WW & WT Models Key to Symbols | 3 KEY TO SYMBOLS NOTICE: All refrigerant discharged from this Warnings unit must be recovered WITHOUT Warnings in this document are identified by EXCEPTION. Technicians must follow a warning triangle printed against a grey industry accepted guidelines and all local, background.
INSTALLATION Heat Pump operating under extreme conditions will The Water to Water WT series unit should be mounted have limitation on fluid flow rates and/or level on a vibration absorbing pad slightly larger than the temperatures.
WW & WT Models Electrical | 7 ELECTRICAL NOTICE: Never use flexible hoses of a Refer to electrical component box layout. (Figure #) smaller inside diameter than that of the WARNING: Field wiring must comply with fluid connections on the unit. local and national electric codes.
8 | Electrical WW & WT Models UPM control (Remote T-ATAT models Safety Devices and the UPM II Controller only) Safety Devices and the UPM I Controller Figure # 4 [1] Power 24VAC-R [2] Alarm output Dry contact N.O. . [3] Freeze sensors Figure # 3 1] Board Power Indicator...
Page 9
WW & WT Models Electrical | 9 Safety controls include the following: • High pressure switch located in the refrigerant UPM DIP SWITCH DEFAULT POSITION discharge line and wired across the HPC terminals on the UPM. lockout • Low pressure switch located in the unit refrigerant reset suction line and wired across terminals LPC1 and LPC2 on the UPM.
Number of factory installed options are available on limit trip is 26°F (sensor number 1); however this select WW and WT Series of Heat Pumps. The following can be changed to 15°F by cutting the R24 resistor details the purpose, function and components of each located on top of the DIP switch SW1.
HEAT RECOVERY PACKAGE The DPS water flow proving switch is a factory installed Water Tank Preparation option available for the WW/WT series. The DPS Turn off electrical or fuel supply to the water heater. prevents compressor operation if there is inadequate...
12 | Sequence of operation WW & WT Models NOTE: Diagram for illustration purposes only. Ensure access to Heat Pump is not restricted. Figure # 7 Before restoring the power or fuel supply to the Allow the unit to operate for 20 to 30 minutes to water heater, adjust the temperature setting on the ensure it is functioning properly.
WW & WT Models Sequence of Operation flow | 13 SEQUENCE OF OPERATION FLOW START RESET ON R RESET ON Y1 = ON R = 24VAC POWER/ SWITCHES/SENSOR CLEAR FAULTS STATUS CHECK BLINK CODE ON STATUS LED COUNTER SOFT LOCKOUT V >...
14 | Application Considerations WW & WT Models APPLICATION CONSIDERATIONS exchanger. This can be accomplished with either control valve or a bladder type expansion tank. When using a Well Water Systems single water well to supply both domestic water and the Copper is adequate for ground water that is not high in heat pump care must be taken to ensure that the well mineral content.
WW & WT Models Application Considerations | 15 Ball valves should be installed in the supply and return t is imperative that all air be eliminated from the closed lines for unit isolation and unit water flow balancing. loop side of the heat exchanger to ensure against Pressure/temperature ports are recommended in both fouling.
16 | Application Considerations WW & WT Models Figure # 11 [1] Polybutylene or Polyethelene with insulation Verify that vibration isolation has been provided. [2] Ground loop pumping package (GLP) Unit is serviceable. Be certain that all access panels are secured in place. [3] Ground loop connection kit.
The controller will memorize the last mode used before power is removed and will run in that mode after is Bosch water heat pump controller offers a low cost, turned on. In all modes the control will display simple solution to the control of a water to water heat temperature degree differential setting for five seconds pump unit.
18 | Auto Changeover mode WW & WT Models when the unit runs after power is applied or the mode is While in a soft lockout condition the display will show changed from heating to cooling, if fluid temperature is the specific fault (for example LP1) and the “service”...
WW & WT Models Pump cycling | 19 DOWN Button: If control has called for the second stage three times in a row, and compressor setting is “Du”; regardless of the • Press once to display the current set point lead-lag setting control will switch the call to the other temperature.
20 | User Adjustable Settings Chart WW & WT Models USER ADJUSTABLE SETTINGS CHART temperature isn’t changing, then the control will activate the second stage after a three minute delay from the first stage activation. This logic will apply when the Settings Range Default...
WW & WT Models Initial Configuration | 21 INITIAL CONFIGURATION Fifth display field After power up and the steps above are completed Test mode setting, (DE) delay or (ND) no delay: This is utilized for testing the outputs of the controller by the configuration default settings may be changed.
22 | Troubleshooting WW & WT Models TROUBLESHOOTING Troubleshooting Information Solution column may reflect a possible fault that may be one of, or a combination of causes and solutions. Check each cause and adopt “process of elimination” and or verification of each before making any conclusion.
