SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS August 2005 No.OC336 SERVICE MANUAL R407C Outdoor unit [model names] [Service Ref.] Service Ref. is on page 2. • This manual describes only PUH-P25VGAA service data of the outdoor PUH-P35VGAA PU-P35VGAA units. PUH-P35YGAA PU-P35YGAA PUH-P50VGAA...
SAFETY PRECAUTION CAUTIONS RELATED TO NEW REFRIGERANT Cautions for units utilising refrigerant R407C Do not use the existing refrigerant piping. Use liquid refrigerant to charge the system. The old refrigerant and lubricant in the existing piping If gas refrigerant is used to seal the system, the composition contains a large amount of chlorine which may cause the of the refrigerant in the cylinder will change and performance lubricant deterioration of the new unit.
Page 5
[3] Service tools Use the below service tools as exclusive tools for R407C refrigerant. Tool name Specifications Gauge manifold ·Only for R407C. ·Use the existing fitting SPECIFICATIONS. (UNF7/16) ·Use high-tension side pressure of 3.43MPa·G or over. Charge hose ·Only for R407C. ·Use pressure performance of 5.10MPa·G or over.
PART NAMES AND FUNCTIONS Air outlet (Expels warm air during cooling) Air outlet Air intake Air intake PUH-P25VGAA.UK PUH-P50VGAA.UK PUH-P50YGAA.UK PUH-P35VGAA.UK PUH-P60VGAA.UK PUH-P60YGAA.UK PUH-P35YGAA.UK PUH-P71VGAA.UK PUH-P71YGAA.UK PU-P35VGAA.UK PU-P50VGAA.UK PU-P50YGAA.UK PU-P35YGAA.UK PU-P60VGAA.UK PU-P60YGAA.UK PU-P71VGAA.UK PU-P71YGAA.UK Air outlet Air outlet Air intake Air intake PUH-P100VGAA.UK PUH-P125YGAA.UK...
SPECIFICATIONS 4-1. HEAT PUMP PUH-P25VAA.UK PUH-P35VGAA / YGAA.UK Service Ref. Cooling Heating Cooling Heating Mode Single,50Hz,230V Single,50Hz,230V / 3-ph,50Hz,400V Power supply (phase, cycle, voltage) Running current 5.32 4.89 7.61 / 2.54 7.85 / 2.62 7.23 10.67/5.4 Max current External finish Munsell 5Y 7/1 Refrigerant control Linear Expansion Valve...
Page 8
PUH-P100VGAA / YGAA.UK PUH-P71VGAA / YGAA.UK Service Ref. Mode Cooling Heating Cooling Heating Single, 50Hz, 230V / 3-ph, 50Hz, 400V(4wires) Power supply (phase, cycle, voltage) Running current 15.66 / 5.23 16.67 / 5.56 16.43/ 5.48 17.34 / 5.79 22.66 / 10.8 23.57 / 10.8 Max current External finish...
Page 9
4-2. COOLING ONLY TYPE PU-P35VGAA / YGAA.UK PU-P50VGAA / YGAA.UK PU-P60VGAA / YGAA.UK Service Ref. Cooling Cooling Cooling Mode Single, 50Hz, 230V / 3-ph, 50Hz, 400V(4wires) Power supply (phase, cycle, voltage) Running current 7.61 / 2.54 10.97 / 3.98 13.27 / 4.43 10.67 / 5.4 15.35 / 7.0 18.03 / 7.7...
Page 10
PU-P125YGAA.UK PU-P140YGAA.UK Service Ref. Mode Cooling Cooling 3-ph, 50Hz,400V(4wires) Power supply (phase, cycle, voltage) Running current 7.52 8.92 18.0 20.4 Max. current External finish Munsell 5Y 7/1 Linear Expansion Valve Refrigerant control Hermetic Compressor BE82YADMT BE96YADMT Model Motor output Line start Starter type Thermal relay, HP switch, Discharge thermo Protection devices...
