About this document About this document ................7 Safety regulations ...................9 Signal words and symbols ................9 2.1.1 Classification and meaning of signal words..........9 2.1.2 Symbols and their meaning ..............9 2.1.3 Classification and meaning of additional symbols ........10 Safety-relevant working instructions ............10 Main features of CS1140 ..............12 Overview of technical data for CS1140..........13 Logical and physical structure ............14...
Page 4
About this document 17.1 Features ....................48 17.1.1 Plexi glass doors for AlgoPilot B3Q6../566 ..........48 17.1.2 Positioning of E3I020 RS232 plug-in module and PSA interface board K3I090 .....................49 17.1.3 Positioning E3I040 I bus/LON plug-in module ........49 17.1.4 Components and labeling kits for B3Q6../566 ........50 17.2 Installation options ..................51 17.3...
Page 5
About this document Remote transmission (conforming to EN54-2) ........85 31.1 CPU-wide remote transmission ..............86 Extinguishing ..................87 32.1 Main features of extinguishing SECTION ..........87 32.2 Degraded mode link E3G110 option............88 32.3 Key data ....................88 32.4 Typical extinguishing system ..............89 32.5 Functions needed..................89 Printer interface..................90 33.1 Features ....................90...
Page 6
About this document 43.1 CI1142 in housing H38... (flat) ..............114 43.2 CI1142 in housing H38... (deep) ............115 43.3 CI1142 in housing H47… ..............116 43.4 CC1142/43 in housing H47… ...............117 43.5 CC1142/43 in housing H47… (with extra power supply) ......118 43.6 CC1142/43 in housing H67...
About this document About this document Goal and purpose This document describes how to plan the hardware components of the CS1140 control panel. Safe applications will result from consistently following these instruc- tions. Scope of validity This document contains information about all CS1140 components for ≥EP7F, in- cluding order numbers.
Page 8
Disregard of the safety regulations Products are designed for proper use, and before they are delivered they are tested to ensure they function correctly. Siemens disclaims all liability for damage or injuries caused by the incorrect application of the instructions or disregard of warnings of danger contained in the documentation.
Safety regulations Safety regulations This chapter describes the danger levels and the relevant safety regulations appli- cable for the use of our products. Please read the work instructions as well as the chapter 1 'About this document' before beginning any work. Signal words and symbols 2.1.1 Classification and meaning of signal words...
Safety regulations 2.1.3 Classification and meaning of additional symbols Tips and information. Refers to extremely important or critical decisions to be taken into account before continuing the work. Safety-relevant working instructions Country-specific standards The products are developed and produced in compliance with the relevant Euro- pean safety standards.
Page 11
Safety regulations Testing the product operability Evacuate and cordon off the extinguishing sector. Inform people about the possibility of fogging and noise. Inform people before testing alarm devices; take the possibility of panic reac- tions into account. Inform the alarm and fault receiving stations connected to the system before car- ...
Main features of CS1140 Main features of CS1140 Fire detection system that can be configured in a modular manner 2150 detectors possible per CC1143; 980 detectors possible per CC1142; 600 detectors possible per CI1142 For processing collective and addressable detectors ...
Overview of technical data for CS1140 Overview of technical data for CS1140 Operating voltage 115 / 230 VAC +10 % / –15 % 50...60 Hz Power consumption 40...320 VA (per converter B2F020) 30...350 VA (per converter B2F040) Battery operations should the mains fail Switchover without interruption –...
Logical and physical structure Logical and physical structure The logical structure in the CS1140 fire detection system is totally separate from the physical structure. This allows for maximum flexibility. Display and operation are oriented towards geographical and organizational aspects and are not depend- ent on the detector network's effective hardware installation.
Bus systems Bus systems There are 6 levels of communication in the CS1140 fire detection system: C bus Local data bus between control panel(s), operating console(s) and gateway(s) I bus Internal data bus between the individual plug-in modules in the control panel (li- ...
Principle sensor/actor bus sensor/actor bus conventional sensor/actor bus Cerberus protocol Cerberus protocol ’K31’ current gain principle Siemens protocol ’P2’ – – – – ’K51’ serial 8 bit voltage thresholds serial 32 bit – – –...
