Protection and Automation Functions
5.25 67 Directional Overcurrent/Earth Fault
Functions > Protection > 67 > Gn 67G
Parameter
Char Angle
Minimum Voltage
Functions > Protection > 67 > Gn 67GS
Parameter
Char Angle
Minimum Voltage
Compensated Network
Wattmetric
Wattmetric Power
Ires Select
Functions > Protection > 67 > Gn 67N
Parameter
Polarizing Quantity
Char Angle
Minimum Voltage
Information List
5.25.6
Input/Output Matrix
The complete serial protocol information list containing the DNP3, IEC 60870-5-103, and Modbus RTU data
information for the configured device can be generated using the Export Report feature in the Reydisp
Manager 2 tool, Serial Comms & Events.
336
Range
-95° to +95°, Δ 1°
0.33 V to 67 V, Δ 0.5 V
Range
-95° to +95°, Δ 1°
0.33 V to 67 V, Δ 0.5 V
Enabled
Disabled
Enabled
Disabled
0.05 to 20 ⋅ I
⋅ W, Δ 0.05
rated
⋅ I
⋅ W
rated
Ires
Ires Real
Range
NPS
ZPS
-95° to +95°, Δ 1°
0.33 V to 3 V, Δ 0.5 V
General Pickup
User Logic
67 FWD PhA
67 REV PhA
67 FWD PhB
67 REV PhB
67 FWD PhC
67 REV PhC
67G FWD
67G REV
Inhibit Wattmetric
67GS FWD
67GS REV
Wattmetric Po> Operated
67N FWD
67N REV
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
Settings
Default Gn1
Gn2
-15°
0.33 V
Settings
Default Gn1
Gn2
-15°
0.33 V
Disabled
Disabled
0.1 ⋅
I
⋅ W
rated
Ires
Settings
Default Gn1
Gn2
ZPS
-15°
0.33 V
C53000-G7040-C014-1, Edition 11.2019
Gn3
Gn4
Gn3
Gn4
Gn3
Gn4
Type
Output
Output
Output
Output
Output
Output
Output
Output
Input
Output
Output
Output
Output
Output