2.3.4 EVENTS
0
9
METER
2.3-02
INTRO
BREAKER
TRIP UNIT
LOCKS
ACCESSORIES
2.3.4 EVENTS mode
EVENT LOGGING
The trip unit keeps a log of the last 10 events:
-- Over current trips
-- Protec ve relay trips
-- Shunt trip (Op onal, if the coil contact is used)
-- Under voltage Release trip (Op onal, if the coil contact is
used)
-- BIM Trip Unit Mismatch - Breaker Interface Module
The following informa on is stored with each event:
-- RMS currents
-- Phase
-- Type of trip
-- Trip counter
-- Time and date stamps
Trips are logged under self power without me stamp. Events
with me stamps are only logged when 24VDC control power is
available.
KEY
Enter
(Save)
Up
Down
SETUP
METER
STATUS
EVENTS
EVENT 0
EVENT 9
Back to
EVENTS
TESTS
APPENDIX
Right (Next)
Left (Previous)