Page 2
___________________ Preface ___________________ Guide to documentation ___________________ SIMATIC Product overview ___________________ Wiring ET 200SP Analog input module ___________________ AI 8xRTD/TC 2-wire HF Parameters/address space (6ES7134-6JF00-0CA1) ___________________ Interrupts/diagnostics alarms Manual ___________________ Technical specifications ___________________ Parameter data record ___________________ Representation of analog values 09/2018 A5E32942580-AB...
Page 3
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Purpose of the documentation This manual supplements the system manual ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293). Functions that generally relate to the system are described in this manual. The information provided in this manual and in the system/function manuals supports you in commissioning the system.
Page 5
Siemens' products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customers' exposure to cyber threats.
Guide to documentation The documentation for the SIMATIC ET 200SP distributed I/O system is arranged into three areas. This arrangement enables you to access the specific content you require. Basic information The system manual describes in detail the configuration, installation, wiring and commissioning of the SIMATIC ET 200SP.
Page 8
You can download the product information free of charge from the Internet (https://support.industry.siemens.com/cs/us/en/view/73021864). Manual Collection ET 200SP The Manual Collection contains the complete documentation on the SIMATIC ET 200SP distributed I/O system gathered together in one file. You can find the Manual Collection on the Internet (http://support.automation.siemens.com/WW/view/en/84133942).
Page 9
● Manuals, characteristics, operating manuals, certificates ● Product master data You can find "mySupport" - CAx Data in the Internet (http://support.industry.siemens.com/my/ww/en/CAxOnline). Application examples The application examples support you with various tools and examples for solving your automation tasks. Solutions are shown in interplay with multiple components in the system - separated from the focus in individual products.
Page 10
You can find the SIMATIC Automation Tool on the Internet (https://support.industry.siemens.com/cs/ww/en/view/98161300). PRONETA With SIEMENS PRONETA (PROFINET network analysis), you analyze the plant network during commissioning. PRONETA features two core functions: ● The topology overview independently scans PROFINET and all connected components.
Page 11
Guide to documentation SINETPLAN SINETPLAN, the Siemens Network Planner, supports you in planning automation systems and networks based on PROFINET. The tool facilitates professional and predictive dimensioning of your PROFINET installation as early as in the planning stage. In addition, SINETPLAN supports you during network optimization and helps you to exploit network resources optimally and to plan reserves.
Product overview Properties Article number 6ES7134-6JF00-0CA1 View of the module ① ⑦ Module type and name Function class ② ⑧ LED for diagnostics Color coding module type ③ ⑨ 2D matrix code Function and firmware version ④ ⑩ Wiring diagram Color code for selecting the color identification labels ⑤...
Page 13
Product overview 2.1 Properties Properties The module has the following technical properties: ● Analog input module with 8 inputs ● Resolution: Up to 16 bits including sign ● Voltage measurement type can be set per channel ● Resistor measurement type can be set per channel ●...
Page 14
● Color identification labels ● Reference identification label ● Shield connection See also You can find additional information on the accessories in the ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293) system manual. Analog input module AI 8xRTD/TC 2-wire HF (6ES7134-6JF00-0CA1) Manual, 09/2018, A5E32942580-AB...
This section includes the block diagram of the AI 8xRTD/TC 2-wire HF module with the terminal assignments. You can find information on wiring the BaseUnit in the ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293) system manual. Note • The load group of the module must begin with a light-colored BaseUnit. Keep this in mind also during the configuration.
Page 16
Wiring 3.1 Wiring and block diagram Wiring: 2-wire connection for thermocouples, resistance-type sensors or thermal resistors (RTD) The following figure shows the block diagram and an example of the terminal assignment of the analog input module AI 8×RTD/TC 2-wire HF on the BaseUnit BU type A0/A1. ①...
Page 17
Wiring 3.1 Wiring and block diagram Analog input module AI 8xRTD/TC 2-wire HF (6ES7134-6JF00-0CA1) Manual, 09/2018, A5E32942580-AB...
Thermocouple (TC) Type E, N, J, K, L, S, R, B, T, C, U, TXK (acc. to GOST) For sensors LG-Ni 1000 from Siemens Building Ltd (Landis & Stäfa). Analog input module AI 8xRTD/TC 2-wire HF (6ES7134-6JF00-0CA1) Manual, 09/2018, A5E32942580-AB...
Page 19
Parameters/address space 4.1 Measurement types and measuring ranges Special features when using PTC resistors PTCs are suitable for monitoring temperature and as thermal protection devices for complex drives or transformer windings. ● Choose "Resistor (2-wire)" and "PTC" in the parameter assignment. ●...