WIRING SPECIFICATIONS 8-1. FIELD ELECTRICAL WIRING (power wiring specifications) Outdoor unit model P25,35V P50,60V P71,100V P35,50,60,71,100Y P125, 140Y Outdoor unit power supply ~/N (single), 50 Hz, ~/N (single), 50 Hz, ~/N (single), 50 Hz, 3N ~ (3phase), 50 Hz, 3N ~ (3phase), 50 Hz, 230 V 230 V 230 V...
Page 25
8-2. INDOOR-OUTDOOR CONNECTING CABLE L(m) Wire size Number Cross section Polarity of cable of wires Round Clockwise : S1-S2-S3 (50) w Pay attention to stripe of yellow and green Flat Not applicable applicable (Because center wire has no cover finish) Flat (45) From left to right : S1-Open-S2-S3...
Page 26
8-3. M-NET WIRING METHOD (Points to notice) (1) Outside the unit, transmission wires should stay away from electric wires in order to prevent electromagnetic noise from making an influence on the signal communication. Place them at intervals of more than 5cm. Do not put them in the same conduit tube.
Page 27
M-NET wiring M-NET (1) Use 2-core x 1.25mm shield wire for electric wires. terminal Ground (Excluding the case connecting to system controller.) block wire (2) Connect the wire to the M-NET terminal block.Connect one core of the transmission wire (non-polar) to A terminal and the other to B. Peel the shield wire, twist the shield part to a string and connect it to S terminal.
TROUBLESHOOTING 10-1. TROUBLESHOOTING <Error code display by self-diagnosis and actions to be taken for service (summary)> Present and past error codes are logged and displayed on the wired remote controller and control board of outdoor unit. Actions to be taken for service, which depends on whether or not the inferior phenomenon is reoccurring at service, are sum- marized in the table below.
Page 31
Operating procedures While the room temperature display on the remote "TEST RUN" and the currently selected controller is “PLEASE WAIT”, the remote controller is disabled. operation mode are displayed altemately. Wait until “PLEASE WAIT” disappears before using remote controller. 1. Turn on the main power supply. “PLEASE WAIT”...
Page 32
Test run [for wireless remote controller] Measure an impedance between the power supply terminal block on the outdoor unit and ground with a 500V Megger and check that it is equal to or greater than 1.0M". TEST RUN 1 Turn on the main power to the unit. TEST RUN 2 Press the button twice continuously.
Page 33
10-3. HOW TO PRECEED "SELF-DIAGNOSIS" 10-3-1. When a Problem Occurs During Operation If a problem occurs in the air conditioner, the indoor and outdoor units will stop, and the problem is shown in the remote controller display. [CHECK] and the refrigerant address are displayed on the temperature display, and the error code and unit number are displayed alternately as shown below.
When the error history is reset, the display will look like the one shown below. Press the button twice within three seconds. The self-diagnosis ON/OFF However, if you fail to reset the error history, the error content will be displayed again. address or refrigerant address will flash.
Page 35
10-3-4. Malfunction-diagnosis method by wireless remote controller <In case of trouble during operation> When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform unusual stop. < Malfunction-diagnosis method at maintenance service> [Procedure] 1.
Page 36
• Refer to the following tables for details on the check codes. [Output pattern A] Beeper sounds Beep Beep Beep Beep Beep Beep Beep OPERATION · · · Repeated INDICATOR lamp flash pattern Approx. 2.5 sec. 0.5 sec. 0.5 sec. 0.5 sec.
10-4. SELF-DIAGNOSIS ACTION TABLE <Abnormalities detected when the power is put on> (Note 1) The number in ( ) is the error cord of upper remote controller (M-NET) Error Code Meaning of error code and detection method Case Judgment and action 1 No voltage is supplied to termi- 1 Check following items.
