LPB and BSB plants OZW672.01 Web server OZW672… V3.0 OZW672.04 Commissioning instructions OZW672.16 CE1C5712en Building Technologies 06.06.2011...
Web server fault ..................50 File transfer .....................52 Operation with ACS790................55 Visualize plants ..................56 Overview ....................56 Example of a plant web page..............57 Plant web page features .................58 Toolbar ....................59 3 / 102 Siemens Web server CE1C5712en Building Technologies Table of contents 06.06.2011...
Page 4
6.2.1 Internet protocol ..................83 6.2.2 Free e-mail account providers..............83 6.2.3 Install RNDIS driver.................84 6.2.4 Alternative network configuration............85 6.2.5 Siemens routers ..................87 Technical data ..................88 6.3.1 Web browser / OS ...................88 6.3.2 Web server ....................88 6.3.3 Connections ....................90 6.3.4 Pin assignment..................90 6.3.5...
Do not open the device. Failure to comply will invalidate any warranty claims. The technical data are provided solely for use with Siemens bus devices. The user ensures the functionality of operation when using third-party devices not expressly mentioned here. Siemens assumes no responsibility for service and warranty under these circumstances.
History data is not deleted. Switch • Position "On" Message inhibition Messages cannot be sent. • Position "Off" Message sending allowed. (DIP switches) No function. 6 / 102 Siemens Web server CE1C5712en Building Technologies Overview 06.06.2011...
Click the field to go directly to the display of all plant faults. 6 Plant name Shows the web server name. 7 Display Shows the contents of the selected function. Shows Logo 1 and Logo 2. 8 Logo area 7 / 102 Siemens Web server CE1C5712en Building Technologies Overview 06.06.2011...
Page 8
• Administer own user account. Administrator • Operate service and end user data. • Fault overview • Documents, Message history, Logos and System definitions. • Administer all user accounts. • Create device websites. 8 / 102 Siemens Web server CE1C5712en Building Technologies Overview 06.06.2011...
• PC: Start > Settings > Network connections > Local Area Connection Entry in the web browser address line: IP address, domains • IP address: 192.168.2.10 • Domains: www.siemens.com Buttons Buttons are written as follows: Add 9 / 102 Siemens...
Shielded Twisted Pair Transmission Control Protocol Transport Layer Security UPnP Universal Plug and Play Universal Serial Bus Unshielded Twisted Pair Further explanations on abbreviations and terms are available in the appendix. 10 / 102 Siemens Web server CE1C5712en Building Technologies Overview 06.06.2011...
• The web server recognizes whether LPB or BSB devices Notes are connected to the bus. • IP address USB: 192.168.250.1 (unchangeable). • IP address Ethernet: 192.168.251.1 (ex works). 11 / 102 Siemens Web server CE1C5712en Building Technologies Commissioning 06.06.2011...
4. The RNDIS driver is installed automatically if the PC is connected to the Inter- net and no RNDIS driver is installed. The installation wizard will guide you through installation. Note You can also manually set up the RNDIS driver (see Section 6.2.3). 12 / 102 Siemens Web server CE1C5712en Building Technologies Commissioning 06.06.2011...
• When you log in for the first time, you must enter "User name" = "Administrator", Notes "Password" = "Password". • Change the password after initial login. • Note case sensitivity. • English is the web browser language after the initial login. 13 / 102 Siemens Web server CE1C5712en Building Technologies Commissioning 06.06.2011...
Enter / select user data: - User name - Password - Repeat password - Description (optional) - E-mail address (optional) - Language: English - User group Close with OK. 14 / 102 Siemens Web server CE1C5712en Building Technologies Commissioning 06.06.2011...
Page 15
• A secure password is comprised of lowercase and uppercase letters, numbers and special characters, is at least 20 characters long, and does not include a name or words from dictionaries. 15 / 102 Siemens Web server CE1C5712en Building Technologies Commissioning 06.06.2011...
Click Add. Enter the bus address: LPB: Segment number and Device number. BSB: Device number (default: 1=basic device). You can add just one BSB device to the device list. 16 / 102 Siemens Web server CE1C5712en Building Technologies Commissioning 06.06.2011...
Page 17
Wait until Process finished is displayed. In the device list, the web server and the bus device display status "Generated". 10. The device websites are now available under Home. 17 / 102 Siemens Web server CE1C5712en Building Technologies Commissioning 06.06.2011...
