Set controller parameters K
Procedure
1. Temporarily set the ramp-up and ramp-down times of the ramp-function generator (p2257
and p2258) to zero.
2. Enter a setpoint step and monitor the associated actual value.
The slower the response of the process to be controlled, the longer you must monitor the
controller response. Under certain circumstances (e.g. for a temperature control), you need
to wait several minutes until you can evaluate the controller response.
3. Set the ramp-up and ramp-down times of the ramp-function generator back to their original
value.
You have manually set the technology controller.

Limiting the output of the technology controller

In the factory setting, the output of the technology controller is limited to ± maximum speed. You
must change this limit, depending on your particular application.
Example: The output of the technology controller supplies the speed setpoint for a pump. The
pump should only run in the positive direction.
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
, T
and T
.
P
I
d
Optimum controller response for applications that do not permit
any overshoot.
The actual value approaches the setpoint without any significant
overshoot.
Optimum controller behavior for fast correction and quick com‐
pensation of disturbance components.
The actual value approaches the setpoint and slightly over‐
shoots, maximum 10 % of the setpoint step.
The actual value only slowly approaches the setpoint.
● Increase the proportional component K
the integration time T
The actual value only slowly approaches the setpoint with slight
oscillation.
● Increase the proportional component K
the rate time T
The actual value quickly approaches the setpoint, but over‐
shoots too much.
● Decrease the proportional component K
increase the integration time T
Advanced commissioning
6.5 Technology controller
(p2280) and reduce
P
(p2285).
I
(p2280) and reduce
P
(p2274)
d
P
(p2285).
I
(p2280) and
249