C bus stations C bus stations Max. 16 stations (participants) can be operated in the C bus network. Any stations (CC, CI, CT, CK) in any arrangement are possible below the limits stated below max. 64 AREAS DMS/LMS (management system) CERLOOP...
C bus stations Meaning of the endings 42, 43 Provides information about the outline quantities (see section 8) or the size of the RAM available: Cx1142 2x512Kx8 bits – Cx1143 4x512Kx8 bits – Hardware Station type Component Function Function Function 'Main CPU' 'Operation'...
C bus stations 7.5.3 'CT11 visualizer for WINDOWS' remote control software For operating platform needed, see document 006824 – Terminal types supported: B3Q661/681/686/566 – For details, also see document A6V10225450 – Standard control terminal Parallel control terminal CT/CI (RS232) V24 ..1000m E3I020 E3I020 max.
C bus stations Logical AREAS All AREAS control terminal Max. 4 AREAS can be configured within one CPU ('CI' or 'CC'). CPU-wide AREAS are not possible. CPU-wide controls are possible. Operating units ('CT'/'CI') can be assigned to any AREAS. ...
We would highly recommend using loop technology. Options with requirements The following options with requirements are available on fire detection system Algorex CS1140. The chapter numbers belong to EN54-2. Indications: 7.13 Alarm counter...
Outline quantities of C bus participants Outline quantities of C bus participants This section describes the limits of the various station types in terms of quantities. Any performance limits which may be dependent on outline quantities are not cov- ered. The details provided in the relevant Release Notes or the corresponding edition ...
Outline quantities of C bus participants Main CPU (CI/CC) limitation The limits within the station types are given by hard- and software. Verify all given limits for each required station by going through this flow chart. Maximum number of devices per station (RAM) select station with This limitation is for the CI1142, CC1142, CC1143 station types and depends on how the logical higher RAM...
Page 24
Outline quantities of C bus participants New definition of the number of devices to count: Structure Number of devi- D bus participants with their own D bus address (e.g. DOT1151, DO1131, DM1154, DCW1151, DOW1171...) FDnet participants with their own FDnet address (e.g. DOOT2x1, DO2x1, DM2x1, ...
Page 25
Outline quantities of C bus participants Example: CI1142 with 150 control objects with an average of 9 links. The intersect between the number of control objects (150) and the number of links (9) must fall within the permitted area. 'Limit values for controls' diagram for CI1142 and CC1142 Number of links per control object Exam-...
Page 26
Outline quantities of C bus participants Limitation due to 5V power consumption All I bus components are supplied with 24 V and 5 V. The power available for the 5 V supply is limited select station with after the CPU: higher capacity, 'Main CPU' Power available...
Outline quantities of C bus participants Operating unit limitation (CT/CI) define the required number of control terminals by going through this flow chart Maximum number of texts There is a limit to the number of texts of external stations (or AREAS) which can be displayed on an operating unit (CT/CI).
Outline quantities of C bus participants Gateway limitation (CK) check gateway configuration Memory limitation (RAM) use CK1143 type gateway CK1143 (E3H021): – station type CC1143 suitable for stations CI1142, CC1142, CC1143 – visible on CK ? Limitation of CERLOOP address range use second Max.
Establishing the hardware needed Establishing the hardware needed The key system data must be known in order to determine the hardware needed: 1. Define number and type of detector lines Depending on: Detector series – Number of detectors, input and output modules –...
Selecting the appropriate control panel Selecting the appropriate control panel With a suitable normal application, the control panel housing required can be de- rived from the outline quantities of the main CPU. Station type Housing Housing Housing Housing Housing H38G220 H38G320 H47...
CC1142/43 in housing H47... 15.2 Cable kits for additional power supply in H47 housing The Z3I870 cable kit can always be used to wire the additional power supply. The cable kit contains all the cables and wires needed for connections to the next ex- tension.
