Rotary actuator SAL..T10 integrated Mounting and installation of butterfly valves and slipper valves corrected and expanded New chapter „Position feedback U“ Technical data corrected 5 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies About this documentation 22.12.2010...
1.4.2 Copyright This document may be duplicated and distributed only with the express permission of Siemens, and may be passed on only to authorized persons or companies with the required technical knowledge. 1.4.3 Quality assurance These documents were prepared with great care.
Siemens assumes no liability to the extent allowed under the law for any losses resulting from a failure to comply with the aforementioned points or for the improper compliance of the same.
Valve stem coupling Coupling Yoke Valve neck coupling For use in connection with Siemens 2-port or 3-port valves with 20 mm stroke, as SAX.. control or shutoff valves for HVAC plants. SAL.. For use in connection with Siemens butterfly or slipper valves, as control or shutoff valves for HVAC plants.
VXG41.50 VXG41.5001 Insert running number instead of k value .. = insert k value With tight bypass; VXG41.1301 and VXG41.1401: use only SAX61.., SKD32.50 or SKD82.50. 10 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Engineering 22.12.2010...
0,63 / 1 VVG41.13 1'600 VVG41.14 VVG41.15 VVG41.20 VVG41.25 1'550 VVG41.32 VVG41.40 -25…150 °C VVG41.50 insert running number instead of k value .. = insert k value 11 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Engineering 22.12.2010...
2’100 ASK33N 4’000 ASK33N VKF41.200 -10 °C…120 °C SAL..T10 rotary actuators only fit on VBF21.., DN65…150. For VBF21.., DN40/50 use SQK34.., SQK84.. or SQK33.00 rotary actuators. 12 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Engineering 22.12.2010...
SAL31.00T10 SQL33.03 SAL31.03T10 SQL83.. SQL83.00 12,5 SAL81.00T10 SQL83.04 SAL81.03T10 SAL.. positioning time differs from that of SQL32.12 and SQL32.13 rotary actuators. Consider positioning time when replacing. 14 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Engineering 22.12.2010...
1 pc. 11 mm 4 screws 2 pcs. M5 x 20 mm 2 pcs. M6 x 20 mm Single components from the spare part sets are not available. 16 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Engineering 22.12.2010...
• The operating voltage drop at AC/DC 24 V may be a maximum of 8% (4% above the G0 wire). Basic diagram − voltage drop across the power supply cables 17 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Engineering 22.12.2010...
The engineering data specified in chapter "Equipment combinations" (page 10) are only guaranteed in connection with the Siemens valves listed. Note When using the actuators in connection with valves of other manufacture, correct functioning must be ensured by the user, and Siemens will assume no responsibility. 18 / 60 Siemens Actuators SAX.., SAL..
Handling Mounting and installation 3.1.1 Mounting positions Indoor use Outdoor use Only in connection with weather shield ASK39.1 19 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Handling 22.12.2010...
1 pc. M5 x 20 incl. nut Note Actuators SAL.. are not compatible with mounting sets ASK31, ASK32, ASK33, ASK35, ASK40, and ASK41. 5 mm 5 mm 21 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Handling 22.12.2010...
1 adapter inc. fixing Mounting set (2 parts) 5 screws 1 adapter screw 4 pcs. M6 x 16 mm 1 pc. M5 x 20 mm incl. nut 22 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Handling 22.12.2010...
Page 23
With VBF21.. (e.g. DN 125), the following steps must be performed prior to fitting the mounting set. Opening counterclockwise 4 mm, 5 mm 4 mm, 5 mm 12 mm 12 mm 23 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Handling 22.12.2010...
Before fitting the accessory items shown below, the following steps must be mounting performed: Actuator is mechanically connected to a Siemens valve. Observe compatibility and choice of combinations. Refer to "Accessories" (page 13). Disconnect actuator from power. Attention if AC 230 V connected danger...
Page 25
1 pc. • First, observe "Special notes on mounting" (page 24). • Fit the screw covers first – otherwise danger of life! Plug-in space A No.: 1 25 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Handling 22.12.2010...
Page 26
Set function module (page 38) Nr.: 3 Plug-in space B Auxiliary switch Scope of delivery 1 auxiliary switch ASC10.51 1 screw 2 screw covers ASC10.51 1 pc. 26 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Handling 22.12.2010...
Page 27
Adjust switch position (refer also to "Manual operation" page 46) No.:1 When initial situation: 0 Ω When initial situation: ∞ Ω Observe "Wiring" (page 30) Observe "Connection terminals" (page 53) 27 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Handling 22.12.2010...
Page 28
Adjust switch position (refer also to "Manual operation" page 46) No.: 1 When initial situation: 0 Ω When initial situation: ∞ Ω Observe "Wiring" (page 30) Observe "Connection terminals" (page 53) 28 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Handling 22.12.2010...
Page 29
• If fitted several times, 2 UV-proof cable ties (800 x 4 mm) must be used. • The manual adjuster can not be used when the weather shield is mounted. 29 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en...
Metric Inch thread ½“ Prior to installation, the following preconditions must be satisfied: • Actuator is mechanically connected to a Siemens valve. • Housing cover is removed (step 6 "Special notes on mounting", page 24). Actuator No.: 4 Observe "Connection terminals" (page53)
Before making the function check, the following preconditions must be satisfied: Mechanically • "Environmental conditions" specified in chapter "Technical data" (page 50) • Actuator is mechanically connected to a Siemens valve • Actuator is in "Manual operation" mode (page 46).
