hit counter script
Mitsubishi Electric PKFY-P VKM-E Installation Manual
Mitsubishi Electric PKFY-P VKM-E Installation Manual

Mitsubishi Electric PKFY-P VKM-E Installation Manual

Air-conditioners for building application - indoor unit
Hide thumbs Also See for PKFY-P VKM-E:

Advertisement

Quick Links

Air-Conditioners For Building Application

INDOOR UNIT

PKFY-P·VKM-E

INSTALLATION MANUAL

For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner
unit.
INSTALLATIONSHANDBUCH
Zum sicheren und ordnungsgemäßen Gebrauch der Klimaanlage das Installationshandbuch gründlich
durchlesen.
MANUEL D'INSTALLATION
Veuillez lire le manuel d'installation en entier avant d'installer ce climatiseur pour éviter tout accident et vous
assurer d'une utilisation correcte.
INSTALLATIEHANDLEIDING
Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner
installeert.
MANUAL DE INSTALACIÓN
Para un uso seguro y correcto, lea detalladamente este manual de instalación antes de montar la unidad de
aire acondicionado.
MANUALE DI INSTALLAZIONE
Per un uso sicuro e corretto, leggere attentamente questo manuale di installazione prima di installare il
condizionatore d'aria.
E
MANUAL DE INSTALAÇÃO
Para segurança e utilização correctas, leia atentamente este manual de instalação antes de instalar a unidade
de ar condicionado.
MONTA ELK TABI
mniyetli ve do ru biçimde nas l kullan laca n
elkitab n dikkatle okuyunuz.
EIPI IO O H I N E KATA TA H
,
For use with the R410A
Bei Verwendung von R410A
A utiliser avec le R410A
Bij gebruik van R410A
Para utilizar con el R410A
FOR INSTALLER
FÜR INSTALLATEURE
POUR L'INSTALLATEUR
VOOR DE INSTALLATEUR
PARA EL INSTALADOR
PER L'INSTALLATORE
.
PARA O INSTALADOR
renmek için lütfen klima cihaz n monte etmeden nce bu
.
Uso del refrigerante R410A
R410A
Para utilizaçao com o R410A
R410A ile beraber kullanmak için
,
MONT R Ç N
R410A
English (GB)
Deutsch (D)
Français (F)
Nederlands (NL)
Español (E)
Italiano (I)
(GR)
Português (P)
Türkçe (TR)
(RU)

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric PKFY-P VKM-E

  • Page 1: Indoor Unit

    Air-Conditioners For Building Application INDOOR UNIT PKFY-P·VKM-E For use with the R410A Uso del refrigerante R410A Bei Verwendung von R410A R410A A utiliser avec le R410A Para utilizaçao com o R410A Bij gebruik van R410A R410A ile beraber kullanmak için Para utilizar con el R410A R410A INSTALLATION MANUAL...
  • Page 2: Table Of Contents

    Failure to observe these instructions may result in overheating or a fire. specified refrigerant (R410A) to charge the refrigerant lines. Do not mi it Use only accessories authorized by Mitsubishi Electric and ask the dealer with any other refrigerant and do not allow air to remain in the lines.
  • Page 3: Installation Location

    2. Installation location PKFY-P·VKM-E 2.1. Outline dimensions (Indoor unit) (Fig. 2-1) Select a proper position allowing the following clearances for installation and (mm) 1170 maintenance. PKFY-P·VKM-E (mm) Min. 100.5 Min. 52.3 Min. 48 Min. 250 Min. 220 Air outlet: Do not place an obstacle within 1500 mm of the air outlet. Floor surface Furnishing When the projection dimension of a curtain rail or the like from the wall exceeds 60 mm,...
  • Page 4 . Installing the indoor unit .2. . Installing the wall mounting fi ture Since the indoor unit weighs near 22 kg, selection of the mounting location requires thorough consideration. If the wall does not seem to be strong enough, reinforce it with boards or beams before installation. The mounting fi ture must be secured at both ends and at the centre, if possible.
  • Page 5 . Installing the indoor unit Leakage check of the L-shaped connection pipe connection portion 1. Attach the charge nut 5 to the liquid pipe side joint portion. Tightening force: 34 to 42 N·m 2. Pressurize by filling with nitrogen gas from the charge nut. Do not pressurize to the current constant pressure all at once.
  • Page 6 . Installing the indoor unit . . Mounting the indoor unit 1. Affix the mount board 1 to the wall. 2. Hang the indoor unit on the hook positioned on the upper part of the mount board. Rear, right and lower piping (Fig. -14) 3.
  • Page 7: Installing The Refrigerant Piping

