Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Overview 1-phase SITOP PSU8200 power supplies from the SITOP modular product line are high- performance, regulated technology power supplies for automated systems and machines. The key benefits of the product include: ● Suitable for connecting to almost any 1-phase line supply around the world ●...
Page 4
Overview ● Remote "ON/OFF" contact for switching the power supply unit output into a no-current state ● To increase the system availability, these reliable power supplies can be expanded using SITOP supplementary modules (redundancy module, selectivity module, buffer module), as well as SITOP DC-UPS modules. Ordering data The following device options are available: Regulated power supply unit SITOP PSU·8200 1ph...
Table of contents Overview..............................3 Safety instructions ........................... 7 Description, device design, dimension drawing..................9 Device description .......................... 9 Connections and terminal designation ..................10 Potentiometer ..........................11 Status displays and signaling ....................... 12 Change-over switch ........................13 Remote contact ..........................14 Block diagram ..........................
Page 6
Table of contents Safety, approvals, EMC ........................41 Safety ............................41 Test voltage ..........................42 Approvals ............................ 43 EMC ............................43 Ambient conditions ..........................45 Applications ............................47 Parallel connection to increase power rating ................47 Parallel connection for redundancy ..................... 49 Series connection for increased voltage ..................
Safety instructions WARNING Correct handling of the devices When operating electrical devices, it is inevitable that certain components will carry dangerous voltages. Therefore, failure to handle the units properly can result in death or serious physical injury as well as extensive property damage. Only appropriately qualified personnel may work on or in the vicinity of this equipment.
Description, device design, dimension drawing Device description SITOP PSU8200 1ph is a primary-clocked power supply for connection to a 1-phase AC line supply. An electronically regulated DC voltage that can be set via a potentiometer is available at the output of the device. The output of the device is isolated, no-load proof and short-circuit proof.
Description, device design, dimension drawing 2.2 Connections and terminal designation Connections and terminal designation ① The line input terminals can be used to establish the connection to the supply voltage. ② The output terminals are used to connect to the loads to be supplied (see also section Installation (Page 27)).
Description, device design, dimension drawing 2.3 Potentiometer Potentiometer ③ The potentiometer on the front of the device is used to set the output voltage. The output voltage is set to 24 V in the factory and can be adjusted in the range 24...28.8 V; for example, to compensate voltage drops across long supply lines to the connected load.
Description, device design, dimension drawing 2.4 Status displays and signaling Status displays and signaling 6EP3333-8SB00-0AY0 (24 V/5 A) 6EP3334-8SB00-0AY0 (24 V/10 A) ④ Green LED for 24 V O.K. Status indicator Yellow LED for overload in "constant current" mode Red LED for latching shutdown in "shut down" mode ⑤...
Description, device design, dimension drawing 2.5 Change-over switch Change-over switch Figure 2-5 Selector switch (example: 6EP3333-8SB00-0AY0) The two switches A and B are used to influence the output characteristic curve: Switch Parallel operation: Single operation: Delivery state influences the output 'Soft' characteristic curve (see, e.g.
Description, device design, dimension drawing 2.6 Remote contact Remote contact 6EP3333-8SB00-0AY0 (24 V/5 A) 6EP3334-8SB00-0AY0 (24 V/10 A) ⑤ Non-isolated input for remote ON/OFF switching of the power supply. Remote contact (15, 16) Function: The device is remotely switched off when contacts 15 – 16 are short-circuited (R <...
Mounting/removal WARNING Installing the device in a housing or a control cabinet The SITOP PSU8200 1ph power supply is a built-in device. It must be installed in a housing or control cabinet, to which only qualified personnel have access. The device can be mounted in a control cabinet on standard mounting rails according to EN 60715.
Page 20
Mounting/removal WARNING Use in hazardous zones If the devices are installed in a hazardous zone (Ex II 3G Ex nA nC IIC T3 Gc or Ex II 3G Ex nA IIC T3 Gc), they must be installed in a distributor box with degree of protection IP54 or higher.
Mounting position, mounting clearances Standard mounting position The device is mounted on standard mounting rails according to EN 60715. The device must be mounted vertically in such a way that the input terminals and the output terminals are at the bottom to ensure correct cooling. A clearance of at least 50 mm should be maintained above and below the device (maximum depth of the cable duct, 50 mm).
Page 22
Mounting position, mounting clearances 4.1 Standard mounting position Figure 4-3 Mounting height derating For details, see Ambient conditions (Page 45) SITOP PSU8200 1ph Operating Instructions, 06.2014, C98130-A7633-A1-2-7629...
Mounting position, mounting clearances 4.2 Other mounting positions Other mounting positions For mounting positions that deviate from the standard mounting position, derating factors (reduction of the output power or the permissible ambient temperature) must be observed in accordance with the following diagrams. Note In the case of mounting positions that deviate from the standard mounting position, reduced mechanical resistance of the devices against vibration and shock must be expected.
