hit counter script

Technical Description; Principle Of The Cp 523; Print Mode - Siemens SIMATIC S5 CP 523 Manual

Serial i/o module
Hide thumbs Also See for SIMATIC S5 CP 523:
Table of Contents

Advertisement

CP 523
2

Technical Description

2.1

Principle of the CP 523

The CP 523 handles data transfer with a peripheral device autonomously. Data transfer between
the CPU and the CP 523 must always be started by the CPU by sending a job request to the CP 523.
Typical jobs would be, for example, "Print message text number 20" in Print mode or "Receive a
message frame from a peripheral device" in Communications mode.
EPROM / EEPROM
memory submodule
DB1 (parameter setting data
for the serial interface and
configuration data for the
format of message text
printouts)
DB2 to 255 (up to 4095
message texts)
RS-232-C (V.24) serial
interface or TTY
interface
(25-pin subminiature D
Cannon connector) of
peripheral device (printer,
barcode reader, CP 523,
etc.)

Print mode

The "Print message text XY" job request causes the message text stored in the memory submodule
under the number XY to be transferred to the printer via the serial interface. Current values of
variables, time of day and date can be entered in the message text during this process. You can
configure up to 4095 different message texts and store them in the memory submodule. You can
also include control commands for the printer in the message text. These are then executed on
printout (double-width type on/off).
EWA 4NEB 811 6044-02a
CP 523
RAM
Send mailbox
Receive mailbox
Message
buffer
Micro-
processor
Operating system
memory
Integral real-time
clock
Figure 2-1. Schematic Representation of the CP 523
8-byte
transfer
memory
Internal bus
Technical Description
S5 Bus
2-1