    4. Installing the refrigerant piping 4.1. Connecting pipes (Fig. 4-1) 45±2° When commercially available copper pipes are used, wrap liquid and gas pipes with commercially available insulation materials (heat-resistant to 100 C or more, thickness of 12 mm or more). The indoor parts of the drain pipe should be wrapped with polyethylene foam insulation materials (specific gravity of 0.03, thickness of 9 mm or more).
  • Page 8 4. Installing the refrigerant piping 4. . Refrigerant piping (Fig. 4- ) Indoor unit 1. Remove the flare nut and cap of the indoor unit. 2. Make a flare for the liquid pipe and gas pipe and apply refrigerating machine oil (available from your local supplier) to the flare sheet surface.
  • Page 9: Drainage Piping Work

    . Drainage piping work .1. Drainage piping work (Fig. -1) Drain pipes should have an inclination of 1 100 or more. For extension of the drain pipe, use a soft hose (inner dia. 15 mm) available on the market or hard vinyl chloride pipe (VP-16 O.D. ø22 PVC TUBE). Make sure that there is no water leakage from the connections.
  • Page 10: Electrical Work

    . Electrical work .1. Electrical work PKFY-P·VKM-E PKFY-P·VKM-E (Fig. -1) Connection can be made without removing the front panel. 1. Open the front grille, remove the screw (1 piece), and remove the electrical parts cover. 2. Securely connect each wire to the terminal board. * In consideration of servicing, provide extra length for each of the wires.
  • Page 11 . Electrical work Breaker for wiring Minimum wire thickness (mm²) Local switch (A) (NFB) Total operating current of the indoor unit Ground-fault interrupter *1 Main cable Branch Ground Capacity Fuse F0 = 16 A or less *2 20 A current sensitivity *3 F0 = 25 A or less *2 30 A current sensitivity *3 F0 = 32 A or less *2...
  • Page 12: Electrical Characteristics

    . Electrical work .4. Connecting remote controller, indoor and outdoor transmission cables (Fig. - ) M1 M2 M1 M2 M1 M2 TB15 TB5 TB15 Connect indoor unit TB5 and outdoor unit TB3. (Non-polarized 2-wire) The “S” on indoor unit TB5 is a shielding wire connection. For specifications about the connecting cables, refer to the outdoor unit installation manual.
  • Page 13: Test Run