Page 24
Mounting position, mounting clearances 4.2 Other mounting positions Figure 4-6 6EP3333-8SB00-0AY0 mounting position (3) Figure 4-7 6EP3333-8SB00-0AY0 mounting position (4) Figure 4-8 6EP3333-8SB00-0AY0 mounting position (5) SITOP PSU8200 1ph Operating Instructions, 06.2014, C98130-A7633-A1-2-7629...
Installation WARNING Hazard due to electric shock Before installation or maintenance work can begin, the system's main switch must be switched off and measures taken to prevent it being switched on again. If this instruction is not observed, touching live parts can result in death or serious injury. Line-side connection The SITOP PSU8200 1ph power supply is designed for connection to a 1-phase AC line supply with a rated voltage of 120/230 V AC, 50/60 Hz.
Page 28
Installation 5.1 Line-side connection Protection SITOP PSU8200 1ph Line-side protection 6EP3333-8SB00-0AY0 Recommended: Miniature circuit breaker (IEC 898) characteristic C, 6 A (24 V/5 A) 6EP3334-8SB00-0AY0 Recommended: Miniature circuit breaker (IEC 898) characteristic C, 10 A (24 V/10 A) The protective conductor of the line supply must be connected at the PE terminal. Other country-specific regulations may have to be observed when installing the device.
Installation 5.2 Output-side connection Output-side connection At its output, the SITOP PSU8200 1ph power supply provides an isolated (= non-grounded) SELV output voltage (Safety Extra Low Voltage). The output of the power supply is no-load, overload, and short-circuit proof. If an overload occurs, the electronic current limiting function limits the output current to a maximum value (see section Technical data (Page 31)).
Technical data Note Technical data is applicable for a rated input voltage, rated load and +25° C ambient temperature (if nothing else is specified). Input 6EP3333-8SB00-0AY0 6EP3334-8SB00-0AY0 (24 V/5 A) (24 V/10 A) Input 1-phase, AC 1-phase, AC Rated voltage value Ue rated 120/230 V 120/230 V Voltage range...
Technical data 6.2 Output Figure 6-1 Power-failure buffering Output 6EP3333-8SB00-0AY0 6EP3334-8SB00-0AY0 (24 V/5 A) (24 V/10 A) Output Regulated, isolated DC voltage Regulated, isolated DC voltage Rated voltage value Ua rated DC 24 V 24 V Total tolerance, static ± Static line regulation, approx.
Page 33
Technical data 6.2 Output 6EP3333-8SB00-0AY0 6EP3334-8SB00-0AY0 (24 V/5 A) (24 V/10 A) Current range 0 to 5 A 0 to 10 A At Ue<100 V / <200 V: 80% Ia rated +60 to +70 °C derating: Remark • approx. 2% Ia rated/K At Ue<100 V / <200 V: 80% Ia rated Output active power / typical 120 W...
Page 34
Technical data 6.2 Output Figure 6-3 Output characteristic curve 6EP3333-8SB00-0AY0 stand-alone operation Figure 6-4 Output characteristic curve 6EP3334-8SB00-0AY0 stand-alone operation The device supplies a constant output voltage until the current limit is reached. In the event of an overload, the output current and the output voltage are reduced. Change-over switch A on: Parallel operation.
Page 35
Technical data 6.2 Output Figure 6-6 Output characteristic curve 6EP3334-8SB00-0AY0 parallel operation Change-over switch B on: Latching shutdown. The device is shutdown if the overload lasts longer than 100 ms. Turning the power supply off for at least 60 seconds causes a reset. Figure 6-7 Output characteristic curve 6EP3333-8SB00-0AY0 latching shutdown Figure 6-8...
Technical data 6.3 Efficiency Efficiency 6EP3333-8SB00-0AY0 6EP3334-8SB00-0AY0 (24 V/5 A) (24 V/10 A) Efficiency at Ua rated, Ia rated, approx. 93 % 94 % Power loss at Ua rated, Ia rated, approx. 18 W No-load operation power loss, approx. 1.5 W 1.5 W Power loss in the "latching shutdown"...
Technical data 6.7 Mechanical system Mechanical system 6EP3333-8SB00-0AY0 6EP3334-8SB00-0AY0 (24 V/5 A) (24 V/10 A) Connection system Screw-type terminal Screw-type terminal Connections / line supply L1, N, PE: 1 screw terminal each L1, N, PE: 1 screw terminal each for 0.2 to 2.5 mm² solid/finely for 0.2 to 2.5 mm²...
Technical data 6.9 Dimension drawing Dimension drawing See section Dimensions and weight (Page 16) CAD data that can be downloaded from the Internet: 6EP3333-8SB00-0AY0 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00963) 6EP3334-8SB00-0AY0 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00966) SITOP PSU8200 1ph Operating Instructions, 06.2014, C98130-A7633-A1-2-7629...
