Bc Controller Transformer - Mitsubishi Electric PURY-HP72 Service Handbook

R410a
Hide thumbs Also See for PURY-HP72:
Table of Contents

Advertisement

[8-9 Troubleshooting Problems with Major Components on BC Controller ]
8-9-5

BC Controller Transformer

BC controller control board
CNTR
CN03
Red
White
Red
Red
Normal
Abnormal
CNTR(1)-(3)
about 58 Ω.
Open-phase or shorting
CN03(1)-(3)
about 1.6 Ω.
* Before measuring the resistance, pull out the connector.