CC1142/43 in housing H67... 16.1 Possible forms of installation on component carrier H67... Special feature: H67E101 is designed with 3 continuous perforated rasters. The connector panel / plug-in module / battery split can thereby be arranged differently. Rasters for plug-in modules Rasters for relays and terminal Rasters for cable ducts Rasters for accumulators...
CC1142/43 in housing H67... 16.5 Cable kits for additional power supply The Z3I870 cable kit can always be used to wire the additional power supply. The cable kit contains all the cables and wires needed for connections to the next ex- tension.
AlgoPilot B3Q... operating terminal AlgoPilot B3Q... operating terminal There are 2 different forms of operating unit, the standard terminal and the comfort terminal. Standard and comfort terminals can be mixed in the same system con- figuration. Application range Comfort terminals Standard terminals International B3Q661...
AlgoPilot B3Q... operating terminal 17.1 Features Features Comfort termi- Standard termi- nals nals Large backlit display with plain text readout (LCD 240x128 points) for very user-friendly use Context and system status-controlled convenient operation – using softkeys Operating and display elements split functionally and ergo- nomically Detailed event information like type of event, location of event, measure text, operating modes etc.
AlgoPilot B3Q... operating terminal 17.1.2 Positioning of E3I020 RS232 plug-in module and PSA interface board K3I090 RS232 plug-in module E3I020 is secured to the rear of the operating terminal using option Z1B020. For installation details for E3I020, see docu- ment 1393 The PSA interface board K3I090 is secured to the rear of the operating terminal using option Z1B060.
AlgoPilot B3Q... operating terminal 17.1.4 Components and labeling kits for B3Q6../566 AlgoPilot operating terminal B3Q661 A5Q00020708 'International' operating terminal Operating unit and main CPU at the same time B3Q681 S54371-F12-A1 'Nordic' operating terminal ” B3Q686 S54371-F11-A1 'CH' operating terminal ” B3Q566 S54371-F13-A1 'China' operating terminal...
Housing range H23... / H26... / H28... Housing range H23... / H26... / H28... H23G230 H28G200 H26G220 For operating unit B3Q... / B3R051 / cover H23B020 with lock (DOM) H28T110 Front cannot be swiveled H23G230: Measurements 125 x 219 x 76 mm For parallel displays (4x H28T120 Material Plastic...
Housing range H37... Housing range H37... H37G410 H37G420 H37G410: H37G420: Measurements 540 x 510 x 200 mm Measurements 540 x 510 x 214 mm Material Steel sheet Material Steel sheet Color RAL7035 light gray Color RAL7035 light gray Protection category IP30 Protection category IP30 H37G430 H37T120...
Housing range H38... Housing range H38... H38G210 H38G310 Doors can be locked with 2 Allen screws H38G210/220/230: H38G310/320: Measurements 520 x 602 x 100 mm Measurements 520 x 602 x 155 mm Material Steel sheet Material Steel sheet Color RAL7035 light gray Color RAL7035 light gray Protection category IP40...
Housing range H67... Housing range H67... H67G601/620 H67G611 H67T101 H67T111 Including component carrier with: Doors can be locked with DOM H67T101/H67T111: Cable ducts lock Measurements 434 x 110 x 300 mm – Mains terminals (pre-wired) Material Steel sheet – Retaining plate for batteries Color RAL7035 light gray –...
Housing range H98... Housing range H98... –> for details, see document 654 / ZH4.2 Installation of component carriers H47E.../H67E... –> for details see page 44 H98G600 H98G600 H28V000 H28V010 19” Doors can be H98T000 locked with KABA H98T020 lock 1057-25 H98Z010 H15Z200 H67Z020...
Principle of internal pre-wiring Principle of internal pre-wiring Component carrier H47E... Component carrier H67E... Connection cable Connection cable Z1I030 –> short 0.5 m Z1I050 –> short 0.8 m 19-wire 19-wire Connection cable Connection cable Z1I020 –> short 0.5 m Z1I040 –> long 0.8 m 9-wire 9-wire Z1I060 –>...