Page 18
Click Yes to confirm. The web server removes the device from the device list. Wait until Process finished is displayed. Click OK confirm. The device is removed from the device list. 18 / 102 Siemens Web server CE1C5712en Building Technologies Commissioning 06.06.2011...
Page 19
Device web pages are generated. Process takes a few minutes Wait until Process finished is displayed. Close with OK. In the device list, the web server and the bus device display status "Generated". 19 / 102 Siemens Web server CE1C5712en Building Technologies Commissioning 06.06.2011...
Page 20
Click Update. The device web pages are updated. Process takes a few minutes Wait until Process finished is displayed. The device list for the web server display status "Generated". 20 / 102 Siemens Web server CE1C5712en Building Technologies Commissioning 06.06.2011...
• Otherwise, both date and time must be newly set. Data point Explanation, example Time of day/date Set the current time and date. Weekday is calculated automatically. Default val: 00:00 1.1.2005 Setting val: Time of day/date 21 / 102 Siemens Web server CE1C5712en Building Technologies Commissioning 06.06.2011...
= Factory setting for administrator password). Setting value "Yes" is a temporary state, i.e. the setting value automatically goes to "No" after ca. 2 seconds. * with PC software ACS790 only. 22 / 102 Siemens Web server CE1C5712en Building Technologies Commissioning 06.06.2011...
Page 23
(daylight saving time), i.e. time is adjusted backward one hour. Note Disable the function by setting both start of daylight saving and standard time to the same date. 23 / 102 Siemens Web server CE1C5712en Building Technologies Commissioning 06.06.2011...
Page 24
* This setting affects the LPB only. The Device number and time supplier are automatically specified on BSB. 24 / 102 Siemens Web server CE1C5712en Building Technologies Commissioning...
Page 25
UPnP localization Web server registers its existence via Ethernet, when • "UPnP localization" = "Ethernet" is set and • The connection between PC/laptop and the web server is active via Ethernet. 25 / 102 Siemens Web server CE1C5712en Building Technologies Commissioning...
Page 26
Max. 46 char. Signature line 1..10 Signature lines are transmitted with the e-mail. — It identifies the sender, e.g. the plant's Internet Default val: (Blank) Setting val: Max. 46 char. address. 26 / 102 Siemens Web server CE1C5712en Building Technologies Commissioning 06.06.2011...
Page 27
Setting val: All, status messages. Only urgent ones E-mail address For E-mail recipient types: — Setting value is recipient email address. Default val: messagereceiver@ example.com Setting val: Max. 46 characters 27 / 102 Siemens Web server CE1C5712en Building Technologies Commissioning 06.06.2011...
Page 28
Not urgent exempts all message recipients subscribing to "Only urgent ones". Next report Waiting time to next system report. — Default val: 0 d (day) Setting val: 0...255 d (Resolution: 1 d) 28 / 102 Siemens Web server CE1C5712en Building Technologies Commissioning 06.06.2011...
Page 29
Default val: Setting val: Max. 20 char. Water pressure too low. * Notes: • Note Section 2.4, "Update device web pages". • Delete the entry to reset to default text. 29 / 102 Siemens Web server CE1C5712en Building Technologies Commissioning 06.06.2011...
Page 30
• Note Section 2.4, "Update device web pages". • Delete the entry to reset to default text. Note "System" faults refer to bus device faults received via LPB/BSB bus. 30 / 102 Siemens Web server CE1C5712en Building Technologies Commissioning 06.06.2011...
Special day The default settings is to always send mes- 00:00 On … sages. Setting val: Monday...Sunday, Special day 00:00…24:00 Off / On 31 / 102 Siemens Web server CE1C5712en Building Technologies Commissioning 06.06.2011...
Page 32
• You can copy the switching times for a day of the week by clicking Copy one day to a selection of other days • Click Check to check the data before it is saved. 32 / 102 Siemens Web server CE1C5712en Building Technologies Commissioning 06.06.2011...
Page 33
Notes • Select checkbox to select active entries. • Select "Annually" to set annually recurring switching times. • Click Check to check the data before it is saved. 33 / 102 Siemens Web server CE1C5712en Building Technologies Commissioning 06.06.2011...
PC with web browser on a local area network (LAN): • IP address • Subnet mask The addresses in the illustration are examples must be adapted to router address- Note ing. See Section 5.1.1 for more details. 34 / 102 Siemens Web server CE1C5712en Building Technologies Commissioning 06.06.2011...
