setting, check for no operation, apply 1.1x setting, check operation...
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide 2.2.2.1 Element Blocking The Measured Earth Fault elements can be blocked by Binary Input Inhibit, VT Supervision and Inrush Detector operation. The Characteristic can be made non-directional by VT Supervision. This functionality should be checked.
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide Measured Earth fault (50G, 51G) Figure 2-5 Measured Earth Fault Voltage Inputs: None Current Inputs: G1 , Disable: 50BF, 64H Map Pickup LED: 51G-n/50G-n - Self Reset Other protection functions may overlap with these functions during testing, it may be useful to disable some functions to avoid ambiguity.
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide 2.3.1 Definite Time Overcurrent (50G) If DTL setting is small, gradually increase current until element operates. If DTL is large apply 0.9x setting, check for no operation, apply 1.1x setting, check operation...
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide 2.3.2.1 Element Blocking The Measured Earth Fault elements can be blocked by Binary Input Inhibit, VT Supervision and Inrush Detector operation. The Characteristic can be made non-directional by VT Supervision. This functionality should be checked.
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide Restricted Earth fault (64H) Figure 2-6 Restricted Earth Fault Voltage Inputs: Current Inputs: G1 , Disable: 50G, 51G, 50BF Map Pickup LED: 64H-n - Self Reset The external stabilising resistor value should be measured and compared to that specified in the settings data.
Page 285
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide These elements can be enabled for the I or I current inputs by relay settings, ensure that current is injected on the correct input. Since the DTL setting is generally small the pick-up setting can be tested by gradually increasing current until element operates.
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide Open Circuit (46BC) Figure 2-7 Open Circuit Voltage Inputs: Current Inputs: W1-I ), W1-I ), W1-I ), or W2-I ), W2-I ), W2-I Disable: 51N, 46IT, 46DT Map Pickup LED: 46BC - Self Reset This function uses the ratio of NPS current to PPS current to detect an open circuit .
Page 287
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide 46BC Setting 1P unbalance current (% of 3P current) 100% 129% 161% 200% 46BC Setting 3P balanced current (A) 1P unbalance current (A) Measured Unbalance current 46BC-1 46BC-2 Apply 1A 1P unbalance current without 3P balanced current. Measure 46BC operating time.
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide 2.6.1 Definite Time NPS Overcurrent (46DT) If DTL setting is small, gradually increase current until element operates. If DTL is large apply 0.9x setting, check for no operation, apply 1.1x setting, check operation...
Page 290
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide 2.6.2.1 ANSI Reset If the element is configured as an ANSI characteristic, it may have a reset delay applied. If ANSI reset is selected for an IEC characteristic element, the reset will be instantaneous.
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide Phase P.U. Current Operate Time NOTES (Amps) (sec) Amps 0.5 x Is Wn-I Wn-I Wn-I Wn-I Wn-I Wn-I Elements can be blocked by operation of a Binary Input Inhibit or by operation of the 37-n U/I Guard element.
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide Thermal Overload (49) Figure 2-10 Thermal Overload Voltage Inputs: Current Inputs: W1-I ), W1-I ), W1-I ), or W2-I ), W2-I ), W2-I Disable: 51, 50, 37, 46NPS, 50CBF, 87BD Map Pickup LED: 49 Alarm The current can be applied from a 3P balanced supply or phase by phase from a 1P supply.
Page 294
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide Time Constant (mins) Operate Time (sec) 17.3 34.5 51.8 86.3 51.8 1726 The Thermal State must be in the fully reset condition in order to measure the operate time correctly. This can be achieved by setting change in the Thermal protection settings menu or by pressing the Test/Reset button when the Thermal Meter is shown in the Instruments Mode.
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide Under/Over Voltage (27/59) Figure 2-11 Phase Under/Over Voltage Voltage Inputs: Current Inputs: n/a apply zero current to stabilize other functions Disable: Map Pickup LED: 27/59-n - Self Reset Where more than one Undervoltage (27) elements are being used with different settings, it is convenient to test the elements with the lowest settings first.
Page 296
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide Where more than one Overvoltage (59) elements are being used with different settings, it is convenient to test the elements with the highest settings first. The elements with lower settings can then be tested without disabling the higher settings.
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide 2.9.2 Undervoltage Guard (27/59UVG) If any 27 Undervoltage element is set to be inhibited by the 27 Undervoltage Guard element, this function should be tested. Connect the test voltage inputs to suit the installation wiring diagram utilising any test socket facilities available. It may be useful to temporarily map an LED as ‘General Pickup’...