Line plug-in modules Line plug-in modules There are different line plug-in modules for the various detector systems: E3M071 for interactive detectors – E3M171 for interactive 'Ex' detectors – E3M120 for CBA8000/TS9000 detectors – E3M111 for AnalogPLUS detectors – E3M060 for MS9i detectors –...
Line plug-in modules 26.2 "Interactive" detector line Number of addresses per line: Max. 128, –> limitations for certain device types 1) T-branches possible anywhere max. 30 detectors Ventilation, 3 contacts air-conditioning, 1 Loop line elevator etc. DOW1171 3 relay DF1191/92 contacts DCW1151...
Line plug-in modules 26.3 "Interactive" Ex detector line Number of addresses: Max. 32, –> limitations for certain device types 1) T-branches possible 1 Stub line the software can not proof wheter or not Non-Ex- detectors are in the explosion hazard area non-Explosion hazard area Explosion hazard area...
Line plug-in modules 26.5 'AnalogPLUS' detector line Number of addresses per line: Max. 128, for limitations, see All detectors, HFM and input/output module with integrated short-circuit isolator DJ1192 DJ1191 4 Loop lines DF1191/92 DC1131 DBZ1197A DO113x DT/DOT/DO113x DM113x DOT1131 DMA1133 AnalogPlus-Bus max.
Line plug-in modules 26.6 'MS9i addressing' detector line The E3M060 allows existing system parts to be integrated with detectors of the MS9i/MS7i series Number of elements (addresses) per line: Max. 50, but depends on element type Z9..Si Parallel detectors (slaves) MS716i max.
Line plug-in modules 26.7 'Collective' detector line All detectors within a line have the same collective address (OBJECT) Depending on application, end-of-line by means of transzorb diode or EOL22 (Ex) Number of detectors per line: DS11 detectors: Max. 25 –...
Line plug-in modules 26.8 'FD20' detector line Number of addresses per line: Max. 126, –> limitations for certain device types Only 1 T-branch possible between 2 devices Stub line Stub line max. 32 devices max. 32 devices FDOOT241-9 FDO221 2 Loop lines FDT221...
Control plug-in modules Control plug-in modules 27.1 Using control plug-in modules To activate fire controls (shut down ventilation, close fire protection flaps etc.) To activate and monitor alarm devices To activate and monitor remote transmission devices To activate mimic displays= ...
Control plug-in modules 27.6 Control outputs, station type CT11 remote I-Bus B3Q... E3I040 Converter I-Bus/LON LON-Bus K3I110 1..16 30VDC 1A For installation details for E3I040, see document 1393 E3I040 Z1B070 K3I110 Components E3X102 6290250001 Control panel module For alarm devices and control outputs E3X103 6290380001 Control panel module...
Control plug-in modules 27.7 CPU-wide controls Multi-area Single-area Gateway C-Bus CC/CI CC/CI CC/CI CC/CI B = AREA Control OBJECT/ELEMENT Must be in the same CPU Control device ● = activating data point Limitation: See section 8 Building Technologies 008725_h_en_-- Fire Safety &...
LON bus devices LON bus devices 28.1 Features Activation via local 'LON' communication bus 4 different device types B3Q580 plain text display terminal – B3Q590/595 plain text operating terminal – K3I050 LON/mimic display converter – K3I110 LON I/O board –...
LON bus devices 28.5 LON I/O board K3I110 Input/output board 16 programmable monitored control inputs – 16 programmable control outputs – Measurements: 122 x 220 x 14 mm H23G230 K3I110 K3I110 28.6 Display devices B3Q580 and B3Q590/595 Both devices with identical sizes ...
Page 81
LON bus devices Components E3I040 4993100001 LON plug-in module Converter between I bus and LON bus K3I050 4967660001 LON/mimic display converter Converter between LON bus and data bus for K3R072 or B3R051 K3I110 5288540001 LON I/O board 16 programmable control inputs/outputs B3Q580 4961770001 plain text display terminal...
Gateway Gateway 29.1 Main features C bus network <–> DMS / LMS connection via V28 interface (RS232) Conversion C bus <–> CERLOOP/CERBAN/ISO1745 For bridging distances of up to 1000 m (double V28 modem integrated) For distances > 1000 m, use FSK/PSK modem ...