Safety, approvals, EMC Safety 6EP3333-8SB00-0AY0 (24 V/5 A) 6EP3334-8SB00-0AY0 (24 V/10 A) Primary/secondary galvanic isolation Galvanic isolation SELV output voltage Ua according to EN 60950-1 and EN 50178 Protection class Class I Degree of protection (EN 60529) IP20 Leakage current, typ. 1 mA Leakage current, max.
Safety, approvals, EMC 7.2 Test voltage Test voltage Figure 7-1 Test voltage diagram Only the manufacturer can perform the type test and production test; users can also perform the field test. Preconditions for performing the field test: Tests (A) & (B) ●...
Ambient conditions 6EP3333-8SB00-0AY0 (24 V/5 A) 6EP3334-8SB00-0AY0 (24 V/10 A) Ambient temperature -25 ... +70° C with natural convection Tested according to: EN 60068-2-1 cold • EN 60068-2-2 dry heat • EN 60068-2-78 humid heat, constant • EN 60068-2-14 temperature change •...
Applications Parallel connection to increase power rating To increase the power rating, SITOP PSU8200 power supplies of the same type can be directly connected in parallel. The following must be observed: ● The cables connected to each power supply at terminals "+" and "-" must have identical lengths and the same cable cross-sections (or the same impedance) up to a common external connection point (terminal strip) if possible.
Page 48
Applications 9.1 Parallel connection to increase power rating NOTICE Protective circuit for the parallel connection of more than two power supplies For connection of more than two power supplies in parallel, additional measures must be taken to prevent high backward feeding currents in the event of a secondary device fault.
Figure 9-2 Redundant configuration with two power supplies and SITOP PSE202U redundancy module You can find additional information in the: SITOP PSE202U manual (http://support.automation.siemens.com/WW/view/en/42248598) SITOP PSU8200 1ph Operating Instructions, 06.2014, C98130-A7633-A1-2-7629...
Applications 9.3 Series connection for increased voltage Series connection for increased voltage To achieve an output voltage of 48 V DC, two 24 V SITOP PSU8200 power supplies of the same type can be connected in series. In this case, connect the "-" terminal of the first power supply to the "+"...
SIMATIC S7-1200/1500/300/400, for STEP 7 and TIA Portal as well as for SIMOTION CPUs and SIMOTION SCOUT. You can find additional information at: SITOP PSE200U selectivity module manuals (http://support.automation.siemens.com/WW/view/en/10807226/130000) Figure 9-4 Electronic protection of 24 V consumers with the SITOP PSE200U selectivity module SITOP PSU8200 1ph...
5 A. This time can be increased a multiple number of times by connecting buffer modules in parallel; the maximum buffer time is 10 s. You can find additional information at: SITOP PSE201U manual (http://support.automation.siemens.com/WW/view/en/41129219) Figure 9-5 Buffering brief power failures using the SITOP PSE201U buffer module SITOP PSU8200 1ph Operating Instructions, 06.2014, C98130-A7633-A1-2-7629...
PC. You can find additional information at: DC UPS with capacitors manual (http://support.automation.siemens.com/WW/view/en/48932766/133300) Using DC UPS SITOP UPS1600 and SITOP UPS100 battery modules, buffer times in the range of hours can be implemented. Intelligent battery management using Energy Storage Link automatically detects the UPS1100 energy storage device, and ensures optimum temperature-controlled charging and continuous monitoring.
Page 54
– make it easy to integrate operating and diagnostics information into STEP 7 user programs. Preconfigured UPS faceplates for WinCC visualization can be downloaded at no charge. You can find additional information at: DC UPS SITOP UPS1600/UPS1100 Manual (http://support.automation.siemens.com/WW/view/en/84977415) SITOP PSU8200 1ph Operating Instructions, 06.2014, C98130-A7633-A1-2-7629...
Environment The devices are in conformance with RoHS. As a rule, only non-silicon precipitating materials are used. Disposal guidelines Packaging and packaging aids can and should always be recycled. The product itself may not be disposed of as domestic refuse. SITOP PSU8200 1ph Operating Instructions, 06.2014, C98130-A7633-A1-2-7629...
● Phone: + 49 (0) 911 895 7222 ● E-Mail (mailto:support.automation@siemens.com) ● Internet: Online support request form (http://www.siemens.de/automation/support-request) Technical documentation on the Internet Operating instructions and manuals for SITOP are available in the Internet: Operating instructions/manuals (http://www.siemens.de/sitop/manuals) SITOP power supply homepage General news about our power supplies is available in the Internet at the SITOP homepage: SITOP (http://www.siemens.de/sitop)
Page 58
Service & Support Contact persons If you have any questions regarding the use of our products, then contact the Siemens contact person in your regional Siemens sales office. You can find these addresses as follows: ● On the Internet (http://www.siemens.de/automation/partner) ●...