SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Introduction Security recommendations SIMATIC Ident Description Mounting RFID systems SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Connection Configuring Operating Instructions Configuring with the WBM Programming Service and maintenance Technical data Dimension drawings Appendix Syslog messages Service &...
Page 2
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Assigning an IP address via DHCP ..................53 Configuration via PROFINET IO (STEP 7) ................54 Configuration via XML ....................... 61 Configuration via OPC UA....................61 Configuring with Studio 5000 Logix Designer ..............62 SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 4
Update firmware via TIA Portal (STEP 7 Basic / Professional) ..........141 9.3.3 Updating the firmware of the reader via WBM ..............141 9.3.4 Updating firmware of the readers using the TIA Portal (STEP 7 Basic / Professional) ... 143 SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 5
Certificates & approvals....................173 Syslog messages ..........................177 Structure of the Syslog messages ..................177 Variables in Syslog messages ................... 178 List of Syslog messages ....................179 Service & Support ..........................183 SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
You can find information on the readers and optical readers to be connected in the manual of the respective product family (RF200, RF300, MV400, and MV500). You can find the current versions of the various manuals on the pages of the Siemens Industry Online Support (https://support.industry.siemens.com/cs/ww/en/ps/14970/man).
Page 8
Do not dispose of the products at public disposal sites. For environmentally compliant recycling and disposal of your electronic waste, please contact a company certified for the disposal of electronic waste or your Siemens representative. Adhere to the various country-specific regulations.
• The devices have "Low-level service access" that can only be enabled via additional hardware interconnection. The access is used to enable Siemens personnel to perform advanced examination for servicing. The access may only be used by qualified service personnel.
Page 10
• We recommend that you use certificates with a key length of at least 4096 bits. • If protocols support both certificates and keys, you should favor certificates. • With operation via OPC UA, always use the "Sign and encrypt" security method. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 11
Make use of the possibility to prevent write access. The product offers corresponding settings for this. • If SNMP is activated, change the community names. If no unrestricted access is necessary, restrict access over SNMP. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 12
Applies to protocol number 10001, all others are closed. Only outgoing, when configured. Explanation of the table: • Authentication Specifies whether authentication of the communication partner takes place. • Encryption Specifies whether the transfer is encrypted. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure to...
Properties of the communications modules Area of application The SIMATIC RF185C, RF186C, RF188C, RF186CI and RF188CI communications modules are designed for use in all areas of automation within an access-protected area. It covers all areas in which SIMATIC Ident RFID readers and optical readers are operated. Due to the large variety of interfaces - PROFINET, EtherNet/IP, OPC UA, and XML - the application can run at the field level on an S7 or Rockwell controller, on a PC or at the IT level.
Page 16
For security reasons, you should only operate the device within a protected network area and not connect it directly to the Internet. You can find additional information on the various RFID devices and optical readers on the Internet on the "Siemens Industry Online Support (https://support.industry.siemens.com/cs/ww/en/ps/14970/man)" page. Features...
OPC UA or XML user. If you want to adapt the communication modules to your requirements, we recommend the following user-specific procedure: SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 18
You can find information on this in the section "Configuration via OPC UA (Page 61)" or "Configuring with the WBM (Page 63)". 4. Program reader commands You can find information on this in the section "Programming via OPC UA (Page 116)". SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 19
Only the sections with user-specific content, in other words, content that is interface-specific, contain these symbols. Sections without these symbols are general and relevant for all areas of application. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
⑤ 2x interfaces for the power supply (M12, 4-pin, L-coded) Figure 3-2 Design of the communication module The I/O interface and I/O-LEDs are only a feature of the CI devices. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 21
TIA Portal or another engineering system. The GSDML file is stored on the communication module and can be downloaded from it using a Web browser. You can also find the GSDML file at the website of Siemens Industry Online Support. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI...
