Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Overview Description In conjunction with a 24 V power supply, the selectivity module is used to distribute the load current across several branches and to monitor the individual currents in these branches. Faults in the individual branches caused by overload or short-circuit are detected and selectively switched off, so that the fault does not impact the other load circuits.
Page 4
Overview ● Fast fault diagnostics using: – Multi-colored LEDs for each output for faster troubleshooting on-site – You can toggle between group message and single-channel diagnostics ● Floating group signal contact for remote diagnostics ● Single-channel signal using the diagnostics interface to serially signal the state of the individual outputs ●...
Page 5
Overview Ordering data The following device options are available: Selectivity modules Type Order number SITOP SEL1200 8 × 5 A 6EP4437-7FB00-3DX0 24 V DC input Number of outputs: 8 Setting range of the response threshold: 1 - 5 A with group signaling contact SITOP SEL1200 4 ×...
Page 6
Overview Validity This manual provides information on the following products: ● Selectivity module SITOP SEL1200 8 × 5 A Article number: 6EP4437-7FB00-3DX0 Product state: 1 ● Selectivity module SITOP SEL1200 4 × 10 A Article number: 6EP4437-7FB00-3CX0 Product state: 1 ●...
Safety instructions General safety instructions WARNING Correct handling of the devices When operating electrical devices, it is inevitable that certain components will carry dangerous voltages. Therefore, failure to handle the units properly can result in death or serious physical injury as well as extensive property damage.
Safety instructions 1.2 Safety instructions for hazardous zones Safety instructions for hazardous zones The devices comply with ATEX directive 2014/34/EU; EN 60079-0; EN 60079-7. WARNING OPERATE POTENTIOMETERS OR SWITCHES IN NON-HAZARDOUS AREAS ONLY! SITOP SEL1200-1400 Equipment Manual, 06.2020, A5E46496083-2-76...
Description, device design, dimension drawing Device description Using the selectivity module, a 24 V DC output voltage from a regulated power supply can be distributed across four or eight load circuits. The response threshold of the output current can be individually set for each output using a potentiometer. When the set response threshold is exceeded, the output is automatically switched off according to a defined switch off characteristic, and can be switched on again after a wait time using a pushbutton (ON/OFF/RST) or remote reset (RST).
Page 12
Description, device design, dimension drawing 2.1 Device description ① +24 V DC input ② 0 V connection for the internal supply ③ +24 V DC outputs ④ Group signaling contact (13, 14); not assigned (NF); remote reset (RST) ⑤ Potentiometer for each output ⑥...
Description, device design, dimension drawing 2.2 Connections and terminal designation Connections and terminal designation ① The input terminals can be used to establish the connection to the supply voltage. The ② ③ "0 V" connection is used to supply the internal electronics. The output terminals used to connect to the loads to be supplied (see also Chapter Installation (Page 47)).
Page 14
Description, device design, dimension drawing 2.2 Connections and terminal designation NOTICE Overload of the wiring The "0 V" connection is only used to supply the internal electronics of the selectivity module. The 0 V of the connected loads must be routed directly to the power supply using separate cables! SITOP SEL1200-1400 Equipment Manual, 06.2020, A5E46496083-2-76...
Description, device design, dimension drawing 2.3 Potentiometer Potentiometer ⑤ The potentiometer on the front of the device is used to set the response threshold of the output current. When delivered, the maximum possible response threshold is set. Figure 2-3 Potentiometer Note It is only permissible to use an insulated screwdriver when actuating the potentiometer.
Description, device design, dimension drawing 2.4 Status displays and signaling Status displays and signaling 6EP4437-7FB00-3DX0 6EP4437-7FB00-3CX0 6EP4438-7FB00-3DX0 6EP4437-7EB00-3DX0 6EP4437-7EB00-3CX0 6EP4438-7EB00-3DX0 ④ floating relay contact (NO contact), Group signal contact (13, 14) contact rating: 24 V AC/0.1 A; 30 V DC/0.1 A NOTICE: It is not permissible that the signaling contact is connected to the line voltage! ④...
