4.2.9

Connecting the PROFINET interface

Industrial Ethernet Cables and cable length
Listed in the table below are the recommended Ethernet cables.
Table 4- 9
Industrial Ethernet FC TP
Standard Cable GP 2 x 2
Industrial Ethernet FC TP
Flexible Cable GP 2 x 2
Industrial Ethernet FC Trailing
Cable GP 2 x 2
Industrial Ethernet FC Trailing
Cable 2 x 2
Industrial Ethernet FC Marine
Cable 2 x 2
Cable screening
The screen of the PROFINET cable must be connected with the protective earth. The solid
copper core must not be scored when the insulation is removed from the core ends.
Converter with control units CU240D-2
Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA
Recommended PROFINET cables
Max. Cable Length
100 m (328 ft)
85 m (278 ft)
85 m (278 ft)
85 m (278 ft)
85 m (278 ft)
Installation
4.2 Electrical Installation
Order Number
6XV1840-2AH10
6XV1870–2B
6XV1870–2D
6XV1840–3AH10
6XV1840–4AH10