Integral action time Tn
You can set the primary controller's integral action time Tn for each room
group depending on demand (0..600 s).
Main menu > Room groups > Room group X
> Primary controller > Int action time Tn:
Factory setting
Ventilation
Indoor air quality control
The indoor air quality controller calculates a positioning signal based on the
current setpoint (in accordance with the ventilation level) and the current in-
door air quality.
From this, the linear step selector derives the ventilation stage presently re-
quired.
The ppm level of indoor air quality is displayed on the central apartment unit.
Indoor air quality at 0 V/10 V
Connect an indoor air quality sensor (DC 0..10 V) to provide indoor air quality
control sensor.
The indoor air quality sensor must be located in the room itself, thus
ensuring that air also circulates around the sensor when the ventila-
tion system is off. Do not install the sensor in the extract air duct.
The ppm level for 0 V and 10 V (0..2000 ppm) can be set.
Main menu > Ventilation > IAQ controller > IAQ at 0 V:
Factory setting
Main menu > Ventilation > IAQ controller > IAQ at 10 V:
Factory setting
P-band Xp indoor air quality
A P-controller is used to ensures that the indoor air quality is maintained at the
required setpoint. The controller's P-band (0..2000 ppm) can be set here.
Within this range, all available stages are switched on and off.
Main menu > Ventilation > IAQ controller > P-band Xp:
Factory setting
Siemens
Building Technologies
60 s
0 ppm
2000 ppm
400 ppm
Synco™ living
Function settings
107 / 134
CE1C2740en