Pipe Filling Speed / Pf Spd; Pipe Filling Time / Pf Time; Pipe Filling Monitoring Time / Pf Mon Time; Bi: Frost Protection Enable / Fro En - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

p29612[0...n]

Pipe filling speed / PF spd

Access level: 3
Can be changed: T
Unit group: 3_1
Min:
-210000.00 [rpm]
Description:
Sets the speed applied to the motor for the pipe filling.
p29613[0...n]

Pipe filling time / PF time

Access level: 3
Can be changed: T
Unit group: -
Min:
0.50 [s]
Description:
Sets the duration time for the pipe filling.
p29614[0...n]
Pipe filling threshold / PF thresh
Access level: 3
Can be changed: T
Unit group: 9_1
Min:
0.00 [%]
Description:
Defines the threshold for stopping the pipe filling. The filling stops if the actual PID feedback reaches the threshold.
It's used when p29611=1.
p29615[0...n]

Pipe filling monitoring time / PF mon time

Access level: 3
Can be changed: T
Unit group: -
Min:
0.00 [s]
Description:
Monitors the duration time for actual pressure (r2272) >= the threshold (p29614). The pipe filling stops if the duration
time is reached.
Note
It is used when p29611 = 1.
p29622[0...n]

BI: Frost protection enable / Fro en

Access level: 3
Can be changed: T, U
Unit group: -
Min:
-
Description:
Sets the signal source to enable frost protection. If the binary input is equal to 1, then protection will be initiated. If the
inverter is stopped and the protection signal becomes active, protection measure is applied as follows:
- If p29623 != 0, frost protection is activated by applying the specified speed to the motor;
- If p29623 = 0, and p29624 != 0, condensation protection is activated by applying the specified current to the motor.
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Calculated: -
Scaling: p2000
Unit selection: p0505
Max:
210000.00 [rpm]
Calculated: -
Scaling: -
Unit selection: -
Max:
10000.00 [s]
Calculated: -
Scaling: -
Unit selection: p0595
Max:
100.00 [%]
Calculated: -
Scaling: -
Unit selection: -
Max:
100.00 [s]
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Parameters
7.3 Parameters
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
900.00 [rpm]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
50.00 [s]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
10.00 [%]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
0.00 [s]
Data type: Unsigned32 / Binary
Dynamic index: CDS, p0170
Function diagram: -
Factory setting:
0
717