Remote transmission (not conforming to EN54-2) Remote transmission (not conforming to EN54-2) Most fire detection installations are connected to a remote transmission. In alarm status (alarm level 2) the fire detection system activates the remote transmission device (RT device). Remote transmission device Installed in control panel housing –...
Remote transmission (conforming to EN54-2) Remote transmission (conforming to EN54-2) Most fire detection installations are connected to a remote transmission. In alarm status (alarm level 2) the fire detection system activates the remote transmission device (RT device). Remote transmission device Single-channel (alarm + fault) or multi-channel (multi-criteria alarm) –...
Remote transmission (conforming to EN54-2) 31.1 CPU-wide remote transmission all-AREA single-AREA Gateway C-Bus CC/CI CC/CI CC/CI Area 1 Area 2 Area 3 Area 4 common RT-device for all AREAS common RT-device for several CPUs within CPU ● = activating data point 'RT' control element RT device Even functions in degraded mode operation by means of degraded mode func-...
Extinguishing Extinguishing 32.1 Main features of extinguishing SECTION Extinguishing section consists of: Control plug-in module E3G080 (I bus component) – 'Extinguishing' operating unit B3Q440 – Option Monitoring board K5L020 to monitor and control additional solenoid – extinguishing valves E3G080 is designed for one extinguishing SECTION ...
Extinguishing 32.2 Degraded mode link E3G110 option Allows extinguishing to be activated automatically even if the main CPU fails. Depends on 2 detectors. The detectors in the extinguishing SECTION must be split over 2 independent detector lines. CC11, CI11 Z1I030/050 I-Bus E3X10.
Extinguishing 32.4 Typical extinguishing system The requirements relating to monitoring depend greatly on the extinguishing agent used and the properties of the mechanical hardware used The system must satisfy the local requirements Pipe network with nozzles Extinguishing agent Means of activation 32.5 Functions needed...
Printer interface Printer interface 33.1 Features Available for station types CT11, CI11, CC11 Designed for B2Q191, B1Q101 printers, commercially available ISO-LATIN1 printers and EPSON printers Depending on use, extra hardware needed to adapt levels Printer B2Q191 can be connected up directly (for installation inside housing) ...
Printer interface 33.3 CC11 usage variant CC11 zum Drucker I-Bus E3X10. E3I020 F20A020 Z1I030/050 RS232 C-Bus max.1000m E3I020 B2Q191 24VDC (9...36VDC) E3X10. F20A020 CC11 I-Bus E3X10. (TTL) F20A410 B2Q191 max. 1m 24VDC C-Bus Condition: – B2Q191 printer is in the same housing as the main CPU (E3X10.) or in a neighboring housing F20A410 E3X10.
Printer interface 33.5 B2Q191/B1Q101 tape printer Tape printer for event protocoling Integrated automatic paper winding device Thermomatrix printing unit Interface and printing unit monitored For more details, see document 001260 H28G200 housing 19" upright cabinet H housing H28G200 H28T020...
PSA interface PSA interface 34.1 Features The PSA interface board K3I090 can be used universally and serves to analyze the data transmitted by a control panel to its printer output and to transfer this to a PSA or pager system in ESPA 4.4.4 format. The optional printer is connected to the PSA interface board.
Power supply Power supply Concept The power supply for the CS1140 fire detection system consists of: Converter (mains voltage –> system voltage 29.6 V) Battery charging unit (integrated in E3X10. or by means of E3C011) Batteries (capacityas required) ...
Power supply 35.2 Additional power supply Auxiliary batteries for the basic power supply: CT11 max. 1x E3C011 with battery set as an addition Additional batteries with auxiliary power supply: max. 3 battery sets per B2F020 possible mains mains Basic emergency power supply 1st extension 2nd extension 3rd extension...
Power supply 35.3 Operating unit with power supply as of control panel As of CC11 –> operating unit is connected to E3X10. – As of CI11 –> operating unit is connected to AlgoPilot B3Q… – CT11 CT11 + / - / Earth + / - / Earth CC11 CI11...