Page 20
Parameters/address space 4.1 Measurement types and measuring ranges Assignment in the process image input (PII) with SIMATIC S7 Figure 4-1 Assignment in the process image input (PII) Notes on programming ● Bits 0+2 are relevant for evaluation in the process image input. You can monitor, for example, the temperature of a motor using bits 0+2.
Page 21
Parameters/address space 4.1 Measurement types and measuring ranges Example The diagram shows the temperature curve and the associated switching points. Figure 4-2 Temperature curve with prewarning range See also Technical specifications (Page 44) Analog input module AI 8xRTD/TC 2-wire HF (6ES7134-6JF00-0CA1) Manual, 09/2018, A5E32942580-AB...
Parameters/address space 4.2 Parameters Parameters Parameters of the AI 8xRTD/TC 2-wire HF Specify the module properties with the various parameters in the course of your STEP 7 configuration. The following table lists the configurable parameters. The effective range of the configurable parameters depends on the type of configuration. The following configurations are possible: ●...
Page 23
Parameters/address space 4.2 Parameters Parameters Value range Default Reconfigura- Scope with configuration tion in RUN software, e.g., STEP 7 (TIA Portal) GSD file GSD file PROFINET PROFIBUS Type/range of Thermal resistor (2- Channel Channel Deactivated • measurement wire connection) Voltage ±50 mV •...
Page 24
Parameters/address space 4.2 Parameters Parameters Value range Default Reconfigura- Scope with configuration tion in RUN software, e.g., STEP 7 (TIA Portal) GSD file GSD file PROFINET PROFIBUS Type/range of Thermal resistor (2-wire connec- Thermal resistor (2- Channel Channel measurement tion) wire connection) Pt 100 standard Ni 100 climatic range...
Page 25
Parameters/address space 4.2 Parameters Parameters Value range Default Reconfigura- Scope with configuration tion in RUN software, e.g., STEP 7 (TIA Portal) GSD file GSD file PROFINET PROFIBUS Temperature coef- Pt 0.00385055 Channel Channel Pt 0.00385055 • ficient Pt 0.003916 • Pt 0.003902 •...
Page 26
Parameters/address space 4.2 Parameters Parameters Value range Default Reconfigura- Scope with configuration tion in RUN software, e.g., STEP 7 (TIA Portal) GSD file GSD file PROFINET PROFIBUS High limit 1 8500 Channel Value • Hardware interrupt Disable Channel Disable • low limit 1 Enable •...
Parameters/address space 4.3 Explanation of parameters Explanation of parameters Diagnostics: Missing supply voltage L+ Enabling of the diagnostics for missing or insufficient supply voltage L+. Diagnostics: Reference junction Enabling of the reference junction diagnostics if the reference temperature of the reference junction needs to be determined for the TC channel being operated.
Page 28
Parameters/address space 4.3 Explanation of parameters Reference junction using the PROFIBUS GSD file A BaseUnit with an internal temperature sensor (BU..T), the reference channel of group 0, 1, 2, 3, or channel 0 of the I/O module can be used as reference junction for the TC measurement, if this has the parameter setting "Thermal resistor Pt100 climatic range Degrees Celsius".
Page 29
Parameters/address space 4.3 Explanation of parameters Diagnostics: Overflow Enabling of the diagnostics when the measured value exceeds the overrange. Diagnostics: Underflow Enabling of the diagnostics if the measured value falls below the underrange. Diagnostics: Wire break Enabling of the diagnostics if the module has no current flow or the current is insufficient for measurement at the correspondingly assigned input.
Page 30
Parameters/address space 4.3 Explanation of parameters Smoothing The individual measured values are smoothed using filtering. The smoothing can be set in 4 levels. Smoothing time = number of module cycles (k) x cycle time of the module. The following figure shows how many module cycles it takes for the smoothed analog value to approach 100%, depending on the configured smoothing.
Page 31
Parameters/address space 4.3 Explanation of parameters Measuring range center Determines the temperature over which the scalable measuring range is symmetrically spanned. The value must be within the nominal range of the underlying measuring range. It is specified in integers. Maximum / Minimum Corresponds to overflow / underflow for the scalable measuring range.
Parameters/address space 4.4 Scalable measuring range Scalable measuring range Introduction The scalable measuring range is available for the temperature measuring ranges of thermal resistors (RTD) standard and thermocouples. The measuring ranges for voltage, resistor and thermal resistor climatic are not supported. The scalable measuring range is valid for the following ranges: ●...
Page 33
Parameters/address space 4.4 Scalable measuring range Rules ● The measuring range center must be within the nominal range of the underlying measuring range. It is specified in integers. ● The scalable measuring range is spanned symmetrically over the measuring range ①...