Page 38
Case Error Code Meaning of error code and detection method Judgment and action 1 Check disconnection or looseness or polarity Indoor/outdoor unit connector mis- 1 Contact failure or mis-wiring of wiring, excessive number of units (5 indoor/outdoor unit connecting of indoor/outdoor unit connecting wire of units or more) indoor and outdoor units.
Page 39
Case Error Code Meaning of error code and detection method Judgment and action 1 Short cycle of indoor unit 1-6 Check indoor unit and repair defectives. Abnormal high pressure (High-pressure switch 63H worked) 2 Clogged filter of indoor unit 7 Check full open stop valve. Abnormal if high-pressure switch 63H 3 Decreased airflow caused by 8 Check piping and repair defectives.
Page 40
Case Error Code Meaning of error code and detection method Judgment and action Abnormal shortage of refrigerant 1 Leakage or shortage of refrig- 1 Check leakage of refrigerant. Abnormal if intake super heat exceeds fol- erant Charge refrigerant. lowing temperature during heating com- 2 Defective operation of stop 2 Check if stop valve is full open.
Page 41
Note: E1, E2 and E4 to E7, refer to indoor unit service manual. Case Error Code Meaning of error code and detection method Judgment and action 1 Abnormal compressor 1 Check compressor. Compressor over current (start-up locked) breaking 2 Clogged indoor filter Refer to 5-2.
Page 42
Case Error Code Meaning of error code and detection method Judgment and action 12 Put the power off, and on again to check. 1 Noise has entered transmis- Not defined error code Replace indoor controller board or outdoor This code is displayed when not defined sion wire of remote controller.
Page 43
Error Code Meaning of error code and detection method Case Judgment and action NO ACK Common factor that has no rela- Always try the followings when the error tion with abnormality source. 1. Transmitting side controller detects “A7” occures. 1 The unit of former address abnormal if a massage was transmitted does not exist as address but there is no reply (ACK) that a mas-...
Page 44
From the previous page. Error Code Meaning of error code and detection method Case Judgment and action Same as mentioned in “A7” of the previous 5. If displayed address or attribute is 1 During sequential operation of page. FRESH MASTER, indoor unit and FRESH MAS- TER of other refrigerant sys- Indoor unit detects abnormality when...
10-5. TROUBLESHOOTING BY INFERIOR PHENOMENA Phenomena Factor Countermeasure (1)Remote controller display does not Reference (Meaning of the indoor control board LED) work. (Electric current marker “ ” is not LED1 : Micro computer power supply displayed on the remote controller.) ..Display of DC14V is supply or not from indoor power.
Page 46
Phenomena Factor Countermeasure 1Louver motor fault. 1Louver motor resistance value check (7)Left/right louver performance fault. 2Disconnecting, breaking and contact fault of the con- 2Check the removing of indoor controller nector. board (CNL) breaking line and contact fault. 1Open the grille to check the filter. (8)Though the remote controller dis- 1Filter clogging (dirt) Clean the filter and remove dust or dirt...
Page 47
[for wired remote controller] Before you call out a repair man, check the following table to see whether there is a simple solution to your problem. Solution Problem Solution Problem The room neither gets cool nor Clean the filter. (Dust and rebris This sound is made when internal A ticking noise is heard from warm very much.
Page 48
Solution Problem Solution Problem The unit started even though the Is this timer on? "DEFROST" is displayed (no air Frost adheres to the outdoor unit start/stop button was not pushed. Press the start/stop button to stop comes out the unit). when the outside air temperature the unit.
Page 49
[for wireless remote controller] Before you call out a repair man, check the following table to see whether there is a simple solution to your problem. Display reading Cause Solution Problem When POWER ON/OFF button is Main power switch is turned off. Turn main power on.
Page 50
10-6. HOW TO CHECK THE PARTS PUH-P25, P35, P50, P60, P71, P100VGAA.UK PUH-P35, P50, P60, P71, P100, P125, P140YGAA.UK PU-P35, P50, P60, P71, P100VGAA.UK PU-P35, P50, P60, P71, P100, P125, P140YGAA.UK Parts name Check points Liquid temperature Disconnect the connector then measure the resistance using a tester. (Surrounding temperature 10:~30:) thermistor (TH3) Normal...
