Tests

3.1 Visual inspection

3.1
Visual inspection
The visual inspection is performed to ensure that the drive complies with the requirements of
the order. The individual test steps are performed with the drive in a no-voltage condition.
The test together with the customer – or his representative – is carried out with the drive
installed and labeled. The results of all of the tests are documented in the acceptance report.
3.1.1

Rating plate

Fundamentals
The technical data and ordered options on the rating plate and the routine test certificate are
checked to ensure that they match up.
Test procedure
1. The data on the rating plate and the routine test certificate are visually compared.
Result
The test is passed if the data match up.
3.1.2

Housing degree of protection

Fundamentals
A check is made as to whether the housing degree of protection ordered complies with what is
described in the catalog.
Test procedure
1. The housing degree of protection is identified based on what is stamped on the rating plate.
2. Depending on the version, the following components are visually checked, e.g.:
18
– Canopies
– Cooling slots
– Fittings and rubber seals in the doors and between the cabinet units
– Cable entries
– Openings for water pipes, if available
– Additional components, if available
SINAMICS GL150 6SL3850 F03 F70 F98 E11
Reference Manual Rev.201902141420 GL150 luftgekühlt