Emergency power supply Emergency power supply 36.1 Determining the battery capacity Emergency current batteries available FA2006-A1 A5Q00019356 12 V/24 Ah battery FA2007-A1 A5Q00022897 12 V/38 Ah battery FA2005-A1 A5Q00019677 12 V/15 Ah battery 1) The battery capacities supplied may be slightly higher. The values 15 Ah, 24 Ah and 38 Ah should be taken into account when defining ...
Emergency power supply 36.2 Quiescent current table Quiescent current during battery operation (24 V) – As basis for individual emergency current calculation – The current of the 5 V supply is included in these values – Component Quiescent current at 24 V DC (typical) Extra current during alarm B1F120 / B2F020 / B2F040 / B2F060...
Emergency power supply 36.3 Capacity values for standard configurations CS1140 configuration Quiescent Battery capacity requirement for current 12 h 24 h 72 h CI with 128 detectors interactive 260 mA 4.2 Ah 7.8 Ah 18.7 Ah (B3Q… + 1xE3M071 including detector + 1xE3G070 + 1xE3C011) CI with 128 detectors AnalogPLUS 235 mA 3.8 Ah...
Alarming concept Alarming concept The alarming concept must be defined individually for each system The rapid forwarding of alarm messages to the corresponding circle of recipients is important The requirements vary between "Discrete alarming" of the investigation crew, e.g. using human search system –...
Alarming concept 37.2 Defining alarm organization The CS1140 fire detection system has up to 64 programmable organizational – levels (AREAS) Different "alarming variants" are possible (can be selected per OBJECT) – The "V1" and "V2" time memories should be defined individually –...
Protective elements Protective elements Purpose Protection from overvoltage and electromagnetic influences (EMI). Normal usage Control panel No extra protective measures needed. All plug-in modules have integrated pro- tection from overvoltage and electromagnetic influence, but no protection from lightning. Installation As a rule use twisted cables, for detector lines, data lines, external supply ...
Commissioning Commissioning For details, see document 004594 The CS1140 fire detection system is designed for a rational installation setup. Connection to the control panel may be undertaken by experts without special training (e.g. external electricians). Coordinated construction management is however still indispensable.
Flash programming, parameter setting Flash programming, parameter setting The parameters for the CS1140 fire detection system are set via the mainte- nance PC using the 'AlgoWorks' software tool kit. Online help text in various local languages 2 user levels (service technician; national manager) ...
Flash programming, parameter setting 40.2 Download system data 40.2.1 61.2.1 B3Q4../B3Q6../E3X10./E3H02. AlgoPilot B3Q6.. B3Q4.. C U/ Operating unit Maintenance-PC with ‘AlgoWorks’ Modembox B3D021 E3X101/102/103 Both set as 'external' S5-1 Gateway E3H021 (ON) for download S5-2 E3H020 F14E320 Maintenance-PC with ‘AlgoWorks’ Red marking Modembox B3D021...
CS1140 components in alphabetical order CS1140 components in alphabetical order B1F120 4952330001 Converter 115/230 V AC > 24 V DC B1Q101 5045800001 Tape printer 19”/3HU, 24 V DC B2F020 A5Q00025281 Converter 115/230 V AC ->29.6 V DC, 6 A B2F040 5102990001 Converter 115/230 V AC ->29.6 V DC, 3.5 A B2F060...
Page 109
CS1140 components in alphabetical order E3G070 5466610001 'Universal' control plug-in module E3G080 4759490001 'Extinguishing' control plug-in module E3G091 4977070001 'CH' remote transmission interface E3G110 5049910001 Degraded mode link E3H021 A5Q00024660 Gateway plug-in module E3I020 4602390001 RS232 plug-in module E3I040 4993100001 LON plug-in module E3L020 5466450001...
Page 110
CS1140 components in alphabetical order H67G611 4956600001 'Doors with cut-out' housing kit H67T101 4956150001 Housing frame and 'doors without cut-out' H67T111 4956280001 Housing frame and 'doors with cut-out' H67Z020 4969020001 Shielding hood for H67E... H98G600 4161280001 Housing 42HE with base H98T000 4161310001 42HE doors, hinged on right, no windows...