Note Mounting the communication modules Only install the communication module when supply voltages are switched off. You do not have to observe any special rules when installing the communication modules. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
If you need washers, use washers conforming to DIN EN ISO 7089 / DIN EN ISO 7090. Cylinder head screw with M4 hex socket according to DIN EN ISO 4762 SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 25
(≤ 1.2 Nm) onto the panel at both fastening points (front top and bottom). ① Elongated hole: 4.5 mm width × 5.0 mm height Figure 4-1 Installing RF18xC/RF18xCI communication module SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 26
The following figure shows the upper left fastening point for 2.5 mm wide cable ties. Figure 4-2 Fastening the RF18xC/RF18xCI communication module with cable ties SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
You will find the currently valid markings and approvals on the nameplate of the communication module. All other markings and approvals are currently based on an altitude up to 2,000 m. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 28
Mounting 4.3 Use at altitudes over 2,000 m SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
A data transfer terminal (modem, for example) is required to access the WAN (Wide Area Network) in order to ensure compliance with this safety standard. All supply and signal voltages must be safety extra low voltage (SELV/PELV according to IEC 61140). SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
With a line/series topology, remember that if the communication connection of a communication module to the controller is interrupted, the communication connection to all downstream communication modules is also interrupted. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 31
The closing of the line topology to form a ring is via two network ports of one of the devices (ring ports). The communication modules can be integrated as clients in an MRP ring topology via the network ports "X1P1R" and "X1P2R". SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
When the communication module is set up with grounded reference potential, any interference currents that occur are diverted to functional ground. The connections must be connected externally (connection between 1M and FE). SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 33
Fuses for line protection (automatic circuit breaker for 16 A) ④ When setting up the communication module with an ungrounded reference potential, there is no connection between 1M, 2M, and FE Figure 5-5 Electrical design SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 34
Isolation monitoring must be provided in the following cases: • Design of the communication module with an ungrounded reference potential • If hazardous plant states can be expected as a result of faults. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
The following figure shows the potential relationships of the communication modules. Figure 5-6 Potential relationships of the communication modules Circuit breaker According to IEC 60364, line protection is required, i.e. the supply lines must always be protected externally. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 36
I/O interface. The following figure shows a configuration with another voltage supply for the communication modules. The different potential groups are highlighted in gray. Figure 5-7 Wiring of the power supply SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
You need the following tool to connect to the functional ground: • Screwdriver Accessories required You need the following accessories to connect to the functional ground: • Fastening screw (M4) and washer SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 38
Ensure there is a low-impedance connection between the communications module and the conductive base and between the conductive base and functional ground. ① Grounded, metallic base ② Unpainted thread or nut support Figure 5-8 Mounting the CM on a conductive base SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
To connect to functional ground with a non-conductive mounting base, you can need the following accessories: • Fastening screw (M4) and washer • Cable lug suitable for M4 screws • Ground conductor cable (copper braid) with a minimum cross-section of 4 mm SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 40
Grounding with non-conductive mounting base Ensure a low impedance connection between the communications module and functional ground. Figure 5-9 Mounting the CM on a non-conductive base / connection to functional ground SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
You can loop the supply voltages and PROFINET IO via the M12 round sockets ⑤ + ⑥. The pin assignments of the various interfaces are lasered on the side of each communication module at the factory. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 42
• for PROFINET IO connection M12 plug (4-pin, D-coded) and 4-wire Ethernet cable (Twisted Pair, shielded) You can find the associated article numbers in the section "Ordering data (Page 170)". SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 43
Pin assignment power supply; M12 socket (4-pin, L-coded) Assignment View of M12 socket, 4-pin L1: +24 V (brown) N2: 0 V load supply (white) Relevant for RF18xCI devices N1: 0 V (blue) L2: +24 V (black) SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 44
2L+: +24 V, for IO-Link module Class B 1N: GND, IO-Link C/Q: Data cable for • IO-Link • a single digital input • a single digital output 2N: GND, for IO-Link module Class SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 45
Connector for connecting digital inputs/outputs (M12, 5-pin, A-coded) ③ Connector for the power supply (M12, 4-pin, L-coded) ④ Connector for PROFINET IO connection (M12, 4-pin, D-coded) Figure 5-11 Connect the plug SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
If you do not observe the maximum permissible supply current and the cable cross- section required, this may result in the cable isolation and contacts overheating and in the device being damaged. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
0.2 V. The value can vary significantly depending on the plug connection or condition. When using a 7 m power cable with ∅ 1.5 mm , the voltage drop is approx. 2.6 V with a 16 A load. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 48
Connection 5.7 Effect of cable length on the supply voltage SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
These alternative methods are described below. 6.1.1 Assigning the IP address / device name with STEP 7 Requirements STEP 7 Basic / Professional is installed, the communications module is connected and has started up. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 50
Procedure Proceed as follows to assign a unique device name to the communications module: 1. Open the TIA Portal with "Start > All Programs > Siemens Automation > TIA Portal Vxx". 2. Create a new project. 3. Change to the Project view.
