13
Overview of All Actions
What does this chapter describe?
This chapter describes all the actions you can use when programming with S7-
Graph.
S7-Graph uses the settings for the mnemonics (SIMATIC or International) selected
in the "Language" tab page in the SIMATIC manager with the menu command
Options > Customize.
13.1
Standard Actions with and without Interlock
These actions are executed each time the sequencer is run through.
Action
Event
In-
Address
struc-
Area
tion
N
Q,I,M,D* m.n
S
Q,I,M,D* m.n
R
Q,I,M,D* m.n
D
Q,I,M,D* m.n
L
Q,I,M,D* m.n
CALL
FB, FC,
SFB,
SFC
NC
Q,I,M,D* m.n
S7-GRAPH for S7-300/400 Programming Sequential Control Systems
C79000-G7076-C526-01
Location
Time
Constant
T#<const> n seconds after step activation the signal
T#<const> If the step is active, the address has
Block
number
Explanation
As long as the step is active, the signal
state of the address is 1.
As long as the step is active, the address
is set to 1 and then remains set to 1.
As long as the step is active, the address
is set to 0 and then remains set to 0.
state of the address is 1 for the duration
of the step activation. This does not apply
if the step is active for a time shorter than
n seconds.
signal state 1 for n seconds.
As long as the step is active, the
specified block is called.
As long as the step is active and the
condition (interlock) is satisfied, the signal
state of the address is 1.
Address
range
0.0 to
65535.7
0.0 to
65535.7
0.0 to
65535.7
0.0 to
65535.7
0.0 to
65535.7
0.0 to
65535.7
13-1