Pipe Sizing for ARUN Series Heat Pump Systems ......120 Pipe Sizing for ARUB Series Heat Recovery Systems ....124 Acronyms ....................6 LG Engineered Y-branch Kits ............127 LG Engineered Header Kits ............. 132 ..............8 LATS Calculated Refrigerant Charge ..........134 Multi V IV Heat Pump and Heat Recovery Outdoor Units..8...
Page 4
UNIT NOMENCLATURE Outdoor and Heat Recovery Units Outdoor Units (ODU) Family ARU = Multi V Outdoor Unit (Refrigerant R410A) Type N = Inverter Heat Pump B = Inverter Heat Recovery Nominal Capacity (Nominal cooling capacity in Btu/h) 072 = 72,000 192 = 192,000 312/313 = 312,000 432 = 432,000...
UNIT NOMENCLATURE Indoor Units Indoor Units (IDU) Family ARN = Multi V Indoor Unit (Refrigerant R410A) Type U = DC Inverter Heat Pump Indoor Unit Nominal Capacity 05 = 5,000 Btu/h 18 = 18,000 Btu/h 42 = 42,000 Btu/h 07 = 7,000 Btu/h 24 = 24,000 Btu/h 48 = 48,000 Btu/h 09 = 9,000 Btu/h...
Page 6
Air-Conditioning, Heating, and Refrigeration Institute LEED Leadership in Energy and Environmental Design American Society of Heating, Refrigeration, and ASHRAE LGAP LG Air Conditioner Protocol Air Conditioning Air Handling Unit Mixed Air Temperature American Wire Gauge Thousands BTUs per hour BLDC...
PRODUCT DATA Mechanical Specifications on page 8 General Data on page 10 Electrical Data on page 31 Outdoor Unit Dimensions on page 35 Heat Recovery Unit Dimensions on page 41 Wiring Diagrams—Outdoor Units on page 44 Refrigerant Flow Diagrams on page 60 Acoustic Data on page 89 Outdoor Unit Accessories on page 97 Indoor Unit Quick Reference on page 102...
Headers, and having integrated controls. bonderized and finished with a baked enamel paint. Each frame has a removable An LG Multi V IV Heat pump system is a inspection panel to allow access to service VRF system that can operate in either cool-...
Page 9
MECHANICAL SPECIFICATIONS Multi V IV Outdoor Units / Multi V Heat Recovery Units Fans and Motors Controls All outdoor unit frames <80MBh include one direct drive, variable Heat pump and heat recovery outdoor units are factory wired with speed propeller type fan. All outdoor unit frames >80MBh include two necessary electrical control components, integral microprocessors, direct drives, variable speed propeller type fans.
59ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB). Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
Page 11
59ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB). Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
Page 12
59ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB). Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
Page 13
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Page 14
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Page 15
59ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB). Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
Page 16
59ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB). Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
Page 17
59ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB). Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
Page 18
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Page 19
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Page 20
59ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB). Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
Page 21
59ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB). Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
Page 22
59ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB). Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
Page 23
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG 59ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
Page 24
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Page 25
59ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB). Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
Page 26
59ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB). Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
Page 27
59ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB). Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
Page 28
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG 59ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
Page 29
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Page 30
GENERAL DATA Figure 1: Two-Port Heat Recovery Unit. Figure 2: Three-Port Heat Recovery Unit. Figure 3: Four-Port Heat Recovery Unit. Heat recovery units can only be used with LG heat recovery systems. Table 21: Model PRHR022A PRHR032A PRHR042A Number of Ports Max.
REFRIGERANT FLOW DIAGRAMS Cooling Mode Indoor Heat Exchanger Indoor Heat Exchanger Electronic Electronic Expansion Valve Expansion Valve High Temperature High Pressure Vapor High Temperature High Pressure Liquid Outdoor Temperature Low Temperature Low Pressure Vapor Sensor Charging Port High Pressure Pressure Vapor Pipe Sensor Switch...
Page 61
REFRIGERANT FLOW DIAGRAMS Heating Mode Indoor Heat Exchanger Indoor Heat Exchanger Electronic Electronic Expansion Valve Expansion Valve High Temperature High Pressure Vapor High Temperature High Pressure Liquid Outdoor Temperature Low Temperature Low Pressure Vapor Sensor Charging Port High Pressure Pressure Vapor Pipe Sensor Switch...
