hit counter script
Download Print this page
Siemens VGD20.253U Technical Instructions

Siemens VGD20.253U Technical Instructions

Gas valves, for use with skpxx.xxxu series electro-hydraulic actuators

Advertisement

Quick Links

 
 
 
 
VGD Series 
VGDxx.xxxU Gas Valves 
for use with SKPxx.xxxU electro‐hydraulic actuators 
VGD20.xxxU 
 
ISO 9001 and 14000 
REGISTERED FIRM 
Description 
 
 
 
 
      
 
Only with series SKPxx.xxxUx actuators 
 
The normally closed VGDxx.xxxU series of modular double‐body gas valves combine 
with SKPxx.xxxU series electro‐hydraulic actuators to provide safety shut‐off, gas 
pressure regulation and/or air‐gas ratio control for commercial or industrial gas 
burners. 
 
Table 1. VGDxx.xxxU model numbers 
Model Numbers 
VGD20.253U 
VGD20.323U 
VGD20.403U 
VGD20.503U 
VGD40.065U 
VGD40.080U 
VGD40.100U 
VGD40.150U 
Technical Instructions
 
 
     
 
Body style 
Double 
Double 
Double 
Double 
Double 
Double 
Double 
Double 
Document No. 7631
VGDxx.xxxU
November 08, 2017
 
VGD40.xxxU 
Connection 
NPT thread 
NPT thread 
NPT thread 
NPT thread 
NPT thread 
NPT thread 
ANSI flange 
ANSI flange 
Siemens AG Building Technologies Division 

Advertisement

loading

Summary of Contents for Siemens VGD20.253U

  • Page 1   ISO 9001 and 14000  REGISTERED FIRM                   Only with series SKPxx.xxxUx actuators    Description  The normally closed VGDxx.xxxU series of modular double‐body gas valves combine  with SKPxx.xxxU series electro‐hydraulic actuators to provide safety shut‐off, gas  pressure regulation and/or air‐gas ratio control for commercial or industrial gas  burners.      Table 1. VGDxx.xxxU model numbers  Model Numbers  Body style  Connection  VGD20.253U  Double  NPT thread  VGD20.323U  Double  NPT thread  VGD20.403U  Double  NPT thread  VGD20.503U  Double  NPT thread  VGD40.065U  Double  NPT thread  VGD40.080U  Double  NPT thread  VGD40.100U  Double ...
  • Page 2 The first (inlet) valve has a flat valve disc applicable for safety shut‐off function only.   The second (outlet) valve has a contoured valve disc for use with pressure regulating  actuators (SKP2x.xxxU, SKP5x.xxxU, SKP7x.xxxU)   A 1‐inch NPT vent connection between the valves   Each VGD20.xxxU double‐valve requires 2 threaded mounting flanges (AGFxx.xxU). Each  flange includes the necessary installation hardware (bolts, nuts and O‐ring). Each mounting  flange has a ¼‐inch NPT pressure tap. The flanges can be pre‐mounted onto the pipe, and  then bolted onto the VGD20.xxxU gas valve body. This feature eliminates the use of pipe  unions and permits the gas valve assembly to be easily removed from a gas train   Connecting pattern of the 1...2 inch AGFxx.xxU flanges are identical. This space permits  any AGFxx.xxU flange to be mounted to any VGD20.xxxU valve body        NOTE:  VGD20.xxxU valves and AGFxx.xxU flanges must be ordered as separate items (see  Tables 2 and 3).     Compact VGD40.xxxU double‐valve bodies consist of 2 safety shut‐off valves in series  VGD40.xxxU models   Each individual safety shut‐off valve has double seats to achieve high flow   Patented seat construction with individual closing spring for each seat to assure reliable  shut‐off and high close‐off pressure rating   Full port vent line connection plates are available        NOTE:  VGD40.xxxU valves and AGA40.xxxxU vent connection plates must be ordered as  separate items (see Tables 2 and 3).    Page 2  Siemens AG Building Technologies Division ...
  • Page 3 VGD Series Double Valves  Technical Instructions    Document Number CC1N7631us    November 08, 2017    Application  All VGDxx.xxxU valves can be combined with any SKPxx.xxxU series actuator. The actuator  can be mounted while the valve is installed and under pressure.    SKPxx.xxxU regulating actuators are applicable for both low and high supply gas pressure  applications, eliminating excessive regulator inventories. Maximum pressure ratings vary  with valve size (see Table 2).    All VGDxx.xxxU valves perform these functions in combination with each of the following  actuators:    SKP15.xxxU  Safety shut‐off  SKP25.xxxU  Safety shut‐off and constant pressure regulation or zero governor  SKP55.xxxU  Safety shut‐off, pressure regulation and differential pressure air‐gas ratio  control  SKP75.xxxU  Safety shut‐off, pressure regulation and adjustable air/gas ratio control    Since more than one function can be performed by a single valve, fewer components and  fittings are required‐significantly reducing both the size and weight of the gas train. In  addition, smaller diameter gas valves can be used. For details on valve sizing see the flow  chart (figure 3).      CAUTION: Do not oversize valves equipped with a regulating SKP2x.xxxU / SKP5x.xxxU /    SKP7x.xxxU actuator. Oversizing may limit turndown and could cause oscillations.  Siemens AG Building Technologies Division  Page 3 ...
  • Page 4: Ordering Information