• DynDNS: The dynamic IP address for the connection must be published if no fixed public IP address is available. Settings depend on network type and application. The different variants are Note described in Section 5.1.2. 35 / 102 Siemens Web server CE1C5712en Building Technologies Commissioning 06.06.2011...
Authentication mail server. The first fault is displayed for multiple faults. Message inhibition Shows the message suppression switch — Display values: Yes, No setting (8) (see Section 1.2). 36 / 102 Siemens Web server CE1C5712en Building Technologies Commissioning 06.06.2011...
Delete history of all events and messages. — Note : Setting value Yes is a temporary state, i.e. Default val: Setting val: the value automatically returns to No after ca. 2 seconds. 37 / 102 Siemens Web server CE1C5712en Building Technologies Commissioning 06.06.2011...
– The web server sends a system report to the defined message receivers. – Fault LED (4) displays (flashing) error in establishing communications. On LED must be green. Fault LED must be dark. 38 / 102 Siemens Web server CE1C5712en Building Technologies Commissioning 06.06.2011...
Procedures are communicated for any firmware update accordingly. Logo update The logos can be customized. Note See Section 3.4, part "Upload logos" for information on uploading. 39 / 102 Siemens Web server CE1C5712en Building Technologies Commissioning 06.06.2011...
• Password Note You can automate the process by adding the login information to the web browser’s address line. Format: <IP address>/main.app?user=<User name>&pwd=<Password> Example: 10.169.9.121/main.app?user=Administrator&pwd=Password 40 / 102 Siemens Web server CE1C5712en Building Technologies Operate using a web browser 06.06.2011...
Page 41
The current, valid login information must be included for syntax "user=<user name>&pwd=<Password>". Note Deep links can be rendered invalid by generating an associated bus device. 41 / 102 Siemens Web server CE1C5712en Building Technologies Operate using a web browser 06.06.2011...
Only the following parts of the user interface are displayed to operate the web server from a smaller screen or to hide navigation: • Plant state • Plant name • Display 42 / 102 Siemens Web server CE1C5712en Building Technologies Operate using a web browser 06.06.2011...
Page 43
Note In partial view, navigation to other plant web pages must be implemented using user-defined links. You can return to the full view at any time for navigation. 43 / 102 Siemens Web server CE1C5712en Building Technologies Operate using a web browser...
Page 44
Data point Explanation, example Time of day/date Set the current time and date. Weekday is calculated automatically. Default val: 00:00 1.1.2005 Setting val: Time of day/date 44 / 102 Siemens Web server CE1C5712en Building Technologies Operate using a web browser 06.06.2011...
Page 45
• Click Copy to copy the switching times for any weekday to a number of other days • Click Check to check the data before it is saved. 45 / 102 Siemens Web server CE1C5712en Building Technologies Operate using a web browser...
Page 46
• Select checkbox to select active entries. • Select "Annual" to set repetitive switching points. • Click Check to check the data before it is saved. 46 / 102 Siemens Web server CE1C5712en Building Technologies Operate using a web browser 06.06.2011...
Field bus module 1 Field bus module 1 type. Software version Field bus module 1 software version. Message inhibition Shows the setting of the message suppression switch (8). 47 / 102 Siemens Web server CE1C5712en Building Technologies Operate using a web browser 06.06.2011...
Page 48
Number of devices Actual number of devices monitored by the web current server on the LPB/BSB bus. Last change Time of last change to device list. 48 / 102 Siemens Web server CE1C5712en Building Technologies Operate using a web browser 06.06.2011...
Page 49
An alternative DNS server is only defined for redundant systems and is typically empty. Physical address The physical address is a unique identification for the Ethernet interface. 49 / 102 Siemens Web server CE1C5712en Building Technologies Operate using a web browser 06.06.2011...
Displays for each fault: • Fault information (date, time, fault code). • Fault text Note Overview of all web server faults included in Section 6.1. 50 / 102 Siemens Web server CE1C5712en Building Technologies Operate using a web browser 06.06.2011...
Page 51
Displayed under "Fault 1..n": Device name, Fault information, Fault text, Device address, Device type. Note Faults for bus devices are listed in the documentation for the corresponding devices. 51 / 102 Siemens Web server CE1C5712en Building Technologies Operate using a web browser 06.06.2011...
(messages.txt: Text file, messages.xls: Excel file). The "File download" dialog box opens. Open the file with the application or save it to any location. 52 / 102 Siemens Web server CE1C5712en Building Technologies Operate using a web browser...
