Page 1
Smart valve actuator SSA911.01TH Wireless radiator valve actuator, works with RDS110.R ● RF-controlled actuator communication based on THREAD protocol (2.4 GHz, bidirectional) ● Connection and operation with RDS110.R and optionally RCR114.1 ● Battery-powered by commercially available 1.5 V AA batteries ●...
Page 2
● The SSA911.01TH wireless radiator valve actuator is designed to work on radiator valves of different manufacturers in HVAC applications using M30x1.5 thread. It operates the valve to control the water flow and controls the room temperature. ● The valve actuator works only in combination with Siemens Smart Thermostat RDS110.R and optionally with wireless repeater RCR114.1.
Page 3
15 %. Error codes In case of an actuator malfunction or communication error with the Smart Thermostat, an error code is shown on the display of the SSA911.01TH. See Error codes [➙ 9] Type summary Type Stock no.
Page 4
The theft protection kit secures the actuator; it prevents the batteries from being removed and the actuator from being unscrewed from the radiator valve without the use of a tool. Equipment combinations Siemens valves The SSA911.01TH is suited for use with the following types of Siemens radiator valves: Type Data sheet [m3/h] VDN1.., VEN1..
Page 5
Third-party valves without adapter The SSA911.01TH can operate third-party radiator valves without adapter, provided they have a M30x1.5 mm connecting thread and meet the following requirements: Force 90 N nominal Fully closed x > 9.0 mm Fully open y ≤ 14.5 mm Valves of the following manufacturers may be used with the SSA911.01TH:...
Page 6
The batteries must be new and undamaged. ● Do not mix new and used batteries. Store, transport and dispose of the batteries in compliance with local requirements, regulations and laws. Also observe the instructions of the battery manufacturer. Siemens A6V11739247_en--_a Smart Infrastructure 2020-10-08...
Page 7
2. Remove plastic slip securing the batteries from the SSA911.01TH and wait for the actuator to start up (approximately 5 s) 3. Press the button on the SSA911.01TH for automatic calibration process (> 2 s) and wait for the confirmation of the calibration on the display 4.
Page 8
(< 1 s) exits the function, turns the display off and sends the actuator to sleep mode – long button press (> 2 s) confirms the chosen function ● yes: appears after confirming the function (except during factory reset) ● Go: indicates the confirmed function is starting Siemens A6V11739247_en--_a Smart Infrastructure 2020-10-08...
Page 9
SSA911.01TH. Error codes cannot be acknowledged on the SSA911.01TH. The error code is shown on the display for as long as the error is active and will disappear once normal status has been reached.
Page 10
Replacing the batteries To replace the batteries, the SSA911.01TH should remain mounted on the radiator valve and the Smart Thermostat should remain on power and switched on. Replacing the batteries does not require any tools. For optimal performance, the use of high performance alkaline batteries is recommended.
Page 11
Warranty Technical data on specific applications are valid only together with Siemens products listed under "Equipment combinations". Siemens rejects any and all warranties in the event that third-party products are used. Radio equipment directive The device is using harmonized frequency in Europe, and is also in compliance with the Radio Equipment Directive (2014/53/EU, formerly 1999/5/EC).
Page 12
Medium temperature permissible in connected valve 1…70 °C Directives and standards Product standard IEC 60730-x Electromagnetic compatibility (field of use) For residential, commercial, and industrial environments EU conformity (CE) A5W00090263A EAC compliance Eurasian compliance for all SAY..P.. Siemens A6V11739247_en--_a Smart Infrastructure 2020-10-08...
Page 13
M30x1.5 W x H x D See Dimensions [➙ 13] Weight Completely mounted Documents can be downloaded at http://www.siemens.com/bt/download Dimensions Dimensions in mm [kg] 0.305 Revision numbers Type Valid from rev. no. SSA911.01TH ..01 S55181-A101 Siemens A6V11739247_en--_a Smart Infrastructure 2020-10-08...