Page 17
Description, device design, dimension drawing 2.4 Status displays and signaling ⑥ ④ Indicator light (LED 1 - 4 (1 - 8)) , signaling contact (13, 14) and selector switch for ⑦ diagnostics interface (COM) Signaling 6EP4437-7FB00-3DX0 6EP4437-7FB00-3CX0 6EP4438-7FB00-3DX0 6EP4437-7EB00-3DX0 6EP4437-7EB00-3CX0 6EP4438-7EB00-3DX0 All LEDs: No supply voltage...
Page 18
LED state "green", "green flashing" or "orange flashing". Additional information about the data transfer (COM = 1) is provided in the documents: ● Diagnostics interface (https://support.industry.siemens.com/cs/ww/en/view/109767425) ● Faceplates and communication blocks (https://support.industry.siemens.com/cs/ww/en/view/109763709) SITOP SEL1200-1400 Equipment Manual, 06.2020, A5E46496083-2-76...
Description, device design, dimension drawing 2.5 Buttons and selector switches Buttons and selector switches Figure 2-5 Buttons and selector switches ⑥ Buttons (ON/OFF/RST) for the selectivity module SITOP SEL1200-1400 fulfill the following two functions: 1. manually switching an output off and on (see the following). 2.
Page 20
Description, device design, dimension drawing 2.5 Buttons and selector switches Manually switching an output on and off An individual output can be switched on and switched off using the button ⑥ (ON/OFF/RST) . When the device is delivered, the outputs are manually switched off. Switching off an output: ⑥...
Description, device design, dimension drawing 2.6 Electronic overload shutdown and reset Electronic overload shutdown and reset An overload is permitted for a defined period of time for each selectivity module output. The output is electronically shut down according to the "Shutdown characteristic" diagram after the limit value has been exceeded.
Page 22
Description, device design, dimension drawing 2.6 Electronic overload shutdown and reset ⑥ Reset of an electronic overload shutdown via button (ON/OFF/RST) and remote reset ④ (RST) An output that has been shut down due to overload can be reset by pressing the associated ⑥...
Page 23
Description, device design, dimension drawing 2.6 Electronic overload shutdown and reset ④ Remote reset (RST) ④ Alternatively, the reset can be performed using a remote reset signal (RST) . The non- isolated 24 V input (referred to the "0 V" terminal of the module) can be used at terminal "RST".
Description, device design, dimension drawing 2.7 Setting the switch-on delay time Setting the switch-on delay time For specific loads, it can make sense to sequentially switch-on the outputs in order to reduce the peak inrush currents, and therefore the load on the power supply. To achieve this, the individual outputs of the selectivity module can be switched-in with a time delay between one another in a fixed sequence (output 1 ⇒...
Mounting/removal WARNING Installing the device in a housing or a control cabinet The SITOP SEL1200-1400 selectivity modules are built-in units. They must be installed in a housing or control cabinet where only qualified personnel have access. The device can be mounted in a control cabinet on standard mounting rails (see Chapter Mechanical system (Page 55)) Mounting To mount the device, position it with the mounting rail guide at the upper edge of the...
Mounting position, mounting clearances Standard mounting position The device is mounted on standard mounting rails TH 35-15/7,5 (EN 60715). The device must be mounted vertically in such a way that the input terminals are at the bottom. A clearance of at least 45 mm should be maintained above and below the device (maximum depth of the cable duct, 50 mm).
Page 32
Mounting position, mounting clearances 4.1 Standard mounting position Figure 4-2 6EP4437-7FB00-3CX0 standard mounting position Figure 4-3 6EP4438-7FB00-3DX0 standard mounting position Figure 4-4 6EP4437-7EB00-3DX0 standard mounting position SITOP SEL1200-1400 Equipment Manual, 06.2020, A5E46496083-2-76...
Page 33
Mounting position, mounting clearances 4.1 Standard mounting position Figure 4-5 6EP4437-7EB00-3CX0 standard mounting position Figure 4-6 6EP4438-7EB00-3DX0 standard mounting position Figure 4-7 Mounting height derating SITOP SEL1200-1400 Equipment Manual, 06.2020, A5E46496083-2-76...