Page 53
You must recreate the devices following a system definition upload. • System definition file transfer is available to administrator and service Notes user levels. • Uploading and installing make take more than 5 minutes. 53 / 102 Siemens Web server CE1C5712en Building Technologies Operate using a web browser 06.06.2011...
Page 54
• The left logo (Logo 1) has max. 625 x 54 pixels. • The right logo (Logo 2) has max. 200 x 54 pixels. • The original logos are restored when resetting the web server to default. 54 / 102 Siemens Web server CE1C5712en Building Technologies Operate using a web browser 06.06.2011...
ACS790 and import them to the web server. • Parameterization: Read and write parameter sets. • Commissioning protocol. • Offline trend. For more details, see data sheet N5649. 55 / 102 Siemens Web server CE1C5712en Building Technologies Operate using a web browser 06.06.2011...
Note The switch from an LPB to a BSB bus system and vice versa is not recommended since this renders the defined plant web pages unusuable. 56 / 102 Siemens Web server CE1C5712en Building Technologies Visualize plants...
HIT. The extension consists of additional, explanatory text (3), a link to the Internet (4) and an integrated web cam image (5), that is updated periodically (e.g. every minute). 57 / 102 Siemens Web server CE1C5712en Building Technologies Visualize plants...
(current available memory is available at "File transfer > Documents") • A maximum of 100 elements may be added on a plant webpage from one web page element type (e.g. a maximum of 100 data point elements). 58 / 102 Siemens Web server CE1C5712en Building Technologies Visualize plants 06.06.2011...
Partial picture Add additional picture to plant web page. "Link external" integrates periodically updated, external images (e.g. web cams). User levels Only an administrator may generate and change visualization. User levels have the same rights for operation and monitoring. 59 / 102 Siemens Web server CE1C5712en Building Technologies Visualize plants 06.06.2011...
Import information is displayed while the file is being read; the property dialog box now opens. 6. Check replacement function with "Replace datapoint addresses". 7. From the dropdown list box, select the bus address for the connected controller. 60 / 102 Siemens Web server CE1C5712en Building Technologies Visualize plants 06.06.2011...
Page 61
• The data point text "Data point not found" is displayed. • Three question marks "???" are displayed as the data point value. See Section 4.6 for any post editing. 61 / 102 Siemens Web server CE1C5712en Building Technologies Visualize plants...
8. Click Apply to check the results of the change in formatting as a preview to the plant web page. 9. If satisfied, click OK to finish. 10. Click OK to change to view. The data point value was read and is displayed. 62 / 102 Siemens Web server CE1C5712en Building Technologies Visualize plants 06.06.2011...
Page 63
The following describes how to add two lines to the plant web page: • To another plant web page. • To an external web page. The link to a document is not displayed, but works accordingly. 63 / 102 Siemens Web server CE1C5712en Building Technologies Visualize plants...
Page 64
12. If satisfied, click OK to finish. 13. Click OK to change to view. The link is enabled immediately in the view mode: Click to open the corresponding web page. 64 / 102 Siemens Web server CE1C5712en Building Technologies Visualize plants...
Page 65
12. Edit Position and Scaling. 13. Click Apply to check the results of formatting in a preview. 14. If satisfied, click OK to finish. 15. Click OK to change to view. 65 / 102 Siemens Web server CE1C5712en Building Technologies Visualize plants...
The PC and web server (e.g. without a router) must be on the same IP subnet to communicate. You must first determine the subnet as well as the IP addresses. Local area network (with router) 66 / 102 Siemens Web server CE1C5712en Building Technologies Communications...
Page 67
• The web server IP address must be entered manually. The web server cannot be configured as a DHCP. • We recommend using IP addresses from the private range in the home network (see Section 6.2.1). 67 / 102 Siemens Web server CE1C5712en Building Technologies Communications...
Page 68
Select Start > Control Panel > Network Connections > Local Area Connection Select the "General" tab. Click Properties. Select "Internet Protocol (TCP/IP)". Click Properties. Select "Use the following IP address". 68 / 102 Siemens Web server CE1C5712en Building Technologies Communications 06.06.2011...
Page 69
• The default gateway and DNS server settings have no meaning for LANs without router, provided no e-mail is sent within the home network. • We recommend using IP addresses from the private range in the home network (see Section 6.2.1). 69 / 102 Siemens Web server CE1C5712en Building Technologies Communications...