Page 62
REFRIGERANT FLOW DIAGRAMS Oil Return and Defrost Operation Indoor Heat Exchanger Indoor Heat Exchanger Electronic Electronic Expansion Valve Expansion Valve High Temperature High Pressure Vapor High Temperature High Pressure Liquid Outdoor Temperature Low Temperature Low Pressure Vapor Sensor Charging Port High Pressure Pressure Vapor Pipe...
Page 63
REFRIGERANT FLOW DIAGRAMS Indoor Heat Exchanger Indoor Heat Exchanger Electronic Electronic Expansion Valve Expansion Valve High Temperature High Pressure Vapor High Temperature High Pressure Liquid Outdoor Temperature Low Temperature Low Pressure Vapor Sensor For 8/10 ton Charging Port High Pressure Pressure Vapor Pipe Sensor...
Page 64
REFRIGERANT FLOW DIAGRAMS Indoor Heat Exchanger Indoor Heat Exchanger Electronic Electronic Expansion Valve Expansion Valve High Temperature High Pressure Vapor High Temperature High Pressure Liquid Outdoor Temperature Low Temperature Low Pressure Vapor Sensor For 8/10 ton Charging Port High Pressure Pressure Vapor Pipe Sensor...
Page 65
REFRIGERANT FLOW DIAGRAMS Cooling Mode Indoor Heat Exchanger Indoor Heat Exchanger Electronic Electronic Expansion Valve Expansion Valve High Temperature High Pressure Vapor High Temperature High Pressure Liquid Outdoor Low Temperature Low Pressure Vapor Temperature Sensor Charging Port High Pressure Pressure Vapor Pipe Sensor Switch...
Page 66
REFRIGERANT FLOW DIAGRAMS Heating Mode Indoor Heat Exchanger Indoor Heat Exchanger Electronic Electronic Expansion Valve Expansion Valve High Temperature High Pressure Vapor High Temperature High Pressure Liquid Outdoor Temperature Low Temperature Low Pressure Vapor Sensor Charging Port High Pressure Pressure Sensor Switch Vapor Pipe...
Page 67
REFRIGERANT FLOW DIAGRAMS Oil Return and Defrost Operation Indoor Heat Exchanger Indoor Heat Exchanger Electronic Electronic Expansion Valve Expansion Valve High Temperature High Pressure Vapor High Temperature High Pressure Liquid Outdoor Low Temperature Low Pressure Vapor Temperature Sensor Charging Port High Pressure Pressure Vapor Pipe...
Page 68
REFRIGERANT FLOW DIAGRAMS Operation Indoor Heat Exchanger Indoor Heat Exchanger Electronic Electronic Expansion Valve Expansion Valve High Temperature High Pressure Vapor Outdoor High Temperature High Pressure Liquid Temperature Low Temperature Low Pressure Vapor Sensor Charging Port High Pressure Pressure Sensor Switch Vapor Pipe Liquid Pipe...
Page 69
REFRIGERANT FLOW DIAGRAMS Operation Indoor Heat Exchanger Indoor Heat Exchanger Electronic Electronic Expansion Valve Expansion Valve High Temperature High Pressure Vapor High Temperature High Pressure Liquid Outdoor Low Temperature Low Pressure Vapor Temperature Sensor Charging Port High Pressure Pressure Active Path Sensor Switch Vapor Pipe...
Page 70
REFRIGERANT FLOW DIAGRAMS Cooling Mode Indoor HEX Indoor Unit Heat Recovery Unit Indoor HEX Indoor Unit Indoor HEX Indoor Unit Indoor HEX Indoor Unit High Temperature High Pressure Vapor High Temperature High Pressure Liquid Outdoor Temperature Low Temperature Low Pressure Vapor Sensor High Pressure Vapor Pipe High Pressure...
Page 71
REFRIGERANT FLOW DIAGRAMS Cooling at Low Ambient Temperatures Indoor HEX Indoor Uni t Heat Recovery Unit Indoor HEX Indoor Uni t Indoor HEX Indoor Uni t Indoor HEX Indoor Uni t High Temperature High Pressure Vapor High Temperature High Pressure Liquid Outdoor Temperature Low Temperature Low Pressure Vapor...
Page 72
REFRIGERANT FLOW DIAGRAMS Heating Mode Indoor HEX Indoor Uni t Heat Recover Unit Indoor HEX Indoor Uni t Indoor HEX Indoor Uni t Indoor HEX Indoor Uni t High Temperature High Pressure Vapor High Temperature High Pressure Liquid Outdoor Temperature Low Temperature Low Pressure Vapor Sensor High Pressure...