Mounting position, mounting clearances 4.2 Other mounting positions Other mounting positions For mounting positions that deviate from the standard mounting position, derating factors (reduction of the output power or the permissible ambient temperature) must be observed in accordance with the following diagrams. Note In the case of mounting positions that deviate from the standard mounting position, reduced mechanical resistance of the devices against vibration and shock must be expected.
Page 35
Mounting position, mounting clearances 4.2 Other mounting positions Figure 4-10 Mounting position 3 Figure 4-11 Mounting position 4 Figure 4-12 Mounting position 5 SITOP SEL1200-1400 Equipment Manual, 06.2020, A5E46496083-2-76...
Mounting position, mounting clearances 4.2 Other mounting positions 4.2.3 SEL1200 8 x 10 A 6EP4438-7FB00-3DX0 NOTICE In total, the maximum device load must not exceed 60 A. The derating of 2 %/K must also be complied with here. At 70 °C, this corresponds to a total maximum device load of 48 A. Figure 4-18 Mounting position 1 Figure 4-19...
Page 39
Mounting position, mounting clearances 4.2 Other mounting positions Figure 4-21 Mounting position 4 Figure 4-22 Mounting position 5 SITOP SEL1200-1400 Equipment Manual, 06.2020, A5E46496083-2-76...
Mounting position, mounting clearances 4.2 Other mounting positions 4.2.6 SEL1400 8 x 10 A 6EP4438-7EB00-3DX0 NOTICE In total, the maximum device load must not exceed 60 A. The derating of 2 %/K must also be complied with here. At 70 °C, this corresponds to a total maximum device load of 48 A. Figure 4-33 Mounting position 1 Figure 4-34...
Page 45
Mounting position, mounting clearances 4.2 Other mounting positions Figure 4-36 Mounting position 4 Figure 4-37 Mounting position 5 SITOP SEL1200-1400 Equipment Manual, 06.2020, A5E46496083-2-76...
Installation WARNING Hazard due to electric shock Before installation or maintenance work can begin, the system's main switch must be switched off and measures taken to prevent it being switched on again. If this instruction is not observed, touching live parts can result in death or serious injury. Connection at the input WARNING The device is only suitable for operation with 24 V DC voltages (safety extra low voltage).
Page 48
Installation 5.1 Connection at the input NOTICE Overload of the wiring The "0 V" connection is only used to supply the internal electronics of the selectivity module. The 0 V of the connected loads must be routed directly to the power supply using separate cables! The input terminals of the selectivity module are designed for a maximum input current of 40 A or 60 A.
Installation 5.2 Connection at the output Connection at the output (see Chapter Technical data (Page 51)) Figure 5-2 Output connection ③ The loads to be supplied are connected at output terminals labeled OUTPUT 1, 2, 3, 4 (1, …, 8). (terminal cross-sections, see Figure Terminal data (Page 13)). Note The 0 V of the loads must be routed directly to the power supply using separate cables! SITOP SEL1200-1400...
Page 50
Installation 5.2 Connection at the output SITOP SEL1200-1400 Equipment Manual, 06.2020, A5E46496083-2-76...
Technical data Note Technical data apply for a rated input voltage, rated load and 25 °C ambient temperature if nothing else is specified. Input 6EP4437-7FB00-3DX0 6EP4438-7FB00-3DX0 6EP4437-7FB00-3CX0 6EP4438-7EB00-3DX0 6EP4437-7EB00-3DX0 6EP4437-7EB00-3CX0 Input Regulated DC voltage Rated voltage U 24 V in rated Voltage range 20.4 - 30 V Overvoltage strength...
Technical data 6.2 Output Output 6EP4437-7FB00- 6EP4437-7EB00- 6EP4437-7FB00- 6EP4438-7FB00- 3DX0 3DX0 3CX0 3DX0 6EP4437-7EB00- 6EP4438-7EB00- 3CX0 3DX0 Output Regulated DC voltage Output voltage - approx. 0.2 V Total tolerance Corresponding to the supplying input voltage Number of outputs Output current up to 60 °C for 10 A 10 A (in total, not each output (rated value)
Page 53
Technical data 6.2 Output The following applies for the SEL1400: In the range > 150 % of the selected current response threshold, the current is limited to 150 %, typically after 10 ms to 100 ms, the output is electronically shut down (LED of the output is lit red). ●...