Page 32
• If function module AZX61.1 is used, observe information given in chapter Notes "Changeover of acting direction" (page 39). • Observe information given in chapter "Acting direction and flow characteristic" on page 41. 32 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Handling 22.12.2010...
Page 33
(65%) position (65%) 12 sec Actuator’s stem Actuator’s spindle Check position value with maintains the maintains the ~ 485 Ω ~ 511 Ω ohmmeter position position 33 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Handling 22.12.2010...
Legislation may demand special handling of certain components, or it may be sensible from an ecological point of view. Observe all local and currently valid legislation. 34 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Handling...
Observe information given in chapter "Acting direction and flow characteristic" on page 41. Internal control ensures very constant positioning times and determination of the actuator’s position. 35 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Functions and control...
Page 36
Calculated position Actual position No power applied time [ms] (power applied) Accurate position feedback is made possible with the help of a potentiometer (page 48). 36 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Functions and control 22.12.2010...
• If function module AZX61.1 is used, observe the information given in chapter Notes "Changeover of acting direction" (page 39). • Observe the information given in chapter "Acting direction and flow characteristic" on page 41. 37 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Functions and control 22.12.2010...
• Can only be used with voltage input. Notes • Maximum input voltage is DC 30 V. If the configuration is invalid, the actuator operates on DC 0…10 V. 38 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Functions and control...
(0 %) when positioning signal Y = 0 V resp. Z = 0 Ω. This applies to all Siemens valves according to "Equipment combinations" (page 10). • With valves whose stem is retracted in the fully closed position, "direct acting"...
Factory setting: All DIL switches set to OFF Ω Flow characteristic Actuator Valve Totally Y, Z Positioning signal Stroke Volumetric flow Acting direction: Direct Acting direction: Reverse 40 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Functions and control 22.12.2010...
The position feedback U (DC 0...10 V) is always proportional to stroke H of the actuator’s stem. Actuator Actuator Positioning signal Y, Z Position feedback U log = equal- percentage lin = linear 41 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Functions and control 22.12.2010...
• If the actuator does not detect the second end position within an appropriate stroke range (max. 25 mm), the first end stop will be adopted and the actuator operates with a working range of 20 mm. 42 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Functions and control 22.12.2010...
From now on, the actuator follows the changed valve stroke position. This means: New position 0%, Y = 2 V, actuator travels 20% of the stored valve stroke in the direction "Actuator’s stem extended". 43 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Functions and control 22.12.2010...
”Y” has no impact Note The operating modes "Z" shown are based on factory setting "direct acting" and a "push to open" valve. 44 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Functions and control 22.12.2010...
With the stroke actuators, the translation from rotary to stroke movement takes place in the output stage. SAL.. Actuator’s stem retracted / Actuator’s stem extended / SAX.. valve fully closed valve fully open 45 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Functions and control 22.12.2010...
The stem coupling (1) and neck coupling (2) Mounting sets are available for use with butterfly ensures full backward compatibility with all types and slipper valves. of Siemens large-stroke valves produced since 1975. 4.12.3 Manual adjuster Automatic When the motor drives the manual adjuster turns.
(page 44) Calibration error Start calibration again (page 31) Blinking Clogged valve Check valve Dark Dark No power or electronics faulty Check operating voltage 47 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Functions and control 22.12.2010...
R = 0 + 1.57 Ohm x rotary angle (°) R = 0 + 7.84 Ohm x rotary angle (°) SAL.. Actuator position in relation to nominal stroke/nominal angular rotat n [%] 48 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Functions and control...
Mounting sets ounting sets ASK31N and ASK33N enable the actuators to be fitted to slipper valves VBF21.., DN65…150 and butterfly valves VKF41.. (page 21). ASK3..N 49 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Functions and control...
-25…70 °C Humidity <95 % r.h. Storage IEC 60721-3-1 Temperature -15…55 °C Humidity 5…95 % r.h. Max. media temperatur when mounted on valve 150 °C 120° 50 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Technical data 22.12.2010...
Page 51
AC 24 V, 30 W Observe acting direction of DIL switches AWG = American wire gauge Also with weather shield ASK39.1 Transformer 160 VA (e.g. Siemens 4AM 3842-4TN00-0EA0) for actuators operating on AC 24 V 51 / 60 Siemens Actuators SAX.., SAL.. for valves...
1 x ASZ7.5/.. Accessories SA..61.. and / or 1x ASC10.51 1x ASC10.51 Accessories SA..81.. and / or 1x ASC10.51 1x ASC10.51 or 1 x ASZ7.5/.. 52 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Connection diagrams and dimensions 22.12.2010...
= 135 Ω, 200 Ω;1000 Ω Stem heating element AC 24 V / 30 W ASZ6.6 System neutral (SN) (red) System potential (SP) (black) 53 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Connection diagrams and dimensions 22.12.2010...
System potential AC/DC 24 V Position feedback Position signal Positioning signal forced control SA..81.. Actuator Controller System neutral System potential AC/DC 24 V Y1, Y2 Positioning signals 54 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Connection diagrams and dimensions 22.12.2010...
Dimensions in mm SAX..: SAX..U: ½" (Ø 21.5 mm) SAX..: SAX..U: ½" (Ø 21.5 mm) Type ► ►► SAX..00 and SAX..03 With ASK39.1 55 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Connection diagrams and dimensions 22.12.2010...
(V = diverting mode). Maximum permissible differential pressure at which the motorized valve will close Δp securely against the pressure (close off pressure). 57 / 60 Siemens Actuators SAX.., SAL.. for valves CE1P4040en Building Technologies Glossary...