hit counter script
Siemens SIMATIC ET 200SP Equipment Manual
Hide thumbs Also See for SIMATIC ET 200SP:

Advertisement

Quick Links

Edition
02/2024
EQUIPMENT MANUAL
SIMATIC
ET 200SP
Digital input/output module DI 8x/DQ 8x24VDC/0.5A ST
6ES7133-6BH00-0BA0
support.industry.siemens.com

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SIMATIC ET 200SP

  • Page 1 Edition 02/2024 EQUIPMENT MANUAL SIMATIC ET 200SP Digital input/output module DI 8x/DQ 8x24VDC/0.5A ST 6ES7133-6BH00-0BA0 support.industry.siemens.com...
  • Page 2 Introduction Safety instructions SIMATIC Product overview ET 200SP Digital input/output module Connection DI 8x/DQ 8x24VDC/0.5A ST (6ES7133-6BH00-0BA0) Parameters/address space Equipment Manual Interrupts/diagnostic messages Technical specifications Parameter data record 02/2024 A5E52173282-AA...
  • Page 3 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 4: Table Of Contents

    Table of contents Introduction............................ET 200SP Documentation Guide..................1.1.1 Information classes ET 200SP.................... 1.1.2 Basic tools........................1.1.3 MultiFieldbus Configuration Tool (MFCT)................1.1.4 SIMATIC Technical Documentation..................11 Safety instructions..........................13 Cybersecurity information....................13 Product overview..........................14 Properties ........................14 Connection............................17 Wiring diagram.........................
  • Page 5: Introduction

    Purpose of the documentation This manual complements the system manual ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293). Functions that generally relate to the system are described in the system manual. The information provided in this manual and in the system/function manuals supports you in commissioning the system.
  • Page 6: 200Sp Documentation Guide

    This arrangement enables you to access the specific content you require. You can download the documentation free of charge from the Internet (https://support.industry.siemens.com/cs/ww/en/view/109742709). Basic information The System Manual describes in detail the configuration, installation, wiring and commissioning of the SIMATIC ET 200SP distributed I/O system.
  • Page 7 Product Information takes precedence over the device and system manuals. You can find the latest Product Information on the ET 200SP distributed I/O system on the Internet. (https://support.industry.siemens.com/cs/de/en/view/73021864) Manual Collection ET 200SP The Manual Collection contains the complete documentation on the SIMATIC ET 200SP distributed I/O system gathered together in one file.
  • Page 8: Basic Tools

    With the TIA Selection Tool , you can generate a complete order list from your product selection or product configuration. You can find the TIA Selection Tool on the Internet. (https://support.industry.siemens.com/cs/ww/en/view/109767888) SIMATIC Automation Tool You can use the SIMATIC Automation Tool to perform commissioning and maintenance activities on various SIMATIC S7 stations as bulk operations independent of TIA Portal.
  • Page 9 You can find SIEMENS PRONETA Basic on the Internet: (https://support.industry.siemens.com/cs/ww/en/view/67460624) SIEMENS PRONETA Professional is a licensed product that offers you additional functions. It offers you simple asset management in PROFINET networks and supports operators of automation systems in automatic data collection/acquisition of the components used through various functions: •...
  • Page 10: Multifieldbus Configuration Tool (Mfct)

    MultiFieldbus- and DALI-devices. In addition, the MFCT offers convenient options for mass firmware updates of ET 200 devices with MultiFieldbus- support and reading service data for many other Siemens devices. Functional scope of the MFCT • MultiFieldbus configuration:...
  • Page 11: Simatic Technical Documentation

    Online Support: Industry Online Support International https://support.industry.siemens.com/cs/ww/en/view/109742705 Watch this short video to find out where you can find the overview directly in Siemens Industry Online Support and how to use Siemens Industry Online Support on your mobile device: Quick introduction to the technical documentation of automation products per video ( https://support.industry.siemens.com/cs/us/en/view/109780491...
  • Page 12 Manuals, characteristics, operating manuals, certificates • Product master data You can find "mySupport" on the Internet. (https://support.industry.siemens.com/My/ww/en) Application examples The application examples support you with various tools and examples for solving your automation tasks. Solutions are shown in interplay with multiple components in the system - separated from the focus on individual products.
  • Page 13: Safety Instructions

    Siemens' products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customers' exposure to cyber threats.
  • Page 14: Product Overview

