Summary of Contents for Siemens SITRANS MAG 6000 I
Page 1
Introduction Safety notes Description SITRANS F Installing/Mounting Electromagnetic flowmeters SITRANS MAG 6000 I/6000 I Ex de Connecting Commissioning Operating Instructions Functions Alarm, error, and system messages Service and maintenance Troubleshooting/FAQs Technical data Spare parts/Accessories Menu diagrams Factory settings 7ME693 (MAG 6000 I)
Page 2
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Pipe or wall mounting with assembly bracket................27 Connecting..............................29 Safety precautions.........................30 Electrical connection......................31 Connection of sensor and transmitter in remote version............34 Wiring in hazardous area.......................37 Connection of bus communication add-on modules..............38 Reassembling the device.......................38 SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Page 4
Technical data............................65 11.1 Technical specifications......................65 11.2 Dimensions and weight......................67 11.3 Accuracy..........................68 11.4 Output characteristics......................69 11.5 Cable data..........................71 11.6 Cable requirements........................72 Spare parts/Accessories..........................73 12.1 Ordering of spare parts......................73 12.2 Accessories..........................73 SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Page 5
50 Hz Dimension dependent Qmax..................91 60 Hz Dimension dependent Qmax..................92 50 Hz Dimension dependent volume/pulse and batch............94 60 Hz Dimension dependent volume/pulse and batch............95 Control drawing............................97 Control drawing........................97 Index.................................103 SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Page 6
Table of contents SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
The following table lists the most important changes made to the documentation in the current and previous editions. Edition Remarks HW version SW version 08/2018 4.08 X06 ● Updated Safety Notes 04/2016 4.08 X06 ● Various technical specifications updated ● Control drawing updated SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
2. Make sure the scope of delivery, and the information on the namelate corresponds to the ordering information SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Product information on the Internet The Operating Instructions are available on the documentation disk shipped with the device, and on the Internet on the Siemens homepage, where further information on the range of SITRANS F flowmeters may also be found: Product information on the internet (http://www.siemens.com/flowdocumentation)
Page 10
Introduction 1.5 Further Information SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
● Altitude up to 2000 m ● Maximum relative humidity 80% for temperatures up to 31°C (88 °F) decreasing linearly up to 50% relative humidity from 40 °C (104 °F) SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Material compatibility Siemens Flow Instruments can provide assistance with the selection of wetted sensor parts. However, the full responsibility for the selection rests with the customer and Siemens Flow Instruments can take no responsibility for any failure due to material incompatibility.
These markings are for the Remote version only; the marking applicable to the Compact versions depend upon their construction. See the latest issues of certificates Sira 07ATEX3181X, Sira 07ATEX1182X and Sira 03ATEX3339X. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Page 14
Sensor electrode input (Terminals 0, 81, 82, 83, 84 - "ia circuits") 30 V DC 30 V DC 6.1 mA 6.1 mA 560 nF 66 nF 0.96 H 45.5 mW 45.5 mW SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Page 15
0 nF 36 µH 18.4 mH 4.6 mH 0 µH 36 µH 0 µH 0 µH 0.7 W 0.66 W 0.61 W 1.2 W 1.2 W 5.32 W 1.2 W SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Page 16
● sensor and transmitter are connected to the potential equalizing conductor. ● when protective earth (PE) is connected, no potential difference between the protective earth (PE) and the potential equalization (PA) can exist, even during a fault condition. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
0 nF 36 µH 18.4 mH 4.6 mH 0 µH 36 µH 0 µH 0 µH 0.7 W 0.66 W 0.61 W 1.2 W 1.2 W 5.32 W 1.2 W SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
3. Conduit seal is required within 460 mm (18") from MAG 6000 I in hazardous areas (Class I, Div. 1). The control drawings are found on the CD-ROM shipped with the device and on the Siemens homepage at http://www.siemens.com/flowdocumentation. See also...