Technical data 6.3 Efficiency Efficiency 6EP4437-7FB00- 6EP4437-7EB00- 6EP4437-7FB00- 6EP4437-7EB00- 6EP4438-7FB00- 3DX0 3DX0 3CX0 3CX0 3DX0 6EP4438-7EB00- 3DX0 Efficiency at 98 % 98 % 99 % 99 % 99 % out rated out rated approx. Power loss at 12 W 15 W 12 W 15 W 15 W...
Technical data 6.8 Dimension drawing Dimension drawing See Chapter Dimensions and weight (Page 26). CAD data that can be downloaded from the Internet: 6EP4437-7FB00-3DX0 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_01648) 6EP4437-7FB00-3CX0 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_01645) 6EP4438-7FB00-3DX0 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_01575) 6EP4437-7EB00-3DX0 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_01654) 6EP4437-7EB00-3CX0 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_01651) 6EP4438-7EB00-3DX0 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_01578) SITOP SEL1200-1400 Equipment Manual, 06.2020, A5E46496083-2-76...
Safety, approvals, EMC Safety 6EP4437-7FB00-3DX0 6EP4437-7FB00-3CX0 6EP4438-7FB00-3DX0 6EP4437-7EB00-3DX0 6EP4437-7EB00-3CX0 6EP4438-7EB00-3DX0 Standard for safety acc. to IEC61204-7 and EN 50178 Protection class Class III Degree of protection IP20 (EN 60529) Approvals 6EP4437-7FB00-3DX0 6EP4437-7FB00-3CX0 6EP4438-7FB00-3DX0 6EP4437-7EB00-3DX0 6EP4437-7EB00-3CX0 6EP4438-7EB00-3DX0 CE marking Yes, (2014/35/EU, 2014/30/EU, 2011/65/EU, 2014/34/EU) CB approval UL/cUL (CSA) approval UR (UL 2367) file E328600;...
Ambient conditions 6EP4437-7FB00-3DX0 6EP4437-7FB00-3CX0 6EP4438-7FB00-3DX0 6EP4437-7EB00-3DX0 6EP4437-7EB00-3CX0 6EP4438-7EB00-3DX0 Ambient temperature -25 ... 70 °C for natural convection (self convection) Tested according to: EN 60068-2-1 Cold, Ad test • EN 60068-2-2 Dry heat, Bb test • EN 60068-2-78 Humid heat, constant Cab test •...
Page 60
Ambient conditions 6EP4437-7FB00-3DX0 6EP4437-7FB00-3CX0 6EP4438-7FB00-3DX0 6EP4437-7EB00-3DX0 6EP4437-7EB00-3CX0 6EP4438-7EB00-3DX0 Damaging gases Sulfur dioxide: 10 cm , 4 days Hydrogen sulfide: 1 cm , 4 days Tested according to: EN 60068-2-42 sulfur dioxide • EN 60068-2-43 hydrogen sulfide • Atmospheric pressure Operation: 1080 - 795 hPa (0 - 2000 m) •...
Environment The devices are in conformance with RoHS. Only substances in conformance with PWIS are used (paint-wetting impairment substances) Disposal guidelines Packaging and packaging aids can and should always be recycled. The product itself may not be disposed of as domestic refuse. SITOP SEL1200-1400 Equipment Manual, 06.2020, A5E46496083-2-76...
You can access technical support through the following communication channels: ● Telephone: + 49 (0) 911 895 7222 ● Internet: Web form for support request (http://www.siemens.de/automation/support-request) Technical documentation on the Internet Operating instructions and manuals for SITOP are available in the Internet: Operating instructions/manuals (http://www.siemens.com/sitop/manuals)
Page 64
Service & Support Contact persons If you have any questions regarding the use of our products, then contact the Siemens contact person in your regional Siemens sales office. You can find these addresses as follows: ● On the Internet (http://www.automation.siemens.com/partner) ●...