    . Test run .1. Before test run After completing installation and the wiring and piping of the indoor and outdoor Do not carry out this test on the control wiring (low voltage circuit) terminals. units, check for refrigerant leakage, looseness in the power supply or control Warning: wiring, wrong polarity, and no disconnection of one phase in the supply.
  • Page 14 . Test run Step 2 Perform the test run and check the air ow temperature and auto vane. Test run Remain Remain 1 Press the button to go through the operation modes in the order of “Cool” and “Heat”. (Fig. 7-5) Pipe Cool mode: Check the cold air blow off.
  • Page 15 ................119 ..................126 ..................120 ................127 ..............120 ................130 ................124 “ ” PAR- 32MAA. “ ”. “ ” Mitsubishi Electric (R410A) R410A R410A.
  • Page 16 PKFY-P·VKM-E 2.1. . 2-1) 1170 PKFY-P·VKM-E . 100,5 . 52,3 . 48 . 250 . 220 1500 J 1800 K 108 . 2-1 L 550 : 265 3.1. . 3-1) P100 . 3-1 3.2. PKFY-P·VKM-E 3.2.1. 15.5 12.5 37.5 62.5 87.5 PKFY-P·VKM-E ( .
  • Page 17 3.2.3. PKFY-P·VKM-E PKFY-P·VKM-E ( . 3-4) . 120 (617,6 . 220 . 70 (130 (4 × 25) 2 3.3. . 3-5) . 3-4 3.4. PKFY-P·VKM-E . 3-5 . 3-6) PKFY-P·VKM-E . 3-9) . 3-10) A L- . 3-6 . 3-7 .
  • Page 18 2G), 2G), 4,15 (41,5 0,01 (0,1 2G). . 3-11) . 125. . 3-11 . 3-12) . 3-12 . 3-13) . 6. . 3-13...
  • Page 19 3.5. . 3-14) 1. ( 3-15) . 3-14 . 3-16) . 3-15 PKFY-P·VKM-E . 3-16...
  • Page 20 4.1. . 4-1) 45±2° 0,03; . 4-1 O.D. ø9,52 12,8 - 13,2 ø15,88 19,3 - 19,7 ø19,05 22,9 - 23,3 R410A O.D. ( · ) ( · ) ODø9,52 34 - 42 ODø15,88 68 - 82 P100 ODø9,52 34 - 42 ODø15,88 68 - 82 PKFY-P·VKM-E...
  • Page 21 4.3. . 4-3) . 4-3 4.3.1. . 4-4) PKFY-P·VKM-E . 4-4...
  • Page 22 5.1. . 5-1) 1/100 (VP-16/ , O.D. ø22). . 5-1 (VP-16) . 5-2) . 5-2 PKFY-P·VKM-E . 5-3) . 5-3 . 5-4) . 5-4...
  • Page 23 PKFY-P·VKM-E 6.1. PKFY-P·VKM-E ( . 6-1) MA: (1, 2) : (M1, M2, S) 55mm 12mm 6.2. 245 IEC 53 IEC57, 245 IEC 53 227 IEC 53. , 1/8 . 6-1 .6-2 ~220-240V ~220-240V TB15 . 6-2...
  • Page 24 ²) F0 = 16 A 20 A *3 F0 = 25 A 30 A *3 F0 = 32 A 40 A *3 IEC61000-3-3. “F0” “F1” “F2”. F1 = × 1,2 F2 = {V1 × ( 1)/C} + {V1 × ( 2)/C} + {V1 ×...
  • Page 25 6.4. M1 M2 M1 M2 M1 M2 . 6-3) TB15 TB5 TB15 “S” 0,75 10 , 1,25 “MA” “1” “2” TB15 M1 M2 M1 M2 M1 M2 “MA”. ( 9 - 13 “MA”) “M-NET” “M1” “M2” “M-NET”. ( 24 - 30 “M-NET”) CN90 TB15...
  • Page 26 7.1. 500- 7.2. 7.2.1. (Fig. 7-1) Fig. 7-1 “Test run” ( “Service” ( . (Fig. 7-2) “9999” (“9999”) “Test run” ( . (Fig. 7-3) “Test run” ( . (Fig. 7-4) Service menu Test run menu Test run Test run Enter maintenance password Input maintenance info.
  • Page 27 “Cool” ( “Heat” Test run Remain Remain ). (Fig. 7-5) Pipe Cool Auto Switch disp. Mode Vane F1 F2 . (Fig. 7-6) “Test run” ( Fig. 7-6 Fig. 7-5 7.2.2. (Fig. 7-7) ON/OFF ( Fig. 7-7 FAN ( ), DRY ( AUTO...
  • Page 28 Travellers Lane, Hat eld, Herts., AL10 8XB, England, U.K. Polish Branch Krakowska 50, PL-32-083 Balice, Poland MITSUBISHI ELECTRIC TURKEY ELEKTR K ÜRÜNLERI A. . erifali Mah. Kale Sok. No: 41 34775 Ümraniye, stanbul / Turkey MITSUBISHI ELECTRIC (RUSSIA) LLC 52, bld.1 Kosmodamianskaya Nab. 115054, Moscow, Russia Please be sure to put the contact address/telephone number on this manual before handing it to the customer.

Table of Contents