    Product overview Properties Article number 6ES7133-6BH00-0BA0 View of the module ① Module type and name ⑦ Article number ② LED for diagnostics ⑧ Function and firmware version ③ QR code for identifica­ ⑨ BU type tion link ④ Wiring diagram ⑩...
  • Page 15 Product overview 3.1 Properties Properties The module has the following technical properties: • Digital inputs – 8 digital inputs – Sink input (PNP) – Configurable input delay 0.05 ms to 20 ms (per channel) – Configurable diagnostics (per module) – Suitable for connection of switches and 2-wire sensors in accordance with IEC 61131, type 1 and 3 •...
  • Page 16 • Labeling strips • Color identification labels • Reference identification label • Shield connector See also You can find additional information on the accessories in the ET 200SP distributed I/O system (https://support.industry.siemens.com/cs/ww/en/view/58649293) system manual. Digital input/output module DI 8x/DQ 8x24VDC/0.5A ST (6ES7133-6BH00-0BA0) Equipment Manual, 02/2024, A5E52173282-AA...
  • Page 17: Connection

    Connection Wiring diagram This section contains the pin assignment for the module. You can find information on wiring the BaseUnit in the ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293) system manual. Terminal assignment Description Signal Terminal BaseUnit BU type A0 Terminal Signal Description...
  • Page 18 Connection 4.1 Wiring diagram Output connection types 1-wire connection for channel n 3-wire connection for channel n You can also connect the ground via a potential distribution module (PotDis module). NOTE You can use and combine the different wiring options for all channels. Digital input/output module DI 8x/DQ 8x24VDC/0.5A ST (6ES7133-6BH00-0BA0) Equipment Manual, 02/2024, A5E52173282-AA...
  • Page 19: Block Diagram

    Connection 4.2 Block diagram Block diagram This section contains the block diagram of the module- Figure 4-1  Block diagram for I/O module and BaseUnit Wire-break detection When wire-break detection is configured the module requires a low quiescent current at the digital input in case of "0" signal for the monitoring. The parallel connection of a resistor with 25 kΩ...
  • Page 20: Parameters/Address Space

    Parameters/address space Parameters Specify the module properties with the various parameters in the course of the parameter assignment of the module with STEP 7. The following table lists the configurable parameters. The effective range of the parameters depends on the type of configuration. The following configurations are possible: •...
  • Page 21: Explanation Of Parameters

    Parameters/address space 5.2 Explanation of parameters Parameters Value range Default Reconfig­ Effective range with config­ uration in uration software GSD file GSD file PROFINET I­ PROFIBUS DP  Input delay • None 3.2 ms Channel Module • 0.05 ms • 0.1 ms •...
  • Page 22 Parameters/address space 5.2 Explanation of parameters Diagnostics DQ: Short-circuit to L+ Enable "Short-circuit" diagnostics when a short-circuit occurs between output and L+. Diagnostics DQ: Wire break Enabling of the diagnostics if the line to the actuator is broken. NOTE Wire break diagnostics in problematic electromagnetic conditions To avoid faulty wire break diagnostics, deactivate the diagnostics or increase the current to at least 10 mA.
  • Page 23: Address Space

    Specify whether a light-colored BaseUnit with incoming supply voltage or a dark-colored BaseUnit is located in this slot (see ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293) system manual). A potential group consists of a group of directly adjacent I/O modules within an ET 200SP station, which are supplied via a common supply voltage.
  • Page 24 (0 = value is incorrect). You can find more information on evaluating the value status in the ET 200SP Distributed I/O System (https://support.industry.siemens.com/cs/ww/en/view/58649293) System Manual. Digital input/output module DI 8x/DQ 8x24VDC/0.5A ST (6ES7133-6BH00-0BA0) Equipment Manual, 02/2024, A5E52173282-AA...
  • Page 25: Interrupts/Diagnostic Messages

    Interrupts/diagnostic messages Status and error display LED display The following figure shows you the LED display of the DI 8x/DQ 8x24VDC/0.5A ST. ① DIAG (green/red) ② Input channel status (green) ③ Output channel status (green) ④ PWR (green) Figure 6-1  LED display Meaning of the LED display The following tables show the meaning of the status and error displays.
  • Page 26 Interrupts/diagnostic messages 6.1 Status and error display DIAG LED Table 6-1  DIAG LED fault/error display DIAG LED Meaning Backplane bus supply of the system is interrupted or switched off. Off
 Module parameters not assigned Flashes Module parameters assigned and no module diagnostics Module parameters assigned and module diagnostics Flashes LED channel status inputs...
  • Page 27: Interrupts