<Thermistor characteristic graph> < Thermistor for lower temperature > Liquid temperature thermistor(TH3) Thermistor for Condenser/evaporator temperature lower temperature thermistor(TH6) Thermistor R =15k' ± 3% Fixed number of B=3480 ± 2% Rt=15exp { 3480( 273+t 15k' 9.6k' 6.3k' 5.2k' 4.3k' 3.0k' -20 -10 10 20 30 40 50 Temperature (:)
Page 52
<Output pulse signal and the valve operation> Output Output (Phase) Closing a valve : 1 Opening a valve : 4 The output pulse shifts in above order. 1. When linear expansion valve operation stops, all output phase become OFF. 2. At phase interruption or when phase does not shift in order, motor does not rotate smoothly and motor will locks and vibrates.
Page 53
10-7. TEST POINT DIAGRAM Outdoor controller board PUH-P25, P35, P50, P60, P71, P100VGAA.UK PUH-P35, P50, P60, P71, P100, P125, P140YGAA.UK PU-P35, P50, P60, P71, P100VGAA.UK PU-P35, P50, P60, P71, P100, P125, P140YGAA.UK When connecting A-control Service Tool [ PAC-SK52ST ], MF4, MF3 operation mode can be displayed (MF4 is only for PUH-P100V, PU-P100V, PUH-P100~140Y and PU-P100~140Y)
10-8. EMERGENCY OPERATION 1. When the outdoor unit becomes under mentioned inspection display. Also when the wired remote controller or micro com- puter in the indoor unit is broken. If there is not any wrong section, short-circuited connector (CN31) in the outdoor con- troller board is possible to emergency operation.
Page 55
10-9. FUNCTION OF SWITCHS, CONNECTORS AND JUMPERS Outdoor switch for a new freon function table Switch Action by the switch operation Function Effective timing Signal Compulsory defrosting w1 Start Normal Heat compressor operating Abnormal history clear Clear Normal off or operating 1 2 3 4 5 6 1 2 3 4 5 6...
Page 56
Jumper connector function table Switch Action by the switch operation Function Effective timing Signal Switch of single phase and 3 phase Single phase When power supply ON 3 phase power supply Switch of cooling When power supply ON Cooling only Cooling and heat pump only/cooling and heat pump :Short...
Page 57
Outdoor unit operation monitor function Operation indicator SW2 : Indicator change of self diagnosis SW2 setting Display detail Explanation for display Unit Code indication 2 3 4 5 6 <Digital indicator LED1 working details> · Lighting (Normal operation) : Indicating the operation mode. (Be sure the 1 to 6 in the SW2 are set to OFF) (Initial setting) (1) Display when the power supply ON.
Page 58
SW2 setting Display detail Explanation for display Unit Piping temperature. (TH3) – 40~90 – 40~90 (When the coil thermistor is 0:or below, “–” and temperature displays by turns.) (Example) When -10: One second interval 2 3 4 5 6 – Discharge temperature.
Page 59
SW2 setting Display detail Explanation for display Unit Piping temperature (TH3) on error – 40~90 occurring (When the coil thermistor is 0:and less, “–” and – 40~90 temperature are displayed by turns) (Example) When –15: One second interval 2 3 4 5 6 –...
Page 60
SW2 setting Display detail Explanation for display Unit Display as an outdoor Capacity setting display Capacity Code capacity code Code display 2 3 4 5 6 P100 P125 P140 Outdoor unit setting advice The tens digit (Total display for applied setting) Setting details Display details H·P / Cooling only...
Page 61
SW2 setting Display detail Explanation for display Unit Indoor setting temperature 17~30 17~30 2 3 4 5 6 Outdoor piping temperature/Cond./Eva. – 39~88 (TH6) (When the temperature is 0: or less, “–” and – 39~88 temperature are displayed by turns) 2 3 4 5 6 Discharge super heat.
