Step: Setting Parameters - Siemens Simatic S7-300 31xC Series Getting Started Manual

Positioning with digital output
Table of Contents

Advertisement

3.3

3. Step: Setting parameters

Procedure
1. Open your project in SIMATIC Manager.
2. In your project, call the configuration table HW Config.
3. Double-click on the submodule "Positioning".
4. Select "Positioning with digital outputs".
5. On the drive, axis and encoder tabs, customize the settings according to your system.
6. Confirm your settings with "OK".
7. Save your configuration to your project with "Station > Save and compile".
First Steps in Commissioning CPU 31xC: Positioning with digital output
Getting Started, 08/2011, A5E00105533-03
A window, divided into two sections, opens showing the title of your project.
The "Positioning properties" dialog opens.
The "Positioning properties" dialog closes.
Note
The input and output address of the submodules "DI24/DO16", "AI5/02", "Counting" and
"Positioning" must be adapted for the example to function correctly.
Double-click the relevant line to adapt the submodule. A dialog opens. Select the
"Addresses" tab in each case. Deselect the "System default" checkboxes. Change the
addresses as follows:
 DI24/DO16: Inputs: 124..126, Outputs: 124..125
 AI5/AO2: Inputs: 752..761, Outputs: 752..755
 Counting: Inputs: 768..783, Outputs: 768..783
 Positioning: Inputs: 784..799, Outputs: 784..799
Confirm your settings with "OK".
Your changes are now stored in your project.