Page 51
3. Select the option "Functions > Assign name". 4. Click the "Flash LED" button. Reaction: The LEDs on the selected communications module flash. 5. Click the "Flash LED" button again to stop the flashing. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Assigning the IP address / device name with SINEC PNI Requirements SINEC PNI is installed and the communication module is connected and running. You can find the SINEC PNI on the pages of the "Siemens Industry Online Support (https://support.industry.siemens.com/cs/ww/en/ps/26672/dl)". Procedure...
6. Double click on an entry in the "Request History" area. The input screen "New Entry" opens. 7. Enter a new unique IP address of the reader in the "IP Address" input box. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
The GSDML file corresponding to the communications module is stored on the communications module and can be downloaded from it via WBM ("The "System - Device settings" menu item (Page 110)"). You can also find the GSDML file at the website of Siemens Industry Online Support.
Page 55
Note: WBM can only be started when the IP address stored in the project has been assigned to the communication module. This means that the device name must have been assigned and the TIA configuration must be loaded into the SIMATIC controller. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 56
• Freeport: Submodule for connecting SIMATIC RF1000, MV32x and other serial devices. • RF300 fast protocol: Submodule for connecting the SIMATIC RF300 readers (2nd Generation, as of FW 1.8) • Reader: Submodule for connecting the SIMATIC RF200 and RF300 readers SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 57
57.6 kBd communication module and the reader. 115.2 kBd When an optical reader is connected: The 921.6 kBd transmission speed selected here must match the transmission speed selected for the reader. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 58
IO-Link Single digital input • Output: Single digital output • IO-Link: Mode for connection of an IO-Link device with digital inputs/outputs. This parameter is only included for RF18xCI communications modules. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 59
The stop bits are appended to every transferred character during transmission. Interface RS422 RS422 Selection of the interface type that the connected hardware (reader / optical readers) RS232 uses. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 60
"On receipt of the end delimiter(s)". The selected end delimiter combination limits the length of the frame. Parameter value depending on the "Data bits" parameter. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Configuration of the communication module is not necessary for pure OPC UA work. You can continue directly with configuration via WBM and with programming via OPC UA. You will find detailed information on this in the manual "OPC UA for SIMATIC Ident (https://support.industry.siemens.com/cs/ww/en/ps/14971/man)". SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
4 bytes of the MAC address of the communication module. Note Tested programs The content described in this section was tested with the programs "Studio 5000 Logix Designer" (V21 to V28) and "RSLogix 5000" (V20). SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
IP address. To achieve a good workflow with the WBM, we recommend that you use a PC that meets the following minimum requirements: • CPU: DualCore • RAM: 2 GB SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 64
Both IP addresses must be located in the same subnet. • Make sure that the connection is not blocked by a firewall. • Use a ping request to check the connection between the PC and the communication module. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 65
Depending on whether the authentication is enabled or disabled, you may have to log in with your user name and the corresponding password. The WBM homepage opens after logging in, even if authentication is disabled. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
The WBM start window is divided into the following areas: ① Toolbar / status bar (including logout area) ② Menu tree ③ Main window ④ Message area Figure 7-2 Start window of the WBM SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 67
Remember that this data is only loaded in the WBM. To transfer the data to the communication module, you also need to click the "Transfer configuration to communication module" button. Key combination: Ctrl + O SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 68
• This symbol indicates that it is a change that leads to a restart of the communications module when it is transferred. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 69
You will find a list of the restrictions in the section "The "User management" menu item (Page 104)". Main window ③ The main window shows the contents of the selected menu items. Here, you can configure the various menu-dependent parameters. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
The "Start page" menu item The "Start page" menu item is divided into the following areas: • Device-specific information • Project ID • Address information • Device clock • Configuration display SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 71
"SINEC PNI" and "STEP 7". Via the link "IP Address" you jump to the "System settings" menu item in which you can also reassign the IP address. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 72
With the "Flash" check box, you can have the LEDs of the communication module and the readers connected to it flash. This enables you to quickly and easily identify the connected devices on sight. Note that this function is not supported by all readers. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Recording of the status frames for PLC communications. Can be switched off if the status frames are used as line monitoring. In this way, the logbook is kept free for user data. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
The settings of each interface are identically structured and divided into the following areas: • Basic settings • Reader parameters SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 75
