On Delay; Off Delay - Siemens ET 200SP Manual

Technology module tm pulse 2x24v
Hide thumbs Also See for ET 200SP:
Table of Contents

Advertisement

Retriggering the Off delay
In the following case, the module cancels the current Off delay and restarts it with the next
rising edge at digital input DIn.0:
Off delay > Pulse duration + Interpulse period
The following figure shows an example of the retriggering of the Off delay:
Figure 4-8
4.4.1.3

On delay

You set the duty cycle in the control interface (Page 89) using OUTPUT_VALUE as integer
(UDINT). The value range is 0 to 85 s with a precision of 1 µs.
A change takes effect on the next rising edge at digital input DIn.0.
4.4.1.4

Off delay

You set the Off delay from 0 to 85 s with a precision of 1 µs in the hardware configuration.
In addition, you can change the OFF delay via the control interface by entering a new value
in SLOT as integer (UDINT). In so doing, you use the MODE_SLOT control bit to choose
whether you want to apply a change once or cyclically:
MODE_SLOT = 0
MODE_SLOT = 1
You can find additional information under Handling of the SLOT parameters (Page 139).
Technology Module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)
Manual, 05/2019, A5E35061186-AB
Retriggering the Off delay
One-time change:
As soon as you write the value 3
from SLOT is applied once as the OFF delay and kept until the next change.
A change using SLOT takes effect on the next falling edge at digital input DIn.0.
Cyclic change:
When you write the value 19
value from SLOT in each case is applied cyclically as the Off delay.
A change using SLOT takes effect on the next falling edge at digital input DIn.0.
Configuring/address space
in the corresponding output byte, the value
D
in the corresponding output byte, the current
D
4.4 On/Off delay mode