Parameter
Function
r0080
CO: Actual torque
[Nm]
Displays actual torque. This value is available filtered (r0031) and unfiltered (r0080).
r0084
CO: Actual air gap flux
[%]
Displays air gap flux relative to the rated motor flux.
r0085
CO: Actual re-active
current [A]
Displays re-active (imaginary part) of motor current.
Dependency:
Applies when V/f control is selected in P1300 (control mode); otherwise, the display shows the value zero.
r0086
CO: Actual active
current [A]
Displays active (real part) of motor current.
Dependency:
See r0085
r0087
CO: Actual power
factor
Displays the actual power factor.
r0094
CO: Transformation
angle [°]
Displays the transformation angle (flux angle in VC mode or angle from frequency in Vf mode).
P0095[0...9]
CI: Display PZD sig-
nals
Selects source of display for PZD signals.
Index:
[0]
[1]
...
[9]
r0096[0...9]
PZD signals [%]
Displays PZD signals.
Index:
[0]
[1]
...
[9]
Note:
r0096 = 100 % corresponds to 4000 hex.
P0100
Europe / North Ameri-
ca
Determines whether the power settings are expressed in [kW] or [hp] (e.g. Rated motor power P0307).
The default settings for the rated motor frequency P0310 and maximum frequency P1082 are set automat-
ically here, in addition to reference frequency P2000.
0
1
2
SINAMICS V20 Inverter
Operating Instructions, 09/2014, A5E34559884
Range
Factory
default
-
-
-
-
-
-
-
-
-
-
-
0.0
0 -
0
4294967295
1st PZD signal
2nd PZD signal
...
10th PZD signal
-
-
1st PZD signal
2nd PZD signal
...
10th PZD signal
0 - 2
0
Europe [kW], motor base frequency is 50 Hz
North America [hp], motor base frequency is 60 Hz
North America [kW], motor base frequency is 60 Hz
Can be
Scaling
changed
-
-
-
PERCENT
-
P2002
-
P2002
-
-
-
4000H
T
4000H
-
-
C(1)
-
Parameter list
7.2 Parameter list
Data
Data
Acc.
set
type
Level
-
Float
4
-
Float
4
-
Float
3
-
Float
3
-
Float
3
-
Float
3
-
U32
3
-
Float
3
-
U16
1
161