If no device is connected to the interface, select the "Empty module" parameter value. RF380R RF300 Gen 2 general RF380R Gen 2 MV400/MV500 General reader RF300 fast protocol RF380R fast protocol Freeport RF1000 MV300 SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 76
Using the "Update firmware" link, you jump to the "System - Reader firmware" menu item in which you can update firmware for the connected reader. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 77
"init_run" or "WRITE-CONFIG" with "Init" (RESET) or after the successful execution of a command. Max. number of 1 ... 40 Number of transponders expected in the transponders antenna field. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 78
• RF290R – Range of values: 0.50 ... 5.00 W – Default value: 1.00 W • RF380R – Range of values: 0.50 ... 2.00 W – Default value: 1.25 W SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 80
Stop bits Selection of the number of stop bits that indicate the end of a character. The stop bits are appended to every transferred character during transmission. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 81
Depending on the data transmission speed the character delay time is limited to a minimum value. Note that the ASCII driver also pauses between two frames during transmission. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
• IO-Link: Mode for connection of an IO-Link device with digital inputs/outputs. Depending on the selection made here, the "IO-Link process data assignment" and/or "Digital inputs/outputs" reports are then displayed. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 83
You can select the connected IO-Link device in the "IO-Link process data assignment" area via the "IO-Link device" drop-down list. If an IO-Link device from Siemens has been selected, the Mapping lines are automatically populated accordingly and the bit assignment is displayed.
The "Network interfaces" tab The "Network interfaces" tab is divided into the following areas: • Network basic settings • SNMP • NTP • Syslog messages SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 85
LLDP is a protocol for monitoring the neighborhood. Note: Make sure that you do not disable the port via which you are currently communicating with the communications module. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 86
Write access is only possible for the SNMP variables "sysName", "sysLocation" and "sysContact" of the "system" group of MIB-II. Allow write Check box to enable/disable write protection for SNMP variables. access SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 87
Text box for entering the address of the Syslog server to which the Syslog server Syslog messages are transferred. Default port Text box for entering the default port of the Syslog server via which the Syslog messages are transferred. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 88
In this area, you can specify whether access to the communications module via EtherNet/IP is allowed. With this setting, the Ethernet interface is closed for EtherNet/IP communication with the controller. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 89
The "XML" tab is divided into the following areas: • XML basic settings • Diagnostic events of XML channel (1-4) Figure 7-9 The "Settings - Communication" menu item, "XML" tab SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 90
User-defined: No default setting. XML communication can be set as desired. XML channel (1-4) Using the input boxes, you can enable/disable the respective XML channels and define the Ethernet ports of the respective XML channels. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 91
The "OPC UA" tab is divided into the following areas: • OPC UA basic settings • Diagnostic events • Security settings Figure 7-10 The "Settings - Communication" menu item, "OPC UA" tab SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 92
Logbook events If the check box is selected, all logbook entries are sent. Transmitting interface (logbook events) Interface (1-4) Selection of the interface via which the selected entries are transmitted. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 93
• If the partner certificate was issued by several CAs (Certification Authorities), all CA root certificates must be stored in the certificate store of the reader. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
In "Diagnostics - Hardware diagnostics", you can display the status parameters of the selected reader and of the transponder currently in the antenna field. This page is divided into the following areas: • Basic settings • Monitoring status • Status • Error counter SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 95
Hardware version of the reader Bootloader version Bootloader version of the reader Firmware version Firmware version of the reader Driver type Driver type of the serial interface of the reader SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 96
P2P master & combined mode with ISO transponder (MDS Dxxx) 0x50 P2P master & combined mode with RF300 transponder 0x4F P2P slave Antenna status Status of the antenna Presence check Set presence check profile SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 97
Received signal strength [dB] for which amplitude modulation with the transponder was detected. PMLI PM power indicator Received signal strength [dB] for which phase modulation with the transponder was detected. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
The menu item "Log" shows all message types that were selected in the menu item "Settings - General" in the "Log settings" area. This menu item documents the actions performed by the communication module. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 99
UTC time, identical to the output in the exported logbook. With a large number of log entries in the history, it may take several minutes before these are displayed. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
The log records internal processes of the communication module and is required for service support by SIEMENS specialists. Only make settings on this page if you are instructed to do so by SIEMENS personnel. The log entries are also evaluated by SIEMENS personnel.
