Diagnostic blocks in S7 standard mode and in the redundancy mode
The table below shows the lengths of the diagnostics blocks and their offset in the diagnostics
frame.
Table 11-1
Length and offset of the diagnostic blocks in S7 standard mode and in redundancy mode
Diagnostic block
Default diagnostics
Identifier-related diagnostics
Module status
Status message
H status
Interrupt section
Total length
* only if interrupts are reported
11.2.2
Structure of the diagnostic blocks
11.2.2.1
Default diagnosis
Format of the default diagnostics
The default diagnostics consists of 6 bytes and is subdivided as follows:
Figure 11-1
Compact FF Link
Operating Instructions, 03/2015, A5E35651552-AA
Length in bytes
6
6
13
38
8
(max. 63 *)
Format of the default diagnostics
Alarm, error, and system messages
11.2 Diagnostics of the Compact FF Link
Offset in the non-redun‐
dancy mode
0
6
12
25
-
(63 *)
63
(max. 126 *)
Offset in the redundancy
mode
0
6
12
25
63
(71 *)
71
(max. 134 *)
65