The appropriate connection is required (e.g. DSL router) for remote operation via Internet. Setting up Internet access is not described here. • The example here were created using the Siemens Gigaset SX763 router (see Notes Section 6.2.5). Workflow, terms and functionality may differ when using other products.
Page 71
We recommend enabling the firewall to protect the local area network: • Firewall: On. Address Translation Activate NAT to ensure that the web server can be reached via the Internet. (NAT) • NAT: On. 71 / 102 Siemens Web server CE1C5712en Building Technologies Communications 06.06.2011...
Page 72
• We recommend using Port Forward Ports from the private range. In the example, queries from the Internet to the public IP address (Internet connec- tion)/Port 80 is forwarded to the local IP address 192.168.2.10 (web server)/Port 72 / 102 Siemens Web server CE1C5712en Building Technologies Communications 06.06.2011...
Page 73
After setting up the account, DynDNS sends an e-mail with a link that must be queried within 48 hours. You then login with • User (user name from above). • Pass (password from above). 73 / 102 Siemens Web server CE1C5712en Building Technologies Communications...
Page 74
• Service Type: Select "Host with IP address" • IP Address: Current IP router address. Can be assumed automatically by click- ing "Use auto detect IP address …". • Click Create Host. 74 / 102 Siemens Web server CE1C5712en Building Technologies Communications...
Page 75
HTTPS encryption via port 443 is also supported. The required certificate is not connection (HTTPS) accredited. The self-signed certificate from Siemens is valid for 20 years and is installed on the web server. The certificate must be installed on the web browser for encrypted communications.
• An e-mail account is available and set up. • Internet access is set up for the web server (see Section 5.1.2). • The settings for "E-mail", "Message receiver 1…4", "System report" (see Section 2.5.2). Example mail: 76 / 102 Siemens Web server CE1C5712en Building Technologies Communications 06.06.2011...
Page 77
Web server fault Example of an e-mail Data point, information From: myhome@bluewin.ch …> Communication > E-mail: E-mail address sender service@siemens.com …> Message receiver > Message receiver 1…4: E-mail address Subj: Message central unit: Message type: Demo HCS, …> Texts: Name, No bus power supply Störungstext...
Page 78
Fault inputs 1-2 Example of an e-mail Data point, information From: myhome@bluewin.ch …> Communication > E-mail: E-mail address sender service@siemens.com …> Message receiver > Message receiver 1…4: E-mail address Subj: Message central unit: Message type: Demo HCS, …> Texts: Name, …>...
Page 79
System report with fault Example of an e-mail Data point, information From: myhome@bluewin.ch …> Communication > E-mail: E-mail address sender service@siemens.com …> Message receiver > Message receiver 1…4: E-mail address Subj: Message central unit: Message type: Demo HCS, N. OK …>...
Page 80
• "Authentication mail server = Yes" checks unsecured, unencrypted information in the data items "User name" and "Password" from the mail server for each e-mail transmission. • The mail server can also be installed on the local area network. 80 / 102 Siemens Web server CE1C5712en Building Technologies Communications...
Device failure (Bus) as a result, device failure (bus) is assigned to "System faults", whereas all other faults generated by the web server are assigned as "Local faults". 3) Possible causes of recipient type e-mail: Erroneous Ethernet or e-mail settings. 81 / 102 Siemens Web server CE1C5712en Building Technologies Appendix 06.06.2011...
Check whether DNS and mail servers can be reached. nslookup <IP address> Translates an IP address to the domain name and vice or <domain> versa: Look up domain names. 82 / 102 Siemens Web server CE1C5712en Building Technologies Appendix 06.06.2011...
Nur mit T-Online DSL-Verbindung T-Online smtpmail.t-online.de Tiscali smtp.tiscali.de Nur mit Tiscali DSL-Verbindung Additional information on free e-mail providers: • http://www.patshaping.de/hilfen_ta/pop3_smtp.htm • http://www.iopus.com/guides/bestpopsmtp.htm Note Siemens is not responsible for third-party page contents. 83 / 102 Siemens Web server CE1C5712en Building Technologies Appendix 06.06.2011...
Click Continue installation. 4. Wait until installation is complete and click Finish. Result The RNDIS driver is now installed. The PC can communicate with the web server via USB. 84 / 102 Siemens Web server CE1C5712en Building Technologies Appendix 06.06.2011...