Page 62
SW2 setting Display detail Explanation for display Unit 0~999 Thermo-on time to error stop. (When the time is 100 or more, the hundreds 0~999 digit and tens, units digit are displayed by turns.) Minute (Example) When 415 minutes 2 3 4 5 6 One second interval –39~88 Indoor unit piping temperature / cond.
Page 63
<Display function of inspection for outdoor unit> • The blinking patterns of two LEDs—LED1(Green) and LED2(Red)—show the diagnoses of troubles in case of malfunction. • By 7SEG indicator board indicates the operation mode and inspection types. LED1 (Green) LED2 (Red) Indication (O.B) Error Name Inspection method...
Page 64
From the preceding page. Indication (O.B) Error Name Inspection method LED1 LED2 (Green) (Red) 1 Check if ball valves are open. •Abnormal high discharge temperature(TH4) 3 blinks 1 blink 2 Check the continuity of connector (TH4) on outdoor controller board by using a tester. 3 Check if the unit fills the refrigerant at the same amount as specified.
FUNCTION SETTING 11-1. UNIT FUNCTION SETTING BY THE REMOTE CONTROLLER Each function can be set according to necessity using the remote controller. The setting of function for each unit can only be done by the remote controller. Select function available from the table 1. <Table 1>...
Page 66
11-1-1. Selecting functions using the wired remote controller First, try to familiarize yourself with the flow of the function selection procedure. In this section, an example of setting the room temperature detection position is given. For actual operations, refer to steps 1 to 0 . Setting number Refrigerant address Unit number...
Page 67
[Operating Procedure] 1 Check the setting items provided by function selection. If settings for a mode are changed by function selection, the functions of that mode will be changed accordingly. Check all the current settings according to steps 2 to 7 , fill in the "Check" column in Table 1, and then change them as necessary. For factory settings, refer to the indoor unit's installation manual. 2 Switch off the remote controller.
Page 68
11-1-2. Selecting functions using the wireless remote controller (Type C) Functions can be selected with the wireless remote controller. Function selection using wireless remote controller is available only for refriger- ant system with wireless function. Refrigerant address cannot be specified by the wireless remote controller. [Flow of function selection procedure] The flow of the function selection procedure is shown below.
Page 69
11-2. FUNCTION SELECTION OF REMOTE CONTROLLER The setting of the following remote controller functions can be changed using the remote controller function selection mode. Change the setting when needed. Item 1 Item 2 Item 3 (Setting content) 1.Change Language Language setting to display •...
Page 70
Flowchart of Function Setting Setting language (English) Normal display (Display when the air condition is not running) Hold down the button and press the button for 2 seconds. Hold down the button and press the button for 2 seconds. Press the operation mode button. Press the TIMER MENU button.
DISASSEMBLY PROCEDURE PUH-P125YGAA.UK PUH-P140YGAA.UK OPERATING PROCEDURE PHOTOS 1. Removing the Service panel and Top panel Photo 1 Top panel screws Top panel (1) Remove the 3 service panel fixing screws (5 15) and slide the hook to remove the service panel. (2) Remove the screws (3 for front, 2 for rear/5 15) of the top panel and remove it.
Page 72
OPERATING PROCEDURE PHOTOS 4. Removing the liquid temperature thermistor, discharge Photo 4 temperature thermistor and condenser/evaporator temperature thermistor Condenser/evaporator Clamp (1) Remove the service panel. (See Photo 1) temperature thermistor (2) Remove the top panel. (See Photo 1) (When the top panel removing is not possible, remove the electric parts box.
Page 73
OPERATING PROCEDURE PHOTOS 9. Removing the high pressure switch Photo 6 (1) Remove the service panel. (See Photo 1) Lead wire (2) Remove the top panel. (See Photo 1) (3) Remove the electrical box. (See Photo 3) (4) Disconnect the lead wire of the pressure switch. (See Photo 6) Capillary (5) Remove the braze part of the pressure switch.