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide 2.10.1 Definite Time (59NDT) If DTL setting is small, gradually increase single phase voltage until element operates. If DTL is large apply 0.9x setting, check for no operation, apply 1.1x setting, check operation...
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide 2.11 Under/Over Frequency (81) Figure 2-13 Under/Over Frequency Voltage Inputs: Current Inputs: n/a apply zero current to stabilize other functions Disable: Map Pickup LED: 81-n - Self Reset For Over-frequency, the elements with the highest setting should be tested first and for Under-frequency the elements with the lowest settings should be tested first.
Page 301
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide If the element is set as 81-n U/V Guarded, The applied voltage must be above the 81 UV Guard Setting in the U/O Frequency menu. Apply setting frequency +0.5Hz for Over-frequency or -0.5Hz for Under-frequency and record operating time.
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide 2.12 Overfluxing (24) Figure 2-14 Under/Over Frequency The settings are set in terms of V/f based on multiple of nominal voltage and frequency. Application of a voltage of nominal voltage and frequency represents 1.0.
Page 303
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide 2.12.2 inverse time (24IT) The inverse V/f element should be tested at each of the points specified by settings that constitute the overall inverse characteristics. Setting Setting Hysteresis Calculated P.U. D.O. Operate...
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide Section 3: Supervision Functions CB Fail (50BF) Figure 3-1 CB Fail Voltage Inputs: Current Inputs: W1-I ), W1-I ), W1-I ), I or W2-I ), W2-I ), W2-I ), I Disable: Map Pickup LED:...
Page 306
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide Apply a trip condition by injection of current to cause operation of a suitable protection element. Allow current to continue after the trip at a level of 110% of the 50BF Setting current level on any phase. Measure the time for operation of 50BF-1 Delay and 50BF-2 Delay.
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide Trip/Close Circuit Supervision (74TCS, 74CCS) Figure 3-2 Trip Circuit Supervision Voltage Inputs: Current Inputs: Disable: Map Pickup LED: 74TCS-n/74CCS-n - Self Reset The T/CCS-n Delay can be initiated by applying an inversion to the relevant status input and measured by monitoring of the alarm output.
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide Magnetising Inrush Detector (81HBL2) Figure 3-3 Magnetising Inrush Detector Voltage Inputs: Current Inputs: W1-I ), W1-I ), W1-I ), or W2-I ), W2-I ), W2-I Disable: Map Pickup LED: Logical operation of the harmonic blocking can be tested by injection of 2 harmonic current (at 100Hz for 50Hz relay) to cause operation of the blocking signals.
Page 309
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide A compromise test can be made by the use of a diode to generate a half-wave rectified waveform from a sinusoidal source. The half-wave rectified current will contain a combination of fundamental and harmonic currents.
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide Overfluxing Detector (81HBL5) Figure 3-4 Magnetising Inrush Detector Voltage Inputs: Current Inputs: W1-I ), W1-I ), W1-I ), or W2-I ), W2-I ), W2-I Disable: Map Pickup LED: Logical operation of the harmonic blocking can be tested by injection of 5 harmonic current (at 250Hz for 50Hz relay) to cause operation of the blocking signals.
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide Section 4: Control & Logic Functions Quick Logic If this functionality is used, the logic equations may interfere with testing of other protection functions in the relay. The function of the Quick Logic equations should be tested conjunctively with connected plant or by simulation to assess suitability and check for correct operation on an individual basis with tests specifically devised to suit the particular application.
It may however be convenient to fit the withdrawable relay to the outer case from a spare relay, to avoid the disturbance of relay panel wiring, for return to Siemens Protection Devices Ltd. The withdrawable relay should never be transported without the protection of the outer case.
If the above checklist does not help in correcting the problem please contact the local Siemens office or contact PTD 24hr Customer Support, Tel: +49 180 5247000, Fax: +49 180 524 2471, e-mail: support.energy@siemens.com.
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide Section 6: Relay Software Upgrade Instructions General Please read thoroughly all of the instructions supplied with the firmware upgrade before starting the download process. If you are loading firmware into a product that is already installed on site then follow the instructions in section 2, 3 and 4.
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide 6.2.4 Things To Do Before Loading New Firmware/Software Ensure that a secure copy of relay settings is available as all settings will be lost during the code upload process. A hard copy is useful for checking purposes. It is usually possible to download the existing settings into Reydisp Evolution, save the file and then reload these settings into the relay following the upgrade.