Device configuration
4.6 Configuring the parameters of the modules
4.6
Configuring the parameters of the modules
To configure the operational parameters for the modules, select the module in the Device
view and use the "Properties" tab of the inspector window to configure the parameters for the
module.
Configuring a signal module (SM) or a signal board (SB)
Digital I/O: Inputs can be configured for rising-edge
Analog I/O: For individual inputs, configure
I/O diagnostic addresses: Configures the start address for the set of inputs and outputs
Configuring a communication module (CM)
Port configuration: Configures the communication
Transmit message configuration: Enables and
Receive message configuration: Enables and
These configuration parameters can be changed by your program.
74
detection or falling-edge detection (associating
each with an event and hardware interrupt) and
also for "pulse catch" (to stay on after a momentary
pulse) through the next update of the input process
image. Outputs can use a freeze or substitute
value.
parameters, such as measurement type (voltage or
current), range and smoothing, and to enable
underflow or overflow diagnostics. Outputs provide
parameters such as output type (voltage or current)
and for diagnostics, such as short-circuit (for
voltage outputs) or upper/lower limit diagnostics
of the module
parameters, such as baud rate, parity, data bits,
stop bits, flow control, XON and XOFF characters,
and wait time
configures transmit related options
configures the message-start and message-end
parameters
S7-1200 Programmable controller
System Manual, 11/2009, A5E02486680-02