(e.g. by use of symbols such as ® or ™). 1.2.2 Copyright This document may be duplicated and distributed only with the express permission of Siemens, and may be passed only to authorized persons or companies with the required technical knowledge. 1.2.3 Quality assurance These documents were prepared with great care.
Siemens assumes no liability to the extent allowed under the law for any losses resulting from a failure to comply with the aforementioned points or for the improper compliance of the same.
(values set by OEM and current configuration, and actual values), cf. section 9.2. For connecting to a PC with RS232 interface, an interface converter AST11 is required. Datasheet: N5852 8 / 44 Siemens VAV compact controller KNX/PL-Link G..B181.1E/KN CE1P3547en Building Technologies 2017-03-23...
Page 9
The app can be obtained free of charge at [7] resp. [8] Accessories For information regarding accessories and spare parts for VAV compact controllers, please refer to datasheet N4698. 9 / 44 Siemens VAV compact controller KNX/PL-Link G..B181.1E/KN CE1P3547en Building Technologies 2017-03-23...
VAV compact controller is disconnected from the power supply. disengagement Dimensions min. 100 3547M01 Ø 3...8 8 - 16 mm 12.8 mm min. 80 15 mm Measures in mm 12 / 44 Siemens VAV compact controller KNX/PL-Link G..B181.1E/KN CE1P3547en Building Technologies 2017-03-23...
Press push button > 20s ƒ LED flashes orange Device restarts ƒ All parameters which can be set by the OEM are reset to the OEM default values. 13 / 44 Siemens VAV compact controller KNX/PL-Link G..B181.1E/KN CE1P3547en Building Technologies 2017-03-23...
SELV or PELV. ∂ Safety transformers with twofold insulation as per EN 61558 required; they must be designed to be on 100 % of the time. 14 / 44 Siemens VAV compact controller KNX/PL-Link G..B181.1E/KN CE1P3547en Building Technologies...
Assume that a VAV box is designed for a nominal pressure of Δp = 120 Pa. Then, has to be set to 1.58: 1.58 < < < 15 / 44 Siemens VAV compact controller KNX/PL-Link G..B181.1E/KN CE1P3547en Building Technologies 2017-03-23...
VAV compact controllers are primarily used for controlling a variable or constant air volume flow. System environments: ∂ Building automation systems using the Siemens peripheral bus PL-Link (Desigo Total Room Automation) ∂ Building automation systems using KNX LTE-mode (Synco 700 Series C and newer) ∂...
5.3, constant, positive or negative pressure in a zone or a room can be achieved. Legend: N1 Room unit with temp. sensor N2 VAV compact controllers (supply air / extract air) 17 / 44 Siemens VAV compact controller KNX/PL-Link G..B181.1E/KN CE1P3547en Building Technologies 2017-03-23...
For a detailed explanation of this application in a Synco 700 system, please refer to [14], chapter 23. For a detailed explanation of this application in a Desigo PL-Link system, please refer to [10]. 18 / 44 Siemens VAV compact controller KNX/PL-Link G..B181.1E/KN CE1P3547en Building Technologies...
In HVAC Integrated Tool (HIT), application examples can be found for the use with room thermostats RDG400KN or RDF341. Navigate to www.siemens.com/hit ⇓ HIT Start Center ⇓ Applications ⇓ Individual Rooms ⇓ “Preferred controller” / “Range”: select “RDG/RDF” in dropdown list and “Operating voltage”...
(ΧU/2U = 4 %) on line length L as per the above table and the basic diagram. P is the decisive power consumption of all actuators connected in parallel. ΧU/2 Basic diagram: Voltage drop on the supply lines U,ΧU ΧU/2 21 / 44 Siemens VAV compact controller KNX/PL-Link G..B181.1E/KN CE1P3547en Building Technologies 2017-03-23...
Instructions regarding topology and addressing in KNX networks can be found in the documents [13] and [16]. The following sections presuppose electrical installations that conform to the KNX-TP1 standard 22 / 44 Siemens VAV compact controller KNX/PL-Link G..B181.1E/KN CE1P3547en Building Technologies...
