Et 200s distributed i/o power module dc24v (18 pages)
Summary of Contents for Siemens 6ES7521-1BL00-0AA0
Page 2
___________________ Preface ___________________ Documentation guide ___________________ SIMATIC Product overview ___________________ Wiring S7-1500/ET 200MP Digital input module ___________________ DI 32x24VDC BA Address space (6ES7521-1BL10-0AA0) ___________________ Diagnostics alarms Manual ___________________ Technical specifications ___________________ Dimensional drawing 12/2016 A5E32363711-AD...
Page 3
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept. Siemens’ products and solutions only form one element of such a concept. Customer is responsible to prevent unauthorized access to its plants, systems, machines and networks.
Page 5
We are liable for the product described, including the open-source software contained in it, pursuant to the conditions applicable to the product. Siemens accepts no liability for the use of the open source software over and above the intended program sequence, or for any faults caused by modifications to the software.
Documentation guide The documentation for the SIMATIC S7-1500 automation system, the CPU 1516pro-2 PN based on SIMATIC S7-1500 and the SIMATIC ET 200MP distributed I/O system is arranged into three areas. This arrangement enables you to access the specific content you require. Basic information The System Manual and Getting Started describe in detail the configuration, installation, wiring and commissioning of the SIMATIC S7-1500 and ET 200MP systems.
Page 8
You must register once to use the full functionality of "mySupport". You can find "mySupport" on the Internet (https://support.industry.siemens.com/My/ww/en). "mySupport" - Documentation In the Documentation area in "mySupport" you can combine entire manuals or only parts of these to your own manual.
Page 9
● Manuals, characteristics, operating manuals, certificates ● Product master data You can find "mySupport" - CAx data on the Internet (http://support.industry.siemens.com/my/ww/en/CAxOnline). Application examples The application examples support you with various tools and examples for solving your automation tasks. Solutions are shown in interplay with multiple components in the system - separated from the focus on individual products.
Page 10
You can find the SIMATIC Automation Tool on the Internet (https://support.industry.siemens.com/cs/ww/en/view/98161300). PRONETA With SIEMENS PRONETA (PROFINET network analysis), you analyze the PROFINET network during commissioning. PRONETA features two core functions: ● The topology overview independently scans PROFINET and all connected components.
Product overview Properties Part number: 6ES7521-1BL10-0AA0 View of the module Figure 2-1 View of the DI 32x24VDC BA module Properties The module has the following technical properties: ● 32 digital inputs; electrically isolated in groups of 16 ● Rated input voltage 24 VDC ●...
Page 12
● Front connector (push-in terminals) including cable tie ● Labeling strips ● U connector ● Universal front door You can find additional information on accessories in the S7-1500/ET 200MP (http://support.automation.siemens.com/WW/view/en/59191792) system manual. Digital input module DI 32x24VDC BA (6ES7521-1BL10-0AA0) Manual, 12/2016, A5E32363711-AD...
You can find information on wiring the front connector, creating a cable shield, etc. in the Wiring section of the S7-1500/ET 200MP (http://support.automation.siemens.com/WW/view/en/59191792) system manual. Wiring and block diagram The figure below shows you how to wire the module and the assignment of the channels to the addresses (input byte a to input byte d).
Address space Address space The module can be configured in various ways in STEP 7. Depending on the configuration, additional/different addresses are assigned in the process image of the inputs. Configuration options of DI 32x24VDC BA You can configure the module with STEP 7 (TIA Portal) or with a GSD file. When you configure the module by means of the GSD file, the configurations are available under different abbreviations/module names.
Page 15
Address space 4.1 Address space Address space for configuration as 1 x 32-channel DI 32x24VDC BA The figure below shows the address space assignment for configuration as a 1 x 32-channel module. You can freely assign the start address for the module. The addresses of the channels are derived from the start address.
Page 16
Address space 4.1 Address space Value status (Quality Information, QI) The meaning of the value status depends on the submodule involved. For the 1st submodule (=basic submodule), the value status is not relevant. For the 2nd to 4th submodule (=MSI submodule), the value status 0 indicates that the value is incorrect or the basic submodule has not yet been configured (not ready).
Page 17
You can find information on the module-internal shared input/shared output (MSI/MSO) function in the section Module-internal shared input/shared output (MSI/MSO) of the function manual PROFINET with STEP 7 V13 (https://support.industry.siemens.com/cs/ww/en/view/49948856). Digital input module DI 32x24VDC BA (6ES7521-1BL10-0AA0) Manual, 12/2016, A5E32363711-AD...
Diagnostics alarms The module has no selectable diagnostics. Diagnostics alarms, for example, cannot be output with STEP 7 (TIA Portal). Status and error displays LED displays The figure below shows you the LED displays (status and error displays) of the DI 32x24VDC BA.
Page 19
Diagnostics alarms 5.1 Status and error displays Meaning of the LED displays The tables below explain the meaning of the status and error displays. LED RUN/ERROR Table 5- 1 RUN/ERROR status and error displays Meaning Remedy ERROR Voltage missing or too low at backplane bus. Switch on the CPU and/or the system pow- •...
Technical specifications Technical specifications of the DI 32x24VDC BA 6ES7521-1BL10-0AA0 General information Product type designation DI 32x24VDC BA Hardware functional status FS01 Firmware version V1.0.0 FW update possible • Product function I&M data Yes; I&M0 to I&M3 Engineering with STEP 7 TIA Portal can be configured/integrated V13 / V13 as of version STEP 7 can be configured/integrated as of version V5.5 SP3 / -...
Page 21
Technical specifications 6ES7521-1BL10-0AA0 Input current for signal "1", typ. 2.7 mA Input delay (for rated value of input voltage) For standard inputs Configurable • 3 ms with "0" to "1", min. • 4 ms with "0" to "1", max. • 3 ms with "1"...
Page 22
Technical specifications 6ES7521-1BL10-0AA0 Electrical isolation of channels Between the channels Between the channels, in groups of Between the channels and backplane bus Between the channels and power supply of the electronics Isolation Isolation tested with 707 V DC (type test) Ambient conditions Ambient temperature during operation Horizontal mounting position, min.
Dimensional drawing The dimensional drawing of the module on the mounting rail, as well as a dimensional drawing with open front cover, are provided in this appendix. Always observe the specified dimensions for installation in cabinets, control rooms, etc. Figure A-1 Dimensional drawing of the DI 32x24VDC BA module Digital input module DI 32x24VDC BA (6ES7521-1BL10-0AA0) Manual, 12/2016, A5E32363711-AD...
Page 24
Index Figure A-2 Dimensional drawing of the DI 32x24VDC BA module, side view with open front cover Digital input module DI 32x24VDC BA (6ES7521-1BL10-0AA0) Manual, 12/2016, A5E32363711-AD...