Page 101
• Service file All data of the communications module relevant for diagnostics is stored as an *.slf file. The file only contains information relevant for Siemens service personnel and can only be evaluated by them. With the "ISO 8601 (UTC)" check box, you can convert the data display in the "Date/Time"...
The "Edit transponder" menu item You can read out and write transponder data with the "Edit transponder" menu item. This page is divided into the following areas: • Basic settings • Read/write SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 103
If no values are displayed, this means that no values have yet been read from the transponder. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
This page is divided into the following areas: • User profiles • User properties • Password • Roles • Auto logout • Authentication Figure 7-16 The "User management" menu item SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 105
In addition to this, as the "user", you cannot write to the reader in the "Run" device status. • Administrator User profile with all read/write rights SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 106
As soon as the configured time period has expired, the connection to the communications module is automatically terminated. This ensures that the connection to the communications module is not blocked by an inactive user and is shared with other users. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
You can create your own certificates or use official certificates created by a certification authority. You can import certificates that contain a certificate as well as a private key (PKCS#12). When you import certificates and the SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 108
Note that the selection of the certificate type has an effect on the display of the subsequent parameters. Update Button for refreshing the certificates displayed in the list Updating loads and displays all certificates currently stored in the communications module. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 109
To delete blacklists from the list again, select the desired blacklist in the list and click on the "Delete" button. Blacklist details List with detail information on the selected blacklist Detailed information about the blacklist details is available in the X.509 specifications. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
PC. This page is divided into the following areas: • Firmware update • Reset • Device description files SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 111
• Check You can use the "Check" button to check the integrity of the firmware. You can use this function to check whether the firmware matches the firmware published by Siemens or whether it has possibly been maliciously modified. Factory setting In the "Factory setting"...
Firmware update In the "Firmware update" area, you can update the firmware of the selected reader. For a detailed description of firmware updates, refer to the section "Firmware update (Page 140)". SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Manual With the "Help - Manual" menu item, you can find the manual for the corresponding communications modules "SIMATIC RF185C, RF186C RF188C, RF186CI, RF188CI". Readme OSS In the "Help - Readme OSS" menu item, you will find the Readme OSS file with the copyright information for the open source software contained in this firmware.
Page 114
Configuring with the WBM 7.3 The menu items of the WBM SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Programming via SIMATIC controller This section is intended only for S7 users. You can program and configure the SIMATIC RF185C, RF186C, RF188C as well as the RF186CI and RF188CI communication modules using Ident instructions via a SIMATIC controller. To configure Ident systems using STEP 7 Basic / Professional (TIA Portal), you need appropriate Ident instructions.
