Motor control
Settings
You will find detailed information about the settings in:
Chapter 4.2.2 "General settings and
Soft starter with
reversing
contactor
ON <
OFF
ON >
FB ON
Non-maintained
command mode
Separate failsafe
function from
control function
Saving change-over
command
Load type
Feedback time
Execution time
Interlocking time
Table 4-20: Soft starter with reversing contactor settings
4-64
definitions".
ON < control command, counter-clockwise
(connection with arbitrary socket
usually with "Enabled control command - ON <" socket)
OFF control command
(connection with arbitrary socket
usually with "Enabled control command - OFF" socket)
ON > control command, clockwise
(connection with arbitrary socket
usually with "Enabled control command - ON >" socket)
Auxiliary control input "Feedback ON"
(connection with arbitrary socket
usually with "Status - Motor current flowing" socket)
• Deactivated
• Activated
• Deactivated:
Safety-oriented tripping via the DM-F module also affects the
SIMOCODE pro control function, so that additional fault
messages are avoided.
This setting is selected for applications where safety-oriented
tripping directly affects the motor controlled by SIMOCODE pro.
• Activated:
Safety-oriented tripping via the DM-F module does not affect the
SIMOCODE pro control function.
This setting is selected for applications where safety-oriented
tripping does not affect the motor controlled by SIMOCODE pro.
• Deactivated
• Activated
You can choose between:
• Motor
• Resistive load (see
Chapter 4.2.2 "General settings and
definitions")
Range 0 - 25.5 seconds (0.5 s)
Execution time > Smooth running down time
Range 0 - 6553.5 seconds (1.0 s)
Range 0 - 255 seconds (0 s)
Description
,
,
,
,
GWA 4NEB 631 6050-22 DS 03
SIMOCODE pro