Result The RNDIS driver is now installed. The PC can communicate with the web server via USB. Note The RNDIS driver is installed as part of the ACS790 Siemens software installation. 6.2.4 Alternative network configuration Alternative We recommend setting up IP settings for commissioning as an alternative configu-...
Page 86
Enter IP address, subnet mark and operational standard gateway as well as DNS server. Result The PC assumes the configuration with these settings as soon as it is no longer integrated in the standard network. 86 / 102 Siemens Web server CE1C5712en Building Technologies Appendix 06.06.2011...
6.2.5 Siemens routers We recommend the following router from Siemens to connect to an internal network with DSL connection: We recommend the Gigaset SX763 WLAN dsl by Siemens. This router supports all requirements for trouble-free operation of web server. Performance features •...
Max. 100 m Digital inputs Interface type Protective low voltage for potential-free low voltage-capable contacts Voltage at open contact DC (16...19) V Current at closed contact DC (4...6) mA 88 / 102 Siemens Web server CE1C5712en Building Technologies Appendix 06.06.2011...
Page 89
87.5 mm x 90 mm x 40 mm Weight Basic unit 0.136 kg Complete device (basic unit with packaging, installation 0.589 kg instructions, power supply unit, USB and Ethernet cable, cable ties) Packaging Cardboard box 89 / 102 Siemens Web server CE1C5712en Building Technologies Appendix 06.06.2011...
Tx – Rx – Rx + Unused Unused Unused USB plug Type Mini-B D – Terminal assignment A LPB/BSB connections DB/CL+ DB/CL+ MB/CL– MB/CL– Terminal assignment C Digital inputs 90 / 102 Siemens Web server CE1C5712en Building Technologies Appendix 06.06.2011...
D2 M D2 M DB/CL+ DB/CL+ MB/CL- MB/CL- Web server LPB/BSB device P1, P2 Devices with potential-free contact output for fault indication 6.3.6 Dimensions 87.5 Drilling plan Dimensions 39.2 87.5 91 / 102 Siemens Web server CE1C5712en Building Technologies Appendix 06.06.2011...
DSL is a type of data transmission allowing for 1.5 Mbps access to the Internet on standard copper phone lines. The Internet Service Provider ISP provides the DSL connection. You need a DSL modem for this type of connection. 92 / 102 Siemens Web server CE1C5712en Building Technologies Appendix 06.06.2011...
Page 93
TCP/IP. All devices connected to the Internet can be identified via IP address. The DNS server assigns domain names to IP addresses. 93 / 102 Siemens Web server CE1C5712en Building Technologies Appendix...
Page 94
Network adapter Hardware to connect network components to a local area network (LAN). Connec- tion can be wired or wireless. 94 / 102 Siemens Web server CE1C5712en Building Technologies Appendix...
Page 95
Different protocols are needed to allow two applica- tions at different levels to communicate with each other, e.g. TCP/IP protocols on the Internet. 95 / 102 Siemens Web server CE1C5712en Building Technologies Appendix...
Page 96
In this case, the first three IP address sections are identical for all network devices. Example: Subnet mask 255.255.255.0 masks IP addresses: 192.168.1.1…192.168.1.254. Note: Do not use the first IP address 192.168.1.0 and last IP address 192.168.1.255. 96 / 102 Siemens Web server CE1C5712en Building Technologies Appendix 06.06.2011...
Page 97
In addition, they automatically provide, depending on class, own services or use services of other devices on the network. A URL refers to an information source, e.g. http://www.siemens.com. The URL is a uniform web address that is used to determine the network protocol used (e.g. http) or the location of the resource on the network.
Page 98
Wireless LANs allow network devices to communicate via radio. The WALN can be WLAN added as an extension to a wired LAN, or it can be the basis of a new network. 98 / 102 Siemens Web server CE1C5712en Building Technologies Appendix 06.06.2011...
Page 99
Fault codes ............81 Recommended router..........87 Faults current............50 Remote operation via the Internet......70 Firmware update........... 39 Free e-mail account providers ......83 Secondary navigation..........7 Settings Glossary..............92 Email Email address sender........26 99 / 102 Siemens Web server CE1C5712en Building Technologies Index 06.06.2011...
Page 100
User interface............7 Daylight saving time........23 Web server diagnostics ........47 Time zone ............23 Web server fault ........... 50 Web server operation ........... 42 UPnP localization........... 27 Web server 100 / 102 Siemens Web server CE1C5712en Building Technologies Index 06.06.2011...
Page 101