3 Installation
3.5.5 AC Output Connection
It's forbidden that several inverters shares an AC switch.
It's forbidden to connect with load between inverter and AC switch.
To ensure the inverter can be disconnected with load safely, we suggest equipping independent
dipolar switch for each inverter to protect the inverter.
Table3-3 Recommended AC breaker specification
Model
iStoragE 3600
iStoragE 5000
iStoragE 6000
During wiring, please pay attention to distinguish the AC live wire, neutral wire and grounding wire.
Step 1
Strip the insulation layer of AC live wire (L), neutral wire (N) and grounding wire (PE) for about
7mm, as shown in Figure3-43.
Figure3-43 Stripping diagram of AC output (unit: mm)
It is recommended to use brown or red wire as the live wire, use blue or white wire as neutral wire and
use yellow-green wire as PE wire to avoid wrong connection. If using the wires of other color, please
confirm the corresponding connection relationship.
44
AC input specification (GRID)
32A
50A
63A
All rights reserved ©Xiamen Kehua Digital Energy Tech
iStoragE Series Energy Storage System
AC output specification (BACKUP)
20A
25A
32A
User Manual