Parameters/address space 4.4 Scalable measuring range 4.4.1 Configuration Requirement You must select a valid temperature measuring range for configuration. Configuration The function is activated using the "Scalable measuring range" parameter. The following figure shows an example of a configuration in STEP 7: Figure 4-5 Configuration for the scalable measuring range Reference...
Parameters/address space 4.4 Scalable measuring range 4.4.2 Evaluating data record 235 Evaluation in the user program In the user program, you can evaluate the status and the limits of the scalable measuring range with data record 235, which may result by reaching underflow/overflow. Structure of data record 235 Figure 4-6 Structure of data record 235...
Page 36
Parameters/address space 4.4 Scalable measuring range Header information The figure below shows the structure of the header information. Figure 4-7 Header information of data record 235 Parameters The figure below shows the structure of the parameter. If the corresponding bit is set to "1", the parameter is activated. * x = 2 + (channel number x 8) Figure 4-8 Structure of data record 235 - channel parameter byte x to x+7...
Page 37
Parameters/address space 4.4 Scalable measuring range Description of the parameters Table 4- 9 Description of the parameters from data record 235 Parameter Description Scalable measuring range enabled 1 = Function is active for this channel. Clipping 1 = Scalable measuring range cut off at the overflow / under- flow of the underlying measuring range (see Figure (Page 32)).
Parameters/address space 4.5 Address space Address space Address space of the analog input module AI 8×RTD/TC 2-wire HF The following figure shows the assignment of the address space with value status (Quality Information (QI)). The addresses for the value status are only available if the value status is enabled.
Interrupts/diagnostics alarms Status and error displays LED displays The figure below shows the LED displays of the AI 8xRTD/TC 2-wire HF: ① DIAG (green/red) ② Channel status (green) ③ Channel error (red) ④ PWR (green) Figure 5-1 LED display Meaning of the LED displays The following tables contain the meaning of the status and error displays.
Page 40
Interrupts/diagnostics alarms 5.1 Status and error displays Channel status/channel error LED Table 5- 2 Status and error display of the LED channel status / channel error LEDs Meaning Channel status Channel error Channel deactivated Channel activated and no channel diagnostics Channel activated and channel diagnostics Not permitted (error) PWR LED...
Interrupts/diagnostics alarms 5.2 Interrupts Interrupts Evaluating hardware interrupts with IO controller The module generates a hardware interrupt at the following events: ● Violation of low limit 1 ● Violation of high limit 1 ● Violation of low limit 2 ● Violation of high limit 2 You can obtain detailed information on the event in the hardware interrupt organization block with the "RALARM"...
Page 42
Interrupts/diagnostics alarms 5.2 Interrupts Structure of the additional interrupt information Table 5- 4 Structure of the additional interrupt information Data block name Content Comment Bytes W#16#0001 additional interrupt information for hardware (User Structure Identifier) interrupts of the I/O module Channel that triggered the hardware interrupt. Channel B#16#00 to B#16#07 Channel 0 to 7 of the I/O module...
Interrupts/diagnostics alarms 5.3 Diagnostics alarms Diagnostics alarms A diagnostics alarm is generated and the DIAG-LED flashes on the module for each diagnostics event. You can read out the diagnostics alarms, for example, in the diagnostics buffer of the CPU. You can evaluate the error codes with the user program. Table 5- 5 Diagnostics alarms, their meaning and remedies Diagnostics alarms...
Page 44
Interrupts/diagnostics alarms 5.3 Diagnostics alarms Diagnostics alarms Error code Meaning Remedy Hardware interrupt lost At least one hardware interrupt could not Correct the program or the process be reported because there were too many pending hardware interrupts. Channel temporarily Firmware update in progress or up- Wait for firmware update.
Technical specifications Technical specifications of the AI 8xRTD/TC 2-wire HF The following table shows the technical specifications as of 09/2018. You will find a data sheet including daily updated technical specifications on the Internet (https://support.industry.siemens.com/cs/ww/en/pv/6ES7134-6JF00-0CA1/td?dl=en). Article number 6ES7134-6JF00-0CA1 General information...
Page 46
Technical specifications Article number 6ES7134-6JF00-0CA1 Power loss Power loss, typ. 0.75 W Address area Address space per module 16 byte; + 1 byte for QI information Address space per module, max. • Analog inputs Number of analog inputs For voltage measurement •...
Page 47
Technical specifications Article number 6ES7134-6JF00-0CA1 Input ranges (rated values), thermocouples Yes; 16 bit incl. sign Type B • 1 MΩ Input resistance (Type B) • Yes; 16 bit incl. sign Type C • 1 MΩ Input resistance (Type C) • Yes;...