RF18xCI CM. Because the physical output value of the CM can deviate from the process image value of the controller through internal linking, each physical output value is also mapped as additional input in the controller. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 117
<Device name> .CH04 :I.Data[3] :O.Data[3] CM Configuration <Configuration variable> <Device name> <Device name> Module .CM_Configuration :I.Data[4] :O.Data[4] The number of available channels depends on the Ident device and device versions used. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
• Via the LED displays of the communication modules • Via SNMP • Using WBM • Via the TIA Portal (STEP 7 Basic / Professional) • Via XML • Via OPC UA These alternative methods are described below. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Indicates that there is a link via the Ethernet interface "1". • LINK P1 (X1 P1R) Indicates that there is a link via Ethernet interface "2". • LINK P2 (X1 P2R) Figure 9-1 LED displays of the RF18xC/RF18xCI communication module SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 121
LED test while the CM is starting up. The flash test is performed for reader identification. At the same time, the LEDs of the reader and PROFINET/Ethernet LED display also flash. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 122
The interface is located in the "IO-Link" configuration. An IO-Link device is connected and was recognized. There may be an error at the input/output (e.g. short-circuit). The load voltage (2L+) is not connected. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
You can find information on SNMP in the section "The "Settings - Communication" menu item (Page 84)". You can find detailed information on using SNMP and, in particular, on the structure of the SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
In the "Log" menu, you can find all the diagnostics messages of the communication module that have occurred. The "Service log" helps SIEMENS specialists to analyze errors. You can read out the syslog messages from the "Syslog log" and you can read out the "Status parameters"...
Page 125
– Under the "PROFINET interface" entry, you can find status information and further information about the PROFINET interface. Figure 9-2 Display of the diagnostics information of the communication module SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Using the OPC UA variables and events, you can read out diagnostic messages and query them in a targeted manner. You can find detailed information on the diagnostic options in the manual "OPC UA for SIMATIC Ident (https://support.industry.siemens.com/cs/ww/en/ps/14971/man)". SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Diagnostic interrupts (communication module diagnostics) If the diagnostic interrupt has been activated ("On"), the following diagnostic interrupts are reported: • Fault in power supply • Hardware fault • Firmware error SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 128
The event no longer exits. For transient events - e.g. soft errors, the reset is delayed by 3 seconds. Further information You can find detailed information on diagnostics on PROFINET IO in the manual "SIMATIC PROFINET system description (https://support.industry.siemens.com/cs/ww/en/view/19292127)". SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
The address range of the transponder has been exceeded. Possible causes: • Start address of the command start has been incorrectly set. • Wrong transponder type • The area to be written to is write-protected. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 130
The transponder has too little power to execute the command. Possible causes: • Transponder is in the limit area. • The transmission/radiated power of the reader or antenna is too low. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 131
More transponders are located in the transmission window than can be processed at the same time by the reader. • There is more than one transponder in the transmission window. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 132
The specified tag field of the transponder is unknown. 0xE4FE8A00 General error 0xE4FE8B00 No or bad configuration data/parameters were transferred. Possible causes: • You are accessing a read point that is not configured. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 133
Incorrect sequence number order (SN) on the reader/communication module 0xE5FE0200 Incorrect sequence number order (SN) in the Ident profile Possible cause: User mode "Ident profile/RFID standard profile" is not set in the device configuration. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 134
The "AdvancedCmd" block was supplied with an incorrect "CMD". • The "CMD" input of the "AdvancedCmd" block was overwritten. Freeport: Incorrect command parameters or unauthorized command chaining (incorrect length specification) 0xE6FE0200 Invalid command index (CI) SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 135
After eliminating the error, execute an "INIT". • Check the parameter "IID_HW_CONNECT". 0xE6FE8100 A parameter is missing. 0xE6FE8200 The parameter has an invalid format. 0xE6FE8300 The parameter type is invalid. 0xE6FE8400 Unknown parameter. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
"Log" in the section "The "Diagnostics - Log" menu item (Page 98)". 9.2.3 XML error messages A list of the possible XML error codes can be found in the "XML programming for SIMATIC Ident (https://support.industry.siemens.com/cs/ww/en/view/109781631)" manual. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
The address range of the transponder has been exceeded. Possible causes: • Start address of the command start has been incorrectly set. • Wrong transponder type • The area to be written to is write-protected. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 138
