DPW-199C This appliance is certified for use without any limitation of the any altitude installation. However for better combustion, from 2,000ft to 4,500ft installation decrease the manifold pressure 0.3' W.C.for Natural Gas. From 4,500ft to 6,000ft installation derease the maniforld pressure 0.6'W.C.
Page 4
doesn’t match supplied gas and specified gas, case...
Page 9
This water heater shall not be connected to any heating system or component(s) previously used without thoroughly flushing the system prior to filling. Contaminated space heating water can cause scale or sludge build-up which affects the system efficiency and life of unit and its components.
Page 15
Temperature Control Indicator and Button Function(DSR-420F) Low water level Indoor Temperature warning light Domestic hot water Indicator temperature indicator If there is not enough Indicates the current water in appliance, After pressing Domestic room temperature of this lamp turns on. Combustion Symbol hot water temperature around room controller...
Page 16
DSR-420F DSR-420F AUTO.ECO AUTO.ECO ℉ ℉ controlling the control dial DSR-420F is blinking. AUTO.ECO ℉ DSR-420F using the control dial. AUTO.ECO ℉...
Page 17
the control dial DSR-420F DSR-420F AUTO.ECO AUTO.ECO ℉ ℉ use the control dial DSR-420F AUTO.ECO ℉...
Page 18
℉ Outdoor reset ℉ Press the outdoor reset button, Press the power button to turn the boiler use the reset function. the unit on. In outdoor reset mode, unit ignores the set temp and operates according to heating curve graph depending on your selected reset ratio.
Page 22
heating loop does not have enough water to operate. fill the loop by opening #6 water supply valve. (Normal operation pressure of closed loop: 14~28psi) DSR-420F AUTO.ECO ℉...
Page 23
Air in the system can trigger low water level warning light. Bleed air out and fill the system as instructed as above.
Page 25
DPW-199C 195,000 3" or 4" 3" 38ft Equivalent each for both Intake and Exhaust Max Vent Length (feet) 4" 45ft Equivalent each for both Intake and Exhaust 3.5" or 4.5" 3" or 4"...
Part List Part No Part Name Part No Part Name 2010435 2020355 Manifolder assembly(LNG) Case Assembly 2020357 Manifolder assembly(LPG) 2070476 Chassis Assembly 3040379 3100108 M4 X 12 Screw Flue collar(3") 3040378 2030278 Gas Valve (UP34-42) Air Intake Connector(3") 3050092 Gas connection pipe 3090260 Flue collar sealing packing (Gas Pressure Point)
Page 30
Part List Part No Part Name Part No Part Name 301 3080136 2060229 Flow switch Flue connector packing 2060228 Water supplementation device 2130439 Latent heat exchanger assembly 2130052 3010925 Fixing clip(P6) Duct assembly 3030200 Expansion vessel connector nipple 2070469 Sensible heat exchanger 3080181 Packing(P14.5) assembly Overheat thermostat...
Page 35
Measure the voltage at the both Blue gas valve wires, then check the both White gas valve wires. If the solenoid valve become to be closed although the voltage reading is 120V, the gas vlave should be replaced. If PCB is not supplying 120V, replace PCB.
Page 36
the burner is not operating, measure the voltage at the both Blue gas valve wires, then check the both White gas valve wires. PCB should be replaced.
Page 37
1) Make sure flame sensing rod is not touching the burner. 2) There is no voltage to the gas valve but there are small flames in the combustion chamber area when the unit stops running.
Page 40
<Air Pressure Switch> <Flg.2> Make sure drain hose is not Problem with drain clogged or frozen. <Flg.2>...
Page 42
Make sure the unit is mounted on a non-combustible material. It may cause mounting screw corrosion and result in failure. from unit falling. mounting plate securely. mounting bracket is not strong enough, the appliance can fall. from unit falling.
Page 47
DPW-199C multiple vent terminals vertically in-line. Do not cover the vent terminal with any type of protective screen or enclosure. In-line or blocked terminals can cause abnormal combustion resulting undesired performance from the water heater.
Page 48
3" or 4" DPW-199C ( one elbow is equal to 5ft length ) See table 1 below. 5. Minimum pipe length of 10ft is recommended to prevent freezing air entering the unit in cold climate. PVC pipe extension is recommended to prevent recirculation of flue gas.
Page 52
Other venting option It is allowed to run exhaust flue pipe through a different wall from air intake pipe side. Maximum allowed flue length remains the same. (Table on page 52) The 90 degree elbow must be installed to the air intake pipe.
Page 53
Other venting option (Single pipe venting) DPW-199C : 3" or 4" Schejule 40 PVC ( one elbow is equal to 5ft length ) See table 1 below. 5. Minimum pipe length of 10ft is recommended to prevent freezing air entering the unit in cold climate.
Page 54
Other venting option #3 (Concentric Vent Termination) 2" & 4" Concentric vent Schedule 40 PVC DPW-199C 6" & 4" Concentric vent Schedule 40 PVC ( one elbow is equal to 5ft length ) ( See table 1 below ) 5. Minimum pipe length of 10ft is recommended to prevent freezing air entering the unit in cold climate.
Page 55
Other venting design #4 (Snorkel flue) or 4" DPW-199C ( one elbow is equal to 5ft length ) ( See table 1 below ) 38 feet 5. Minimum pipe length of 10ft is recommended to prevent freezing air entering the unit in cold climate.
Page 81
Quietside Corporation pursues a policy of continuous improvement in design, specifications and performance of units. Quietside Corporation reserves the right to make changes on products design, specifications and performance without further notice. Please consult with Quietside Corporation for the latest update.