Page 48
Technical specifications Article number 6ES7134-6JF00-0CA1 Input ranges (rated values), resistance thermome- Yes; 16 bit incl. sign Ni 100 • 1 MΩ Input resistance (Ni 100) • Yes; 16 bit incl. sign Ni 1000 • 1 MΩ Input resistance (Ni 1000) •...
Page 49
Technical specifications Article number 6ES7134-6JF00-0CA1 Thermocouple (TC) Temperature compensation – parameterizable – Reference channel of the module Yes; with BaseUnit type A1 – internal comparison point – Reference channel of the group 4; Group 0 to 3 – Number of reference channel groups –...
Page 50
Technical specifications Article number 6ES7134-6JF00-0CA1 Errors/accuracies Linearity error (relative to input range), (+/-) 0.01 %; ±0.1 % for resistance thermometers and resistance Temperature error (relative to input range), (+/- 0.0009 %/K; ±0.005 % / K at thermocouple Crosstalk between the inputs, min. -50 dB Repeat accuracy in steady state at 25 °C (rela- 0.05 %...
Page 51
Technical specifications Article number 6ES7134-6JF00-0CA1 Diagnostics indication LED Yes; green PWR LED Monitoring of the supply voltage (PWR- • LED) Yes; Green LED Channel status display • Yes; Red LED for channel diagnostics • Yes; green/red DIAG LED for module diagnostics •...
Page 52
Thermocouple type B: +700 °C Thermocouple type N: -150 °C Thermocouple type E: -150 °C Thermocouple type R: +200 °C Thermocouple type S: +100 °C Dimension drawing See manual ET 200SP BaseUnits (http://support.automation.siemens.com/WW/view/en/59753521) Analog input module AI 8xRTD/TC 2-wire HF (6ES7134-6JF00-0CA1) Manual, 09/2018, A5E32942580-AB...
Parameter data record Dependencies when configuring with GSD file When configuring the module with a GSD file, remember that the settings of some parameters are dependent on each other. Configuring with a PROFINET GSD file The table lists the properties and their dependencies on the measurement type and measuring range for PROFINET.
Page 54
Parameter data record A.1 Dependencies when configuring with GSD file Measure- Measuring range Temperature coef- Reference junction Temperature unit Conductor re- ment type ficient sistance Thermal Pt100 Pt 0.00385055 No reference chan- Degrees Celsius resistor Pt200 Pt 0.003916 nel mode Degrees Fahrenheit Pt500 Pt 0.003902...
Page 55
Parameter data record A.1 Dependencies when configuring with GSD file Configuring with a PROFINET GSD file The table lists the properties and their dependencies on the measurement type for PROFINET. Table A- 2 Dependencies on the measurement type Measure- Scalable Measuring Diagnostics ment type...
Page 56
Parameter data record A.1 Dependencies when configuring with GSD file Meas- Measuring Tempera- Slot refer- Tempera- Diagnostics urement range ture coeffi- ence junc- ture unit Underflow / Wire break Missing Reference type cient tion overflow supply junction voltage L+ Pt 0.00392 No refer- Degrees –...
Page 57
Parameter data record A.1 Dependencies when configuring with GSD file Meas- Measuring Tempera- Slot refer- Tempera- Diagnostics urement range ture coeffi- ence junc- ture unit Underflow / Wire break Missing Reference type cient tion overflow supply junction voltage L+ Thermo- Type B, N, Reference Degrees...
Parameter data record A.2 Parameter assignment and structure of parameter data record Parameter assignment and structure of parameter data record The data record of the module has an identical structure, regardless of whether you configure the module with PROFIBUS DP or PROFINET IO. With data record 128, you can reconfigure the module in your user program regardless of your programming.
Page 59
Parameter data record A.2 Parameter assignment and structure of parameter data record Structure of data record 128 Figure A-1 Structure of data record 128 Header information The figure below shows the structure of the header information. Figure A-2 Header information Analog input module AI 8xRTD/TC 2-wire HF (6ES7134-6JF00-0CA1) Manual, 09/2018, A5E32942580-AB...
Page 60
Parameter data record A.2 Parameter assignment and structure of parameter data record Parameters The figure below shows the structure of the parameters for channels 0 to 7. You can activate a parameter by setting the corresponding bit to "1". * x = 2 + (channel number x 22); channel number = 0 to 7 Analog input module AI 8xRTD/TC 2-wire HF (6ES7134-6JF00-0CA1) Manual, 09/2018, A5E32942580-AB...