The carrier signal is not activated. ERROR good RF_COMMUNICATION_ General radio protocol error ERROR good DEVICE_FAULT Fault in power supply The power supply is very close to the low limit. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 139
A parameter is missing. Argument BadInvalid The parameter has an invalid format. Argument BadInvalid The parameter type is invalid. Argument BadInvalid Unknown parameter. Argument The command or the frame has an invalid format. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
"RUN" LED is lit/flashes green. Note that the startup process takes approx. 1 minute after a firmware update. The updated firmware is active following the restart. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
• The communication module is connected to the PC via Industrial Ethernet or PROFINET. • The connected reader supports the firmware update. • To avoid complications, all user applications should be ended. • The required update file (*.sfw) is stored locally. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 142
Result: The firmware of the reader is updated. The update process is indicated in the information bar. After the update has completed, the reader is restarted. The updated firmware is active following the restart. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
– Note: If the check box is not selected, the new firmware is only activated on the next startup of the communication module. 10.Click the "Start upgrade" button. Result: The firmware is updated. The update process is displayed. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
"RUN" LED is lit/flashes green. After restarting the communications module, you may have to assign a new IP address or a new device name to the communications module. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
"RUN" LED is lit/flashes green. After restarting the communications module, you may have to assign a new IP address or a new device name to the communications module. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
With the factory settings, the IP address is obtained via a DHCP server. After restarting the communications module, you may have to assign a new IP address or a new device name to the communications module. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
• Using the TIA Portal (STEP 7 Basic / Professional as of V15.1) in a STEP 7 project • Using the WBM on your PC These alternative methods are described below. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
When configuring with HSP, in the "Configuration management" entry, you can save the configuration of the communication module in your project and also load this into the communication module again. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Prior to installation, connecting up and commissioning, read the relevant sections in the manual of the SIMATIC controller you are using. When installing and connecting up, keep to the procedures described in the manual. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 150
8. If necessary, assign a unique IP address and a unique device name to the communications module. 9. Load the configuration onto the communications module, if applicable. 10.Configure the user management according to the requirements of your application. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 151
• The "Device replacement without exchangeable medium" option is enabled in the PROFINET settings of the module. • The new communications module is in the factory state, i.e. no device name and no IP address have been assigned. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
< 100 m at 921.6 Kbaud dependent on reader (preassembled cables 2 ... 50 m; for other standard cables and custom assembled cables, refer to the section "Connecting cables to the reader") SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 154
All supply and signal voltages must be safety extra low voltage (SELV/PELV according to IEC 61140) 24 V DC supply: Safety (electrical) isolation of low voltage (SELV/PELV acc. to IEC 61140) SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
"Connecting cables to the reader") I/O interface Connector M12 interface, 5-pin, A-coded Max. cable length 20 m Connectable I/O devices • Input • Output • IO-Link module (Input/Output module; Class A, B) SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 156
All supply and signal voltages must be safety extra low voltage (SELV/PELV according to IEC 61140) 24 V DC supply: Safety (electrical) isolation of low voltage (SELV/PELV acc. to IEC 61140) SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
All dimensions in [mm]. ① Elongated hole: 4.5 mm width × 5.0 mm height Figure 11-1 Dimension drawing of an RF18xC communication module The figure shows an RF188C communication module. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 158
Dimension drawings ① Elongated hole: 4.5 mm width × 5.0 mm height Figure 11-2 Dimension drawing of an RF18xCI communication module The figure shows an RF188CI communication module. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
The SIMATIC Ident Configuration Guide is an ID-specific guide that supports you in selecting the products relevant for your Ident system by clearly displaying all compatible devices and connecting cables. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
A reader connector with screw terminals is available for self- assembly (see the relevant system manual). Cables and reader connectors can be ordered using the TIA Selection Tool or the SIMATIC Ident Configuration Guide. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 161
