hit counter script

Project Engineering - Siemens SIMATIC NET CP 443-1 Advanced Manual

S7-400 - industrial ethernet
Hide thumbs Also See for SIMATIC NET CP 443-1 Advanced:
Table of Contents

Advertisement

3.3

Project engineering

Configuration and downloading the configuration data
It is possible to download the configuration data to the CP via MPI or LAN/Industrial
Ethernet. Downloading is possible over the PROFINET or the gigabit interface of the CP.
You require STEP 7 with additional modules in the following version:
Table 3- 1
Required STEP 7 version
STEP 7 version (either V5.5 with "SCT" or Professional)
STEP 7 V5.5
STEP 7 V5.5 + Service Pack 4 + HF 8
You also require the following:
HSP 1105 (Hardware Update) *
Program block library "SIMATIC NET CP" version V5.5.4 **
Security Configuration Tool (SCT) V4.1 ***
SCT is used in the configuration of the security function from
within STEP 7.
STEP 7 Professional
STEP 7 Professional V13
* You will find the HSP on the Internet pages of Siemens Industry Online Support at the
following address:
Link: (https://support.industry.siemens.com/cs/ww/en/view/23183356)
** You will find the program block library on the Internet pages of Siemens Industry Online
Support at the following address:
Link: (https://support.industry.siemens.com/cs/ww/en/view/109481127)
*** You will find the SCT on the STEP 7 DVD.
Configuration for use of PROFINET CBA
To be able to work in the PROFINET CBA environment, you require the SIMATIC iMap
engineering tool.
SIMATIC iMap requires a connection via Industrial Ethernet (TCP/IP protocol). The following
SIMATIC iMap configuration software is required:
Table 3- 2
Required SIMATIC iMap version
SIMATIC iMap version
as of V3.0 + Service Pack 3
CP 443-1 Advanced (GX30)
Manual, 03/2019, C79000-G8976-C256-05
CP 4431 Advanced functionality
The full functionality as described in this
document can be used.
The following are not supported:
PROFINET CBA
Innovations of firmware version V3.2
CP 4431 Advanced functionality
The full functionality of the device can be used as of hard-
ware version 1 and firmware version V3.0.
Requirements for use