ID
Bit
Byte
No.
163
96
Output 1 - Action
164
97
Output 2 - Action (refer to Output 1 - Action) x
165
98
Output 3 - Action (refer to Output 1 - Action) x
166
99
Output 4 - Action
100 -
Reserved = 0
111
116
112
Breakaway time
117
113
Breakaway voltage
169
114 -
Maximum starting time
115
170
116 -
Starting time
117
171
118 -
Stopping time
119
172
120
Start torque
118
121
Limiting torque
173
122
Stopping torque
123
Reserved = 0
124
Reserved = 0
119
125
Motor thermal capacity
126 -
Reserved = 0
129
178
130
Dynamic braking torque
SIRIUS 3RW44 manual
GWA 4NEB 535 2195-02 DS 06
Meaning
PROFIBUS DP Communication Module
Only for
data set
Value range [coding]
131
x
• No action (default) [0]
• Control source PIO-DO 1.0
output 1 [1]
• Control source PIO-DO 1.1
output 2 [2]
• Control source input 1 [6]
• Control source input 2 [7]
• Control source input 3 [8]
• Control source input 4 [9]
• Run up [10]
• Operation / bridging [11]
• Stopping [12]
• On-time motor [13]
• Control command MOTOR ON
[14]
• Fan [15]
• DC braking contactor [16]
• Device - ON [18]
• Group warning [31]
• Group error [32]
• Bus error [33]
• Device error [34]
• Ready for motor on [38]
0 ... 2 s [0 ... 200]
40 ... 100 % [8 ... 20]
0 ... 1, 000 s [0 ... 10, 000]
0 ... 360 s [0 ... 3,600]
0 ... 360 s [0 ... 3,600]
10 ... 100 % [2 ... 20]
20 ... 200 % [4 ... 40]
10 ... 100 % [2 ... 20]
1 ... 100 % [1 ... 100]
20 ... 100 % [4 ... 20]
Factor
0.01 s
5 %
0.1 s
0.1 s
0.1 s
5 %
5 %
5 %
1 %
5 %