Page 23
VAV Compact Controllers operate in VAV mode when connected to the specified control (VAV) power supply. The setpoint signal determines the operating range … Vmin [%] Vmax [%] Setpoint Actual value Control range 23 / 44 Siemens VAV compact controller KNX/PL-Link G..B181.1E/KN CE1P3547en Building Technologies 2017-03-23...
Page 24
Ζ ∴ Differential pressure as Ζ ∴ ∑ ⌡ ∋ Χ < < √ Ζ ∴ Ζ ∴ function of actual value √ 24 / 44 Siemens VAV compact controller KNX/PL-Link G..B181.1E/KN CE1P3547en Building Technologies 2017-03-23...
Page 25
The AST20 is designed for portable use on-site. Power supply and establishing the communication between AST20 and a VAV Compact Controller are realized with one of the connection cables which are shipped with the AST20. 25 / 44 Siemens VAV compact controller KNX/PL-Link G..B181.1E/KN CE1P3547en Building Technologies...
This procedure is essential for the recommended engineering and commissioning workflows below. If the label gets lost, the ID is printed on the device housing as well. 32 / 44 Siemens VAV compact controller KNX/PL-Link G..B181.1E/KN CE1P3547en Building Technologies 2017-03-23...
For KNX S-mode engineering, the required product data (*.vd5 or *.knxprod) have Obtaining the KNX product data to be downloaded from the Siemens website and imported into the ETS device catalog. To obtain the product data, navigate to www.siemens.com/hvac-td www.siemens.com/openair and locate the “Downloads”...
The EI or the commissioning engineer (CE) can do a first testing with the SSA tool. 6. The CE can use the design data and Desigo XWP (ABT) to complete the commissioning. 34 / 44 Siemens VAV compact controller KNX/PL-Link G..B181.1E/KN CE1P3547en Building Technologies 2017-03-23...
LED is green ⇓ connection test successful b) LED flashes red (1s – interval) ⇓ connection test failed Acknowledge Short key press LED is off connection test (<0.5 s) 35 / 44 Siemens VAV compact controller KNX/PL-Link G..B181.1E/KN CE1P3547en Building Technologies 2017-03-23...
Configuration is uploaded from the automation station to the VAV compact controllers. ⇓ Optional: Middle key press for connection test (>2 sec and <20 sec). 36 / 44 Siemens VAV compact controller KNX/PL-Link G..B181.1E/KN CE1P3547en Building Technologies...
∂ Third-party regulations issued by general contractors or building operators Safety The electrical safety of building automation and control systems supplied by Siemens depends primarily on the use of extra low-voltage with safe isolation from mains voltage. SELV, PELV Depending on the type of extra low-voltage earthing, a distinction is to be made between SELV and PELV as per HD 384, “Electrical plants in buildings“:...
Mechanical coupling of the devices is not permitted. Do not open the actuator! The device is maintenance-free. Only the manufacturer may carry out any repair Warning, work. maintenance 38 / 44 Siemens VAV compact controller KNX/PL-Link G..B181.1E/KN CE1P3547en Building Technologies 2017-03-23...
In general, unshielded twisted pair cables for building services plant (including data lines) offer adequate EMC characteristics, plus the advantage that no provision is required for coupling to earth. 39 / 44 Siemens VAV compact controller KNX/PL-Link G..B181.1E/KN CE1P3547en Building Technologies...
Drift ± 0.1 Pa / Year Max. permissible operating pressure 3000 Pa Max. permissible overload on one side 3000 Pa The documents can be downloaded from http://siemens.com/bt/download 40 / 44 Siemens VAV compact controller KNX/PL-Link G..B181.1E/KN CE1P3547en Building Technologies 2017-03-23...
Volume flow VAV operating mode Position control control Outside air, Primary supply air, Type of air Outside air Supply air, Extract air Autonomous, Master/Slave Master, Autonomous Slave 42 / 44 Siemens VAV compact controller KNX/PL-Link G..B181.1E/KN CE1P3547en Building Technologies 2017-03-23...
“500%” in ETS5. The same applies for read-back values. For some group objects, alternative data point types (DPT) can be selected in ETS. The first entry indicates the default setting. 43 / 44 Siemens VAV compact controller KNX/PL-Link G..B181.1E/KN CE1P3547en...