    Close‐off  Capacity  Number of  test  Valve body   number  operating  pressure  CFH  points,    material  pressure  psi  Natural gas  1/4" NPT  psi  at  Inlet  Outlet  P = 1" W.C. VGD20.253U *)  1"  20  30  600  Aluminum  Two ¼‐inch and VGD20.323U *)  1¼"   20  30  1200  Aluminum  one 1‐inch port  VGD20.403U*)  1½"  20  30  1,850 ...
  • Page 5                 AGA40.4050U  1” NPT vent connection plate for VGD40.xxxU  Each vent connection  AGA40.6580U  1 ¼” NPT vent connection plate for VGD40.xxxU  includes ¼” NPT test port,  AGA40.0100U  2” NPT vent connection plate for VGD40.xxxU  see Mounting instruction  M7631.3 (74 319 0278 0)  AGA40.0150U  2 ½” NPT vent connection plate for VGD40.xxxU      AGA61  Manual adjusting throttle attachment AGA61 permits VGDxx.xxxU series valves to be used as  adjustable limiting orifice valves. Once adjusted, the AGA61 has a provision to be sealed from  tampering.           AGA66  Sealing gasket to provide NEMA 3, NEMA 3R, and NEMA 4 protection.  Gasket kit to mount SKPxx.xxxU  ‐ Place between actuator SKPxx.xxxU and valve VGDxx.xxxU  ‐ Increases degree of protection from IP54 to IP65  ‐ Refer to Mounting Instruction M7643.2 (74 319 0421 0)      Siemens AG Building Technologies Division  Page 5 ...
  • Page 6: Specifications

      Operating  Maximum operating pressure  See Table 2  environment  Maximum back pressure (differential)  VGD20.xxxU: 2 psi (150 mbar)        VGD40.xxxU: 4 psi (300 mbar)  Close‐off pressure  See Table 2  Permissible gas temperature  14 °F to 140 °F (‐10 °C to 60 °C)  Permissible operating temperature  14 °F to 140 °F (‐10 °C to 60 °C)    Use  Siemens gas valves are in accordance with UL429.    The valve is used as:  Safety shutoff valve (in connection with SKP15.xxxU)  ‐ Control valve with safety shutoff function (in connection with SKP25.xxxU, SKP5x.xxxU or  ‐ SKP7x.xxxU)     Perm. mounting  position  7631z01us/0815     Operating pressure  See Type summary    Types of gases  Suitable natural gases, propane, butane and air   ...
  • Page 7: Operation