Page 23
WW & WT Models Troubleshooting | 23 Unit Troubleshooting Problem Possible Cause Checks and Correction Unit undersized Recalculate heating and or cooling loads. If excessive, possibly adding insulation and shading will rectify the problem Fluid Flow Lack of adequate fluid flow. Refrigerant Low on refrigerant charge causing inefficient operation charge...
Page 24
24 | Troubleshooting WW & WT Models Comfort Alert Module -Flash Codes Status LED Status LED Description Status LED Troubleshooting Information Solution YELLOW "ALERT” Open Circuit Outdoor unit power disconnect is open FLASH CODE 5 Compressor circuit breaker or fuse(s) is open Compressor contactor has failed open •...
WW & WT Models Troubleshooting | 25 HRP Troubleshooting Problem Possible Cause Checks and Corrections NO FLOW No Power Check power supply LOW FLOW On/Off Switch Position Set switch to “ON” position Compressor Contactor Engage heat pump contactor Broken or loose wires Repair or tighten wires Air Lock Purge air from piping system...
26 | Electrical Data Table ww WW & WT Models ELECTRICAL DATA TABLE WW Compressor Service Compressor Total Unit Models Voltage Rated Voltage Cold Winding Resistance Capacitor Code Voltage Min/ (Ω) (μF/V) Single Single Three Circuit Fuse/ Phase: Phase: Phase: Amps HACR Line-Line...
WW & WT Models Electrical Data WT | 27 ELECTRICAL DATA WT Compressor Service Compressor Total Unit Cold Winding Resistance (Ω) Models Voltage Rated Voltage Capacitor Code Voltage Min/Max (F/V) Single Single Three Three Circuit Fuse/ Phase: Phase: Phase: Phase: Amps HACR T1-T2/T2-...
28 | Water Pressure Drop WW WW & WT Models WATER PRESSURE DROP WW Chilled Fluid Side (55°F) Cond. Fluid Side (85°F) Model Pressure Drop (PSIG) Pressure Drop (ft of Pressure Drop Pressure Drop (ft H2O) (PSIG) of H2O) 18.0 2.36 2.05 22.0...
WW & WT Models Water Pressure Drop WT | 29 WATER PRESSURE DROP WT Chilled Fluid Side (55°F) Cond. Fluid Side (85°F) Model Pressure Drop Pressure Drop (ft Pressure Drop Pressure Drop (ft (PSIG) of H2O) (PSIG) of H2O) 0.56 1.30 0.51 1.18...
WW & WT Models Wiring Diagrams | 31 WIRING DIAGRAMS Figure # 13 FOR REFERENCE ONLY Actual unit wiring may vary from this example. Always refer to the wiring diagram attached to the unit. Revised 08-16 8733943362 (2016/08)
Page 32
32 | Wiring Diagrams WW & WT Models Figure # 14 FOR REFERENCE ONLY Actual unit wiring may vary from this example. Always refer to the wiring diagram attached to the unit. 8733943362 (2016/08) Subject to change without prior notice WW &...
Page 33
WW & WT Models Wiring Diagrams | 33 Figure # 15 FOR REFERENCE ONLY Actual unit wiring may vary from this example. Always refer to the wiring diagram attached to the unit. Revised 08-16 8733943362 (2016/08)
Page 34
34 | Wiring Diagrams WW & WT Models Figure # 16 FOR REFERENCE ONLY Actual unit wiring may vary from this example. Always refer to the wiring diagram attached to the unit. 8733943362 (2016/08) Subject to change without prior notice WW &...
Page 35
WW & WT Models Wiring Diagrams | 35 Figure # 17 FOR REFERENCE ONLY Actual unit wiring may vary from this example. Always refer to the wiring diagram attached to the unit. Revised 08-16 8733943362 (2016/08)
Page 36
36 | Wiring Diagrams WW & WT Models Figure # 18 FOR REFERENCE ONLY Actual unit wiring may vary from this example. Always refer to the wiring diagram attached to the unit. 8733943362 (2016/08) Subject to change without prior notice WW &...
Page 37
WW & WT Models Wiring Diagrams | 37 Figure # 19 FOR REFERENCE ONLY Actual unit wiring may vary from this example. Always refer to the wiring diagram attached to the unit. Revised 08-16 8733943362 (2016/08)
Page 38
38 | Wiring Diagrams WW & WT Models Figure # 20 FOR REFERENCE ONLY Actual unit wiring may vary from this example. Always refer to the wiring diagram attached to the unit. 8733943362 (2016/08) Subject to change without prior notice WW &...
WW & WT Models Unit Start-up | 41 UNIT START-UP Set the thermostat to the highest setting. By disposing of this product correctly you Set the thermostat system switch to “COOL”, . The will help ensure that the waste undergoes reversing valve solenoid should energize.
42 | Terminology WW & WT Models TERMINOLOGY functioning relies upon, fluorinated greenhouse gases, PSC - Permanent-split capacitor motor involving a part containing or designed to contain such gases. EER - Energy Efficiency Ratio Conditioned space Space within a building provided COP - Coefficient of Performance.