Page 73
REFRIGERANT FLOW DIAGRAMS Oil Return and Defrost Operation Indoor HEX Indoor Unit Heat Recovery Unit Indoor HEX Indoor Unit Indoor HEX Indoor Unit Indoor HEX Indoor Unit High Temperature High Pressure Vapor High Temperature High Pressure Liquid Outdoor Temperature Low Temperature Low Pressure Vapor Sensor High Pressure Pressure...
Page 74
REFRIGERANT FLOW DIAGRAMS Cooling-based Simultaneous Operation Indoor Unit Heat Recovery Unit Indoor HEX Indoor Unit Indoor HEX Indoor Unit Indoor HEX Indoor Unit High Temperature High Pressure Vapor High Temperature High Pressure Liquid Outdoor Temperature Low Temperature Low Pressure Vapor Sensor High Pressure Pressure...
Page 75
REFRIGERANT FLOW DIAGRAMS Heating-based Simultaneous Operation Indoor HEX Indoor Unit Heat Recovery Unit Indoor HEX Indoor Unit Indoor HEX Indoor Unit Indoor HEX Indoor Unit High Temperature High Pressure Vapor High Temperature High Pressure Liquid Outdoor Temperature Low Temperature Low Pressure Vapor Sensor High Pressure Pressure...
Page 76
REFRIGERANT FLOW DIAGRAMS Balanced Simultaneous Operation Indoor HEX Indoor Uni t Heat Recovery Unit Indoor HEX Indoor Uni t Indoor HEX Indoor Uni t Indoor HEX Indoor Uni t High Temperature High Pressure Vapor High Temperature High Pressure Liquid Outdoor Temperature Low Temperature Low Pressure Vapor Sensor...
Page 77
REFRIGERANT FLOW DIAGRAMS Indoor HEX Indoor Uni t Heat Recovery Unit Indoor HEX Indoor Uni t Indoor HEX Indoor Uni t Indoor HEX Indoor Uni t High Temperature High Pressure Vapor High Temperature High Pressure Liquid Outdoor Temperature Low Temperature Low Pressure Vapor Sensor High Pressure Pressure...
Page 78
REFRIGERANT FLOW DIAGRAMS Indoor HEX Indoor Unit Heat Recovery Unit Indoor HEX Indoor Unit Indoor HEX Indoor Unit Indoor HEX Indoor Unit High Temperature High Pressure Vapor High Temperature High Pressure Liquid Outdoor Temperature Low Temperature Low Pressure Vapor Sensor High Pressure Pressure High Pressure Vapor Pipe...
Page 79
REFRIGERANT FLOW DIAGRAMS Cooling Mode Indoor HEX Indoor Unit Heat Recovery Unit Indoor HEX Indoor Unit Indoor HEX Indoor Unit Indoor HEX Indoor Unit High Temperature High Pressure Gas High Temperature High Pressure Liquid Outdoor Low Temperature Low Pressure Gas Temperature Fa n Sensor...
Page 80
REFRIGERANT FLOW DIAGRAMS Cooling at Low Ambient Temp. Indoor HEX Indoor Unit Heat Recovery Unit Indoor HEX Indoor Unit Indoor HEX Indoor Unit Indoor HEX Indoor Unit High Temperature High Pressure Vapor High Temperature High Pressure Liquid Outdoor Low Temperature Low Pressure Vapor Temperature Sensor High Pressure...
Page 81
REFRIGERANT FLOW DIAGRAMS Heating Mode Indoor HEX Indoor Unit Heat Recovery Unit Indoor HEX Indoor Unit Indoor HEX Indoor Unit Indoor HEX Indoor Unit High Temperature High Pressure Vapor High Temperature High Pressure Liquid Outdoor Low Temperature Low Pressure Vapor Temperature Sensor High Pressure...
Page 82
REFRIGERANT FLOW DIAGRAMS Oil Return and Defrost Operation Indoor HEX Indoor HEX Indoor Unit Indoor Uni Heat Recovery Unit Indoor HEX Indoor HEX Indoor Unit Indoor Uni Indoor HEX Indoor HEX Indoor Uni Indoor Unit Indoor HEX Indoor HEX Indoor Uni Indoor Unit High Temperature High Pressure Vapor High Temperature High Pressure Liquid...