    Interrupts/diagnostic messages 6.3 Diagnostics alarms Interrupts The DI 8x/DQ 8x24VDC/0.5A ST digital input/output module supports diagnostic interrupts. Diagnostic interrupts The module generates a diagnostics interrupt at the following events: • Short-circuit • Wire break • Parameter assignment error • Supply voltage missing •...
  • Page 28 Interrupts/diagnostic messages 6.3 Diagnostics alarms Diagnostic interrupt Error code Meaning Remedy Parameter assignment • The module cannot evaluate parameters Correct the parameter assignment error for the channel/module. • Incorrect parameter assignment. Supply voltage miss­ No or insufficient supply voltage L+ •...
  • Page 29: Technical Specifications

    Technical specifications Technical specifications of the DI 8x/DQ 8x24VDC/0.5A ST The following table shows the technical specifications as of 02/2024. You can find a data sheet including daily updated technical specifications on the Internet (https://support.industry.siemens.com/cs/ww/en/pv/6ES7133-6BH00-0BA0/td?dl=en). Article number 6ES7133-6BH00-0BA0 General information  ...
  • Page 30 Technical specifications 7.1 Technical specifications Article number 6ES7133-6BH00-0BA0 Supply voltage   Rated value (DC) 24 V permissible range, lower limit (DC) 19.2 V permissible range, upper limit (DC) 28.8 V Reverse polarity protection Input current   Current consumption, max. 35 mA; without load output voltage / header  ...
  • Page 31 Technical specifications 7.1 Technical specifications Article number 6ES7133-6BH00-0BA0 Input delay (for rated value of input   voltage) for standard inputs   – parameterizable Yes; 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms –...
  • Page 32 Technical specifications 7.1 Technical specifications Article number 6ES7133-6BH00-0BA0 Parallel switching of two outputs   • for uprating for redundant control of a load • Switching frequency   • with resistive load, max. 100 Hz • with inductive load (acc. to IEC 60947-5-1, 0.1 Hz;...
  • Page 33 Technical specifications 7.1 Technical specifications Article number 6ES7133-6BH00-0BA0 Diagnostics indication LED   • Monitoring of the supply voltage Yes; green PWR LED (PWR-LED) • Channel status display Yes; green LED • for channel diagnostics • for module diagnostics Yes; green/red DIAG LED Potential separation  ...
  • Page 34 Rated current of the channel / mA 5 mH 10 mH 30 mH 50 mH 100 mH 300 mH 500 mH 1152 mH Figure 7-1  Maximum switching frequency Dimension drawing See manual ET 200SP BaseUnits (http://support.automation.siemens.com/WW/view/en/58532597/133300) Digital input/output module DI 8x/DQ 8x24VDC/0.5A ST (6ES7133-6BH00-0BA0) Equipment Manual, 02/2024, A5E52173282-AA...
  • Page 35: Parameter Data Record

    Parameter data record Parameter assignment and structure of the parameter data record The data record of the module has an identical structure, regardless of whether you configure the module with PROFIBUS DP or PROFINET IO. With data record 128, you can reconfigure the module in your user program regardless of your programming.
  • Page 36 Parameter data record A.1 Parameter assignment and structure of the parameter data record Structure of data record 128 for the complete module Byte 0 Header information Byte 2 Module header information Byte 4 Module parameters Byte 5 Input channel header information Byte 7 Input channel 0 Byte 8...
  • Page 37 Parameter data record A.1 Parameter assignment and structure of the parameter data record Module header information The figure below shows the structure of the module header information. Byte 2 Number of the following module parameter blocks = 1 Byte 3 Length of the following module parameter block = 1 Figure A-3  Module header information Module parameter block...
  • Page 38 Parameter data record A.1 Parameter assignment and structure of the parameter data record Channel parameter block input channel The figure below shows the structure of the input channel parameter block. You enable a parameter by setting the corresponding bit to "1". Byte 7...14 0 0 0 Input delay...
  • Page 39: Error Codes

    Parameter data record A.2 Error codes Error codes Errors when transferring the data record The module always checks all the values of the transferred data record. Only if all the values were transferred without errors does the module take over the values from the data record. In case of errors, the WRREC instruction for writing data records returns corresponding error codes in the STATUS parameter, see also the description of the "STATUS"...

Table of Contents