The SITRANS F M platform enables fitting of add-on bus modules without loss of analog, pulse and relay outputs, and all modules can be fitted as true Plug & Play. Standard transmitter: ● HART ● PROFIBUS PA and DP SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
● Low flow cut-off ● Analog, pulse/frequence and relay outputs ● Optional: additional digital communication modules ● Error and error log system ● Uni-/bidirectional flow ● Limit switches ● Integrated batch control SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
The output module converts flow data to analog, digital and relay outputs. The outputs are galvanically isolated and can be individually set to suit a particular application. Theory of operation The flow measuring principle is based on Faraday’s law of electromagnetic induction. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Page 22
23 bit signal resolution. This has eliminated the need for range switching. The dynamic range of the transmitter is therefore unsurpassed with a turn down ratio of minimum 3000:1. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
As the transmitter housing and the display can be oriented in all directions, reading and operating the flowmeter is possible under almost any installation conditions. 360° To ensure optimum flow measurement, attention should be paid to the following: SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
The SENSORPROM is factory-mounted in the transmitter. ® Figure 4-2 Compact installation Note To avoid too high tension on small sizes MAG 1100 sensors, transmitter must be supported. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Cable length and type (as described in Cable requirements (Page 72)) must be used. For installation conditions for sensors, see respective sensor operating instructions. 1. Remove sensor terminal box lid. 2. Remove SENSORPROM unit from sensor terminal box. ® SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Page 26
Electrode cable and coil cable must be kept separate to prevent interference. 6. Tighten cable glands and lid screws well to obtain optimum sealing. WARNING Mount terminal box lid before power up. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Pipe or wall mounting with assembly bracket Optional pipe or wall mounting assembly bracket Note The assembly bracket is not part of the standard delivery and must be ordered separately. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Page 28
2. Fasten the transmitter and assembly bracket to the wall Note The fastening brackets and nuts are not needed for wall mounting. Wall mounting with assembly bracket. Dimensions in mm (inch). SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Cable loops in the terminal box must be avoided. ● To guarantee the IP 67/NEMA 4 degree of protection, use cables with external diameters matching the used cable glands. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
35 A. WARNING Danger of electric shock Do not power up when lid is open. Do not open lid while power is on, unless operating in an Ex ia environment. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Connecting 5.2 Electrical connection Electrical connection Ω Ω Ω Ω Electrical connection label The electrical connection label is placed in the lid of the terminal box. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Page 32
Exception are sensor connections that are connected to ground. WARNING Grounding The mains protective earth wire must be connected to the PE terminal in accordance with the diagram (Protection class I). SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Page 33
Non-Ex versions can be connected as either active or passive. Note The factory default setting for the current output is marked by an "X" and can be found on a label on the back of the lid. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
® WARNING Danger of electric shock Do not power up when lid is open. Do not open lid while power is on, unless operating in an Ex ia environment. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Page 35
® 2. Fit coil and electrode cables through cable glands in sensor terminal box. 3. Connect signal and coil cables to transmitter as follows: SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Page 36
Avoid exposing transmitter to direct sunlight Exposing the transmitter to direct sunlight may increase the operating temperature above its specified limit, and decrease display visibility. In such case, protect the transmitter from direct sunlight. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
= Σ R = Σ R < < Loop max Loop max - Loop - Loop Current output active with and without HART Barrier / Isolator < 650Ω SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
91-97. For more information Refer to the relevant BUS communication Quick Start or Operating Instructions available at the SITRANS F literature CD or on the internet, at: www.siemens.com/flowdocumentation (www.siemens.com/flowdocumentation) Reassembling the device Ensure that the two screws (20 TORX) are tightened properly for correct assembly and proper ground connection.
