Product overview
3.1 Properties
Note
You need to configure and assign parameters to the server module in the configuration
software.
To do this, place the server module in the last configuration slot and enable the parameter
Group diagnostics: missing supply voltage L+. When there are 32 I/O modules, the server
module is inserted in slot 33.
You can find more information in the Server module
(http://support.automation.siemens.com/WW/view/en/63257531) manual.
First BaseUnit of an ET 200SP in the configuration
Note
First BaseUnit of an ET 200SP in the configuration
When an AC I/O module or AI Energy Meter ST is plugged, the first BaseUnit in an ET 200SP
station may be a dark one. Please note the information on limiting the overvoltage and
power rating in the AC I/O module manuals.
In order to route the 24 V DC supply voltage via a fuse, a light BaseUnit must be plugged into
the slot of the first 24 V DC I/O module.
Pay attention to the type of the BaseUnits during the configuration.
16
IM 155-6 PN ST Interface Module (6ES7155-6AU02-0BN0)
Equipment Manual, 11/2023, A5E53132379-AA