Parameter list
7.2 Parameter list
Parameter
Function
Note:
See P0844
P0848[0...2]
BI: 1. OFF3
Defines first source of OFF3 when P0719 = 0 (BICO).
Dependency:
If one of the digital inputs is selected for OFF3, the inverter will not run unless the digital input is active.
Note:
OFF3 means quick ramp-down to 0.
OFF3 is low-active, i.e.
0 = Quick ramp-down.
1 = Operating condition.
P0849[0...2]
BI: 2. OFF3
Defines second source of OFF3.
Dependency:
In contrast to P0848 (first source of OFF3), this parameter is always active, independent of P0719
(selection of command and frequency setpoint). See P0848.
Note:
See P0848
P0852[0...2]
BI: Pulse enable
Defines source of pulse enable / disable signal.
Dependency:
Active only when P0719 = 0 (Auto selection of command / setpoint source).
P0881[0...2]
BI: Quick stop source 1
Allows quick stop source 1 command to be selected using BICO. The signal is expected to be active low
(default setting P0886 = 2).
P0882[0...2]
BI: Quick stop source 2
Allows quick stop source 2 command to be selected using BICO. The signal is expected to be active low
(default setting P0886 = 2).
P0883[0...2]
BI: Quick stop override
Allows quick stop override command source to be selected using BICO. The signal is expected to be
active high.
r0885.0...4
CO / BO: Quick stop
status
Bit field describing status of quick stop.
Bit
00
01
02
04
P0886[0...2]
Quick stop input type
Control Word for selecting the quick stop input type.
0
1
2
3
4
154
Range
-
-
-
-
-
-
-
Signal name
Quick stop is active
Quick stop selected
Override selected
Quick stop enabled
0 - 4
Quick stop not selected
Quick stop input active high
Quick stop input active low
Quick stop input positive edge triggered
Quick stop input negative edge triggered
Factory
Can be
default
changed
1
T
1
T
1
T
1
T
1
T
0
T
-
-
2
T
Scaling
Data
set
-
CDS
-
CDS
-
CDS
-
CDS
-
CDS
-
CDS
-
-
1 signal
Yes
Yes
Yes
Yes
-
CDS
SINAMICS V20 Inverter
Operating Instructions, 07/2012, A5E03728167
Data
Acc.
type
Level
U32 /
3
Bin
U32 /
3
Bin
U32 /
3
Bin
U32 /
3
Bin
U32 /
3
Bin
U32 /
3
Bin
U16
3
0 signal
No
No
No
No
U16
3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents

Save PDF