Table 5- 41
P1200
0
1
2
3
4
5
6
Table 5- 42
Parameter Description
P1202 =
...
P1203 =
...
Note
The higher the search rate (P1203), the longer the search time. The lower the search rate,
the shorter the search time.
The "flying restart" function decelerates the motor slightly. The smaller the drive torque, the
more the drive is decelerated.
The "flying restart" function should not be activated for motors in group drives due to the
different coasting characteristics of the individual motors.
Frequency inverter
Operating Instructions, 08.10. 2008, t.b.d.
Overview: the "flying restart" function
Flying restart active
Flying restart inactive (factory setting) -
Flying restart always active
Flying restart active after:
Power ON
•
Faults
•
OFF2
•
Flying restart active after:
Faults
•
OFF2
•
Flying restart always active
Flying restart active after
Power ON
•
Faults
•
OFF2
•
Flying restart active after
Faults
•
OFF2
•
Additional commissioning parameters
Motor current: flying restart
(entered in %): 10 % ... 200 %, factory setting 100 %
Defines the search current with respect to the rated motor current (P0305) that is
present when the "flying restart" function is used.
Search rate/speed: Flying restart
(entered in %): 10 % ... 200 %, factory setting 100 %
Sets the factor by which the output frequency changes during the flying restart to
synchronize itself with the running motor.
5.10 Technological functions
Search direction
Search performed in both directions, startup in
direction of setpoint
Search performed in both directions, startup in
direction of setpoint
Search performed in both directions, startup in
direction of setpoint
Search performed in direction of setpoint only
Search performed in direction of setpoint only
Search performed in direction of setpoint only
Functions