Indication
Warning level T>
DM-F - Test requirement
Miscellaneous - General
Indication
External Fault 1 to 6
Analog Module 1/2 open circuit
Thermistor short circuit
Thermistor open circuit
Temperature Module 1/2 sensor
fault
Temperature Module 1/2 out of
range
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
Meaning/Possible cause/Acknowledgement/Error processing
Temperature module 1/2 - warning level overshot.
Check the temperature measuring station.
Further information: Analog Temperature Monitoring (Page 65).
The DM-F Local / DM-F PROFIsafe enabling circuits have not
been opened and closed again within the configured time period.
The function of the enabling circuit relay contacts can only be
tested when they are switched.
Please adopt the measures intended for this case.
Meaning/Possible cause/Acknowledgement/Error processing
A signal is pending at the input (socket) of the standard
function.
External fault 1, 2, 3, 4,5 or 6.
Check the motor feeder.
Further information: External Fault (1 to 6).
A wire break has occurred in the analog value measuring
circuit.
Check the measuring transducer and the measuring circuit.
Acknowledge with "Reset".
Further information: Analog Module.
A short circuit has occurred in the thermistor sensor cable.
Check the thermistor sensor cable and the thermistor.
After fault repair acknowledge with "Reset".
Further information: Thermistor (Page 30).
A wire break has occurred in the thermistor sensor cable.
Check the thermistor sensor cable and the thermistor.
After fault repair acknowledge with "Reset".
Further information: Thermistor (Page 30).
Either a short circuit or a wire break has occurred in the
temperature sensor circuit.
Check the temperature sensor and the sensor cable.
Acknowledge with "Reset".
The temperature sensor is yielding values which are not
permitted.
Check the temperature sensor.
Acknowledge with "Reset".
Online Settings and Displays
17.11 Warnings