Page 39
Connecting 5.6 Reassembling the device Ensure sufficient insulation by covering power supply terminals with plastic cover. Fasten the plastic cover with two screws. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Page 40
Connecting 5.6 Reassembling the device SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Local user interface With the capacitive touch keypad the device can be operated without opening the lid. An LED light gives feedback on accepted command. Figure 6-1 Local user interface SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Page 42
FORWARD KEY This key is used to step forward through the menus. It is the only key normally used by the operator. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
1. Press top up key for 2 sec. 2. Enter password. 3. Use forward key or backward key to reach password menu. 4. Press lock/unlock key to unlock password. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Setting of velocity unit per time unit Error level Selecting error level at which flowmeter will detect an error. Note Totalizer 2 is not visible when batch is selected as digital output. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Page 45
6. Press lock/unlock key to unlock settings. 7. Use select key and change key to change settings. 8. Press lock/unlock key to confirm new settings. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Page 46
− − − − − − − Decimal point can be positioned and units set individually for flow rate in totalizer 1 and totalizer SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
4. Use change key to select requested reading. 5. Press lock/unlock key to confirm selection. 6. Use select key to move cursor to line 3. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
5. Use change key to select desired language. 6. Press lock/unlock key to confirm new language. 7. Press top up key two times to exit setup mode. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
3.5 mA High 22.6 mA For setting of error level, see Error level menu diagram (Page 79). If current output is not used, it must be set to "Off". SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
By applying 11 … 30 V DC to terminals 77 and 78, it is possible to perform: ● Batch control (start, stop, hold/continue) ● Reset totalizer ● Force/freeze output ● Q 2 (night) See external input menu diagram (Page 82). SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
It is possible to check whether the outputs are functioning. Error pending and status log lists are also accessible from this menu and the operating time (in days) can be read. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Page 52
Functions 7.6 Service mode The forced control is stopped and all previous settings are reinitialized the moment the service mode is left by pressing top up key SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
The acceptance level for "error pending" can be individually configured to a particular application. The acceptance level is set in the basic settings menu (Page 44). SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Page 54
The alarm field, error output and error pending always operate together. Operator menu Error pending and status log are as default enabled ( ) in the operator menu. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Switch off and on A parameter is out of range. The parameter could not Active Active be replaced by its default value. The error will disap‐ pear at the next power-on SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Page 56
Active ® unit anymore F70 - Coil current Check cables Coil excitation has failed Active Active F71 - Internal error Replace transmitter Internal conversion error in ASIC Active Active SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
● Seal integrity of the process connections, cable entries, and cover screws ● Reliability of power supply, lightning protection, and grounds NOTICE Repair and service must be carried out by Siemens authorized personnel only. Note Siemens defines flow sensors as non-repairable products.
● Information about field service, repairs, spare parts and lots more under Services. Additional Support If you have additional questions about the device, please contact your local Siemens representative and offices at: Local contact person (http://www.automation.siemens.com/aspa_app/contactmenu.aspx? ci=yes®id=DEF&lang=en)
Page 59
You can find the forms on the Internet and on the CD delivered with the device. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Page 60
Service and maintenance 9.4 Return procedures SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Ensure sufficient potential equalization tween medium and sensor 4. Air bubbles in medium Ensure medium does not contain air bubbles 5. High concentration of parti‐ Increase time constant cles or fibres SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Display light on? Yes ⇒ 1 No ⇒ 2 Flashing error triangles? Yes ⇒ Check error table No ⇒ 1.2 Output and display readings OK? Yes ⇒ 1.2.1 No ⇒ 1.2.2 SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Page 63
No ⇒ 2.1.2. 2.1.1 Display defective Replace display 2.1.2 Transmitter defective Replace transmitter Note Sensor check list Check lists for sensors are included in the respective sensor operating instructions. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Page 64
Troubleshooting/FAQs 10.2 Transmitter check list SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Exceptions are sensor connections that are connected to ground. Max. measuring error MAG 6000 I/MAG 6000 I Ex de ±0.2% ± 1 mm/s (incl. sensor and zero point) SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Page 66