Page 61
Parameter data record A.2 Parameter assignment and structure of parameter data record Analog input module AI 8xRTD/TC 2-wire HF (6ES7134-6JF00-0CA1) Manual, 09/2018, A5E32942580-AB...
Page 62
Parameter data record A.2 Parameter assignment and structure of parameter data record Figure A-3 Structure of byte x to x+21 for channel 0 to 7 Codes for measurement type The following table contains the codes for the measurement types of the analog input module.
Page 63
Parameter data record A.2 Parameter assignment and structure of parameter data record Measuring range Code Thermal resistor climatic Pt 100 0000 0000 Pt 200 0000 0111 Pt 500 0000 1000 Pt 1000 0000 1001 Thermal resistor standard Pt 100 0000 0010 Pt 200 0000 1011 Pt 500...
Page 64
Parameter data record A.2 Parameter assignment and structure of parameter data record Codes for temperature coefficient The following table contains the codes for the temperature coefficients of the analog input module. You must enter these codes at byte x+2 (see previous figure). Table A- 5 Codes for temperature coefficient for temperature measurement Temperature coefficient...
Page 65
Parameter data record A.2 Parameter assignment and structure of parameter data record Table A- 8 Limits for thermocouple types R, S, J, and L Thermocouple Types R, S Type J Type L °C °F °C °F °C °F 20189 32765 22921 14499 26419...
Parameter data record A.3 Errors when transferring the data record Errors when transferring the data record Error transferring the data record The module always checks all values of the data record to be sent. The module applies the values from the data record only when all values have been transmitted without errors. The WRREC instruction for writing data records returns corresponding error codes when errors occur in the STATUS parameter, see also the description of the "STATUS"...
Parameter data record A.4 Switchable wire break check Switchable wire break check Function The "Switchable wire break check" is available for thermocouples. It switches off the wire break check for the module. This is required, for example, to calibrate thermocouples, since the test current necessary for a wire break check leads to measurement errors during calibration.
Representation of analog values This appendix shows the analog values for all measuring ranges supported by the analog input module AI 8xRTD/TC 2-wire HF. Measured value resolution The resolution of the analog values differs depending on the analog module and its parameter assignment.
Representation of analog values B.1 Representation of input ranges Representation of input ranges In the following tables, you can find the digitized representation of the bipolar and unipolar input ranges. The resolution is 16 bits. Table B- 2 Bipolar input ranges Dec.
Representation of analog values B.2 Representation of analog values in voltage measuring ranges Representation of analog values in voltage measuring ranges The following tables list the decimal and hexadecimal values (codes) of the possible voltage measuring ranges. Table B- 4 Voltage measuring range ±1 V Values Voltage measuring range...
Representation of analog values B.3 Representation of analog values for resistance-type sensors Representation of analog values for resistance-type sensors The following tables list the decimal and hexadecimal values (codes) of the possible resistance-type sensors. Table B- 6 Resistance-type sensors from 150 Ω to 6000 Ω Values Resistance-type sensor range Range...
Representation of analog values B.4 Representation of analog values for thermal resistors Representation of analog values for thermal resistors Note A higher resolution can be configured for the measuring range for the standard thermal resistors, see section Scalable measuring range (Page 31). The tables below list the decimal and hexadecimal values (codes) of the thermal resistors.
Page 73
Representation of analog values B.4 Representation of analog values for thermal resistors Table B- 9 Thermal resistor Ni 100, 120, 200, 500, 1000, LG-Ni 1000 standard Ni x00 Values Ni x00 Values Ni x00 Values Range standard in standard in standard in Dec.
Representation of analog values B.5 Representation of analog values for thermocouples Representation of analog values for thermocouples Note A higher resolution can be configured for thermocouples, see section Scalable measuring range (Page 31). The tables below list the decimal and hexadecimal values (codes) of the thermocouples. Table B- 11 Thermocouple type B Type B...
Page 75
Representation of analog values B.5 Representation of analog values for thermocouples Table B- 13 Thermocouple type E Type E Values Type E Values Type E Values Range in °C in °F in K Dec. Hex. Dec. Hex. Dec. Hex. > 1200.0 32767 7FFF >...
Page 76
Representation of analog values B.5 Representation of analog values for thermocouples Table B- 16 Thermocouple type L Type L Values Type L Values Type L Values Range in °C in °F in K Dec. Hex. Dec. Hex. Dec. Hex. > 1150.0 32767 7FFF >...
Page 77
Representation of analog values B.5 Representation of analog values for thermocouples Table B- 19 Thermocouple type T Type T Values Type T Values Type T Values Range in °C in °F in K Dec. Hex. Dec. Hex. Dec. Hex. > 540.0 32767 7FFF >...