Page 111
CS1140 components in alphabetical order Z3I520 4849690001 Cable kit for K3R071/K3R072 Z3I530 4849720001 Adapter to B3R051 / K3R071/K3R072 Z3I570 4956440001 133 mm 'TS35' mounting rail with bracket Z3I580 4956570001 291 mm 'TS35' mounting rail with bracket Z3I870 4969440001 Cable kit for supply extension Z3I1040 A5Q00004129 'CH' remote transmission kit...
Spare parts for CS1140 components Spare parts for CS1140 components 4638090001 Cover frame (plastic) For B3Q321, B3Q440, B3R051 5646690001 DOM duplicate key in locking unit 2C 2500 For H28T/H47/H67 5053300001 Flat cable L=0.2 m For B3D021 4714510001 Flat cable for I bus + 'Short' supply line For I bus plug-in modules EOL22 5162220001...
Configuration sheets Configuration sheets The following pages are intended as templates for copying or can be used as a suggestion for a country-specific tool. The system-specific configuration (use of installation space, number and type of components, etc.) is entered on these sheets. List of configuration sheets: Configurations with AlgoPilot B3Q...
Configuration sheets 43.1 CI1142 in housing H38... (flat) System: Type of detector line Interactive Interactive Ex AnalogPLUS FDnet MS9i Collective Number of detector addresses – Number of detector lines Fire controls For 30V For 250 V Number of control outputs Plug-in modules E3M060 ●...
Configuration sheets 43.2 CI1142 in housing H38... (deep) System: Type of detector line Interactive Interactive Ex AnalogPLUS FDnet MS9i Collective Number of detector addresses – Number of detector lines Fire controls For 30V For 250 V Number of control outputs Plug-in modules E3M060 ●...
Configuration sheets 43.3 CI1142 in housing H47… System: Type of detector line Interactive Interactive Ex AnalogPLUS FDnet MS9i Collective Number of detector addresses – Number of detector lines Fire controls For 30V For 250 V Number of control outputs Plug-in modules E3M060 ●...
Configuration sheets 43.4 CC1142/43 in housing H47… System: Type of detector line Interactive Interactive Ex AnalogPLUS FDnet MS9i Collective Number of detector addresses – Number of detector lines Fire controls For 30V For 250 V Number of control outputs Plug-in modules E3X10.
Page 118
Configuration sheets 43.5 CC1142/43 in housing H47… (with extra power supply) System: Type of detector line Interactive Interactive Ex AnalogPLUS FDnet MS9i Collective Number of detector addresses – Number of detector lines Fire controls For 30V For 250 V Number of control outputs Plug-in modules E3X10.
Configuration sheets 43.6 CC1142/43 in housing H67... (Standard) System: Type of detector line Interactive Interactive Ex AnalogPLUS FDnet MS9i Collective Number of detector addresses – Number of detector lines Fire controls For 30V For 250 V Number of control outputs Plug-in modules E3X10.
Page 120
Configuration sheets 43.7 CC1142/43 in housing H67... (with 2 sets of batteries) System: Type of detector line Interactive Interactive Ex AnalogPLUS FDnet MS9i Collective Number of detector addresses – Number of detector lines Fire controls For 30V For 250 V Number of control outputs Plug-in modules E3X10.
Page 121
Configuration sheets 43.8 CC1142/43 in housing H67... (with extended connection panel) System: Type of detector line Interactive Interactive Ex AnalogPLUS FDnet MS9i Collective Number of detector addresses – Number of detector lines Fire controls For 30V For 250 V Number of control outputs Plug-in modules E3X10.
Configuration sheets 43.9 CS1140 in housing H98... or third-party housing This configuration sheet is intended only to specify the mechanical components. The 'CC1142/43 ...' configuration sheets can be used to specify the electronics. Housings, doors, covers Profile bar on H98G600 4161280001 rear panel Cable duct...