Ex d e [ia] ia IIC T6 Gb Ex tD A21 IP67 T85°C Ta -25°C to +60°C FM Class I, II, III, Div 1 FM Class I, Zone 1/21 CSA Class I, Zone 1/21 SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Dimensions and weight Transmitter IP67/NEMA 4X compact die cast aluminum Figure 11-1 Transmitter dimensions shown in mm (inch) Weight: MAG 6000 I/MAG 6000 I Ex de: 6 kg (13.5 lbs) SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
As pulse output ± (0.1% of actual flow + 0.05% FSO) Effect of ambient temperature Display/frequency/pulse output < ± 0.003% / °C act. Current output < ± 0.005% / °C act. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Additions in the event of deviations from reference conditions 11.4 Output characteristics Current output Output characteristics Bidirectional mode Unidirectional mode 4 to 20 mA Frequency output Bidirectional mode Unidirectional mode Pulse output Bidirectional mode Unidirectional mode SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Page 70
Error relay output Bidirectional mode Unidirectional mode No error Error Limit switch (can be used as direction switch) 1 set point 2 set points Passive Digital output Passive Digital output SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Electrode cable, double shielded (for empty pipe detection or low conductivity fluids) Cable kit with standard coil cable and electrode cable double shielded (also available as low noise cable for MAG 1100 sensor) SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
For Ex zone 1 installations only certified cable glands with protection type "e" can be used for the power supply and the coil cable. The cable glands must be approved for the actual temperature and cable dimension. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
6000 I / MAG 6000 I Ex de HART FDK-085U0321 Modbus RTU/RS485 FDK-085U0234 PROFIBUS PA Profile 3 FDK-085U0236 PROFIBUS DP Profile 3 FDK-085U0237 Devicenet FDK-085U0229 FOUNDATION Fieldbus H1 A5E02054250 SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Display unit FDK-085U3122 Electronics cover with Ex glass plate A5E02593565 Cover for connection board incl. gas‐ 7ME5933-0AC02 ket (for remote version) Cover for mains supply/communica‐ 7ME5933-0AC03 tion including gasket SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Menu diagrams Transmitter menu overview The menu diagrams shown on the following pages apply to MAG 5000/6000 as well as MAG 6000 I. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Page 76
Menu diagrams A.1 Transmitter menu overview Not available in MAG 5000 Add-on module Factory-set password: 1000 Not available when batch Only available when batch SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
PDM or ordered by using the Z-option Y20 in the ordering system. The customer unit in the time unit list is displayed as "?". Via PDM or Y20 option this could e.g. be chosen as year "y". SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Do not combine differentiation and low alarm level together with passive output. The output will try to pull down the level to 1.3 mA at fatal errors which is not possible for passive output. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Menu diagrams A.6 Error level Digital output - pulse Digital output - frequency Error level SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
If digital output is set up for pulse, frequency or batch, then the relay output will be turned off if it has been set up for batch. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
(The display is locked during this time). The time cycle can be set at 1 to 240 hours. If the cycle is set at for example three hours, the transmitter will be active every three hours. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
In this case the power must be switched off/on to suppress the P40 error on the output. The frequency can be set to 44 Hz in the MAG 6000 SV transmitter only. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
9 is the best signal measured. If digital output is set to pulse (standard). If digital output is set to frequency. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
2 and flow velocity is chosen in line 3, the text "Flow velocity " is shown in line2 and the measured flow velocity is shown in line 3. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Menu diagrams A.16 Add-on communication module A.16 Add-on communication module Example: HART Note Burst mode is not available with HART communication SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
0 to 9.9% Empty pipe On, Off Velocity unit m, mm, cm, dm, ft , in per s, min, h, d, ? (customer unit) Error level Warning Fatal, permanent, warning SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Page 90
0.85 to 2.00 Sensor charac‐ teristics teristics (Page 83) Language Language English English, German, French, Danish, Swedish, Fin‐ Changing lan‐ nish, Spanish, Russian, Italian, Portuguese, Pol‐ guage (Page 48) SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
1244.881 US GPM 125 (5) 44.05714 1762.285 48.62819 1945.127 US GPM 150 (6) 1101 69.32434 2772.973 70.02459 2800.984 US GPM 200 (8) 1762 109.7986 4391.941 124.48819 4979.525 US GPM SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
Page 93
3000 (120) 308201 28009.84 1120393 US GPM * Factory setting sets Qmax to a metric unit (see previous table). The values here are converted to rounded off US GPM. SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...
1500 (60) 1.472622 l 38603.89 m 1600 (66) 1.675517 l 43922.64 m 1800 (72) 2.120576 l 55589.6 m 2000 (78) 2.617994 l 68629.13 m 2200 (90) 3.167773 l 83041.25 m SITRANS MAG 6000 I/6000 I Ex de Operating Instructions, 08/2018, A5E02083319-AH...