-RxD Brown Green +RxD Yellow +TxD +5 V Gray -TxD Pink Functional Functional Metal mesh ground / ground / shielding shielding The wire color relates to the connecting cable "6GT2891-4Fxxx". SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
1.6 m. Due to its coiling, it can be extended to a length of 4 m during operation. A preassembled cable is also available for connection of the SIMATIC RF1040R/RF1070R readers. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
2. Select the user mode "FB 45" or "Ident profile". 3. Set all other parameters as required. Please note the specifications in the next paragraph. 4. Download the configuration to the controller. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 164
By scanning the code, all relevant parameters for the communication between the communications module and the optical handheld reader are set: • Interface: RS232 • Transmission speed: 115.2 kBd • Data bits: 8 • Parity: None • Stop bits: 1 SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
No length information in the result; max. net data 233 bytes Write Sending data The address must be specified as "0xFFFF". Max. net data 233 bytes (without length information); no error message if the length is exceeded SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 166
"Read" command. After data transmission to the controller, the presence bit is reset unless new data has already been received. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Depending on the channel in which the module is used, you must adapt the module name accordingly ("_2" for channel 2). • SIMATIC RF18xC In the "Ident device" parameter, select the module of the corresponding channel (e.g. "Reader_1" for "Channel1"). SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 169
– Parameter assignment with the "HW_Connect" variable: Adapt the "CM_CHANNEL" and "LADDR" parameters in the "HW_CONNECT" variable. When you establish the connection via an S7-1200/-1500 controller, you must also adapt the "HW_ID" parameter. SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Power supply cable 0.5 m 6XV1801-6DE50 L-coded, 4-pin 1.0 m 6XV1801-6DH10 M12-180 1.5 m 6XV1801-6DH15 2.0 m 6XV1801-6DH20 3.0 m 6XV1801-6DH30 5.0 m 6XV1801-6DH50 10 m 6XV1801-6DN10 15 m 6XV1801-6DN15 SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 171
M12-180 / IE FC RJ45 5.0 m 6XV1871-5TH50 10 m 6XV1871-5TN10 15 m 6XV1871-5TN15 IO-Link cable (Class A) 1.5 m 3RK1902-4PB15-3AA0 M12-180 / M12-180 5.0 m 6GT2891-4MH50 10 m 6GT2891-4MN10 SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 172
Connection cable for wide-range power supply 6GT2091-0PH50 L-coded, 4-pin / A-coded, 4-pin M12-180 / M12-180 M12 sealing caps 3RX9802-0AA00 for unused connections (10 units) Usable as of product version "02" SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
SIMATIC NET/SIMATIC Ident products are regularly submitted to the authorities and approval centers for approvals relating to certain markets and applications. Contact your Siemens representative if you need a list of the current approvals for the individual devices or check the Internet pages of Siemens Industry Online Support: Current approvals (https://support.industry.siemens.com/cs/ww/en/ps/15728/cert)
Page 174
File E85972 USA (FCC) This device complies with part 15 of the FCC rules. Importer UK: Siemens plc, Sir William Siemens House, Princess Road, Manchester M20 2UR EAC (Eurasian Conformity) Eurasian Economic Union of Russia, Belarus, Armenia, Kazakhstan and Kyrgyzstan...
The "sysUpTime" parameter is metainformation about the message. It specifies the time (in hundredths of a second) since the last reinitialization of the network management part of the system. MESSAGE Message as ASCII string (English) SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Number of seconds second} {Max Maximum number of sessions sessions} {Url} URL of the Web server that was accessed. /Engineering/Reset2Factor y?r=0.685644556250803 {Config Character string (with spaces) for the configuration. Power detail} SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
IEC 62443-3-3 Reference: n/a (NERC-CIP 007-R5) User account management Message text Authentication was enabled. Example Authentication was enabled. Explanation Authentication was enabled. Severity Notice Facility local0 Standard IEC 62443-3-3 Reference: SR 1.3 SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 180
{Protocol}: User {User}: Access to url {url} denied. Example WBM: User admin: Access to url /Engineering/Reset2Factory?r=0.6856445562508033 denied. Explanation Access to Web resource was denied. Severity Error Facility local0 Standard IEC 62443-3-3 Reference: SR 2.1 SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 181
{Protocol}: User {User name} has changed {Config detail} configuration. Example OPC: User admin has changed Power configuration. Explanation User has changed specific configuration. Severity Info Facility local0 Standard IEC 62443-3-3 Reference: SR 2.12 SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Page 182
IEC 62443-3-3 Reference: SR 7.4 Message text {Protocol}: Firmware activation failed. Example WBM: Firmware activation failed. Explanation Firmware activation failed. Severity Error Facility local0 Standard IEC 62443-3-3 Reference: SR 7.4 SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...
Industry Online Support In addition to the product documentation, you are supported by the comprehensive online information platform of Siemens Industry Online Support at the following Internet address: Link: (https://support.industry.siemens.com/cs/de/en/) Apart from news, you will also find the following there: •...
Page 184
Service & Support SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI Operating Instructions, 03/2022, C79000-G8976-C512-04...