Page 74
OPERATING PROCEDURE PHOTOS 12. Removing the Bell mouth Photo 9 Bell mouth fixing screw (1) Remove the 6 fan guard fixing screws (5 15) to remove it. (See Photo 1) (2) Remove the top panel. (3) Remove a bell mouth fixing screw (5 15) to remove it.
Page 87
ty/set Price Wiring Recom- Part No. Part Name Specification PUH-P•YGAA.UK PU-P•YGAA.UK Remarks Diagram mended Unit Amount Symbol S70 332 708 CONTACTOR MSO-N11 51C,52C S70 333 708 CONTACTOR MSO-N11 51C,52C S70 E10 716 TERMINAL BLOCK 4P(L1,L2,L3,N) S70 E04 716 TERMINAL BLOCK 3P(S1,S2,S3) S70 K05 763 OUTDOOR FAN MOTOR...
Page 88
FUNCTIONAL PARTS PUH-P71VGAA.UK PU-P71VGAA.UK FUSE 10 11...
Page 89
ty/set Price Wiring Recom- Part No. Part Name Specification Remarks PUH-P71V PU-P71V Diagram mended Unit Amount Symbol GAA.UK GAA.UK S70 330 708 CONTACTOR S-N18EX S70 E03 716 TERMINAL BLOCK 2P(L,N) S70 E04 716 TERMINAL BLOCK 3P(S1,S2,S3) S70 K05 763 OUTDOOR FAN MOTOR YDK75-6U S70 K04 115 PROPELLER FAN 4...
Page 90
FUNCTIONAL PARTS PUH-P71YGAA.UK PU-P71YGAA.UK FUSE 10 11...
Page 91
ty/set Price Wiring Recom- Part No. Part Name Specification PUH-P71Y PU-P71Y Remarks Diagram mended Unit Amount Symbol GAA.UK GAA.UK S70 331 708 CONTACTOR MSO-N11 51C,52C S70 E10 716 TERMINAL BLOCK 4P(L1,L2,L3,N) S70 E04 716 TERMINAL BLOCK 3P(S1,S2,S3) S70 K05 763 OUTDOOR FAN MOTOR YDK75-6U S70 K04 115...
Page 92
FUNCTIONAL PARTS PUH-P100VGAA.UK PU-P100VGAA.UK FUSE 26 25...
Page 93
Part number that are circled are not shown in the figure. ty/set Price Wiring Recom- Remarks Part No. Part Name Specification PUH-P100V PU-P100V Diagram mended Unit Amount Symbol GAA.UK GAA.UK S70 E03 763 OUTDOOR FAN MOTOR N026P72MT S70 30L 115 PROPELLER FAN 4 S70 30L 097 S70 E05 408...
Page 94
FUNCTIONAL PARTS PUH-P100YGAA.UK PU-P100YGAA.UK FUSE 26 25...
Page 95
ty/set Price Wining Recom- Remarks Part No. Part Name Specification PUH-100Y PU-P100Y Diagram mended Unit Amount Symbol GAA.UK GAA.UK S70 E03 763 OUTDOOR FAN MOTOR N026P72MT S70 30L 115 PROPELLER FAN 4 S70 30L 097 S70 E05 408 HEAT EXCHANGER S70 E04 763 OUTDOOR FAN MOTOR N02A672MT...
Page 97
Part number that is circled is not shown in the figure. ty/set Price Wiring Recom- PUH-P•YGAA.UK PU-P•YGAA.UK Remarks Part No. Part Name Specification Diagram mended Unit Amount Symbol OUTDOOR FAN MOTOR S70 E03 763 N026P72MT PROPELLER FAN 4 S70 30L 115 S70 30L 097 S70 E07 408 HEAT EXCHANGER (UNDER)
Page 98