    Specifications      Physical  Body materials  See Table 2  characteristics  Weight   See Tables 4    Connections  Pipe connections  NPT threads or ANSI class 150 flanges  (see Table 2)  Pressure and vent taps  See Tables 2 and 3    All VGDxx.xxxU gas valves are normally closed, two‐way valves. The valves have a standard,  Operation  integral, stainless steel mesh filter (0.9 mm) in the inlet to protect the downstream  components against contamination.    All valves have ¼ NPT ports for pressure test connection. A full size vent connection plate is  available as an accessory for VGD40.xxxU valves.  See Table 2 and 3 for details on ports and vent connection plates.        AGF10... AGF10... 7631z50us/0815 Figure 1. Sectional view of VGD20.xxxU     VGD20.xxxU double valves consist of two valves in series.   The first (inlet) valve has a flat valve disc suitable for the safety shut‐off function only.  The second (outlet) valve has a contoured valve disc for stable regulating control and  smooth release of gas.    Siemens AG Building Technologies Division  Page 7 ...
  • Page 8 Technical Instructions  VGD Series Double Valves  Document Number CC1N7631us    November 08, 2017    Operation, continued    7631z53us/1215     Figure 2. Second view of VGD40.xxxU flange models    VGD40.xxxU double valves consist of two valves in series.   Each valve has a double seat to achieve high flow (see Figure 2).    Closing springs:  Each double seat uses one pair of springs. The spring forces act separately as closing  forces on the individual valve seats.    Page 8  Siemens AG Building Technologies Division ...
  • Page 9 10000 100000 cf/h Butane gas 2.00 1000 10000 100000 cf/h 1.00 1000 10000 100000 m3/h 1.00 1000 Figure 3. Sizing double valves    Assumptions:  1) Pressure downstream of valve is atmospheric  2) Maximum gas temperature of 140 °F  3) Valve in fully open position       NOTE:    Pressure drop is total drop across both valves when using a SKPx5.xxxU actuator,  with or without an AGA66.        CAUTION:  Do not oversize valves equipped with regulating actuators SKP2x.xxxU,    SKP5x.xxxU or SKP7x.xxxU. Oversizing may limit turndown and could cause  oscillations.  Siemens AG Building Technologies Division  Page 9 ...
  • Page 10 (63.5) (19) AGF10... 1/4" NPT   Table 4. VGD20.xxxU dimensions in inches (mm) with 2 flanges AGF10.xxU  Valve model  Nominal size D Length (L)  Weight  inch  inch  pounds  (mm)  (Kg)  1”  10.59 + 2 x 1.02 7  VGD20.xxxU  (269 + 2 x 26)  (3.2)  1 ¼“  10.59 + 2 x 1.02 7  (269 + 2 x 26)  (3.2)  1 ½“  10.59 + 2 x 1.02 7  (269 + 2 x 26)  (3.2)  2”  10.59 + 2 x 1.18 7  (269 + 2 x 30)  (3.15)    Page 10  Siemens AG Building Technologies Division ...
  • Page 11 VGD Series Double Valves  Technical Instructions    Document Number CC1N7631us    November 08, 2017    Dimensions, continued  Dimensions in Inches (mm)    VGD40.065U / VGD40.080U      7631m21us/1215   a) Base plate    Siemens AG Building Technologies Division  Page 11 ...
  • Page 12 (72)  (115.5) (22)  (222)  18.90  13.29  5.71  7.40  2.09  2.30  6.61  10.31 0.63  ‐‐‐  ‐‐‐  9.5  0.91  3.92  5.61  0.90  10.63  VGD40.150U  (480)  (337.5)  (145)  (188)  (53)  (58.5) (168) (262)  (16)  (241)  (23)  (99.5)  (142.5) (22.9)  (270)  *) SW = width across flats  Page 12  Siemens AG Building Technologies Division ...
  • Page 13 4.13 5.49  3.17  0.79 19  (185)  (105) (139.5) (80.5) (20)  (8)  VGD40.100U 8.54  4.76 6.26  3.94  1.95 29  (210)  (121) (159)  (100)  (49.5)  (13)  VGD40.150U 11.30 6.14 7.80  5.47  2.28 53  (287)  (156) (198)  (139)  (58)  (24)    Siemens AG Building Technologies Division  Page 13 ...
  • Page 14 Table 7. AGA40.xxxxU Models Vent connection plate (optional)    Vent  connection  thread "Z"  ●  ●      AGA40.6580U  1¼" NPT  ●        AGA40.0100U  2" NPT  ●        AGA40.0150U  2½" NPT    Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design  improvements are introduced. Other product or company names mentioned herein may be the trademarks of their respective owners.  Siemens AG Building Technologies Division  Your feedback is important to us. If you have  Document No. CC1N7631us  Berliner Ring 23  comments about this document, please send them  Country of Origin: DE  76437 Rastatt  to techsupport@SCCcombustion.com  GERMANY  Page 14  Siemens AG Building Technologies Division ...