Page 83
REFRIGERANT FLOW DIAGRAMS Cooling-based Simul. Operation Indoor HEX Indoor Unit Heat Recovery Unit Indoor HEX Indoor Unit Indoor HEX Indoor Unit Indoor HEX Indoor Unit High Temperature High Pressure Gas High Temperature High Pressure Liquid Outdoor Outdoor Low Temperature Low Pressure Gas Temperature Temperature Sensor...
Page 84
REFRIGERANT FLOW DIAGRAMS Heating-based Simul. Operation Indoor HEX Indoor Unit Heat Recovery Unit Indoor HEX Indoor Unit Indoor HEX Indoor Unit Indoor HEX Indoor Unit High Temperature High Pressure Vapor High Temperature High Pressure Liquid Outdoor Temperature Low Temperature Low Pressure Vapor Sensor High Pressure Pressure...
Page 85
REFRIGERANT FLOW DIAGRAMS Balanced Simul. Operation Indoor HEX Indoor Unit Heat Recovery Unit Indoor HEX Indoor Unit Indoor HEX Indoor Unit Indoor HEX Indoor Unit High Temperature High Pressure Vapor High Temperature High Pressure Liquid Outdoor Low Temperature Low Pressure Vapor Temperature Sensor High Pressure...
Page 86
REFRIGERANT FLOW DIAGRAMS Operation Indoor HEX Indoor Unit Heat Recovery Unit Indoor HEX Indoor Unit Indoor HEX Indoor Unit Indoor HEX Indoor Unit High Temperature High Pressure Vapor High Temperature High Pressure Liquid Outdoor Low Temperature Low Pressure Vapor Temperature Sensor High Pressure Pressure...
Page 87
REFRIGERANT FLOW DIAGRAMS Operation Indoor HEX Indoor HEX Indoor Uni HR unit HR unit Indoor HEX Indoor HEX Indoor Unit Indoor HEX Indoor HEX Indoor Unit Indoor HEX Indoor HEX Indoor Unit High Temperature High Pressure Vapor High High mperature High Pressure Liquid High Te Outdoor Outdoor...
Page 88
REFRIGERANT FLOW DIAGRAMS A : Switch operation between cooling and heating. B : Decreases noise following subcooling operation between inlet of one indoor unit and outlet of another indoor unit during simultaneous operation. C : Prevents liquid from entering high-pressure vapor valve and heat recovery unit during cooling mode. D : Controls pressure between the high and low pressure vapor pipes during simultaneous operation.
Page 93
ACOUSTIC DATA Sound Power Levels • Data is valid under diffuse field conditions. • Data is valid under nominal operating conditions. ARUN145BTE4/ARUN145DTE4, ARUB145BTE4/ARUB145DTE4, • Sound level may be increased in static pressure mode or if air ARUN169BTE4/ARUN169DTE4, ARUB169BTE4/ARUB169DTE4 guide is used. frames are ONLY for use in large capacity triple frame combina- •...
ARUB096BTE4, ARUB096DTE4, ARUB121BTE4, ARUB121DTE4, ARUB144BTE4, ARUB144DTE4, ARUB145BTE4, ARUB145DTE4, ARUB168BTE4, ARUB168DTE4, ARUB169BTE4, ARUB169DTE4 See submittals at www.lg-vrf.com to verify how many kits are needed for each combination frame. ARUN145BTE4-DTE4 / ARUB145BTE4-DTE4, ARUN169BTE4-DTE4 / ARUB169BTE4-DTE4 frames are ONLY for use in large capacity triple frame combinations.
Page 98
ARUB096BTE4, ARUB096DTE4, ARUB121BTE4, ARUB121DTE4, ARUB144BTE4, ARUB144DTE4, ARUB145BTE4, ARUB145DTE4, ARUB168BTE4, ARUB168DTE4, ARUB169BTE4, ARUB169DTE4 See submittals at www.lg-vrf.com to verify how many kits are needed for each combination frame. ARUN145BTE4-DTE4 / ARUB145BTE4-DTE4, ARUN169BTE4- DTE4 / ARUB169BTE4-DTE4 frames are ONLY for use in large capacity triple frame combinations.
Page 99
IDU, user will not be able to record data. This software can be used to both commission new systems and troubleshoot existing systems. LGMV data can be recorded to a “.CSV” file and emailed to an LG representative to assist with diagnostic evaluations. Recommended Minimum PC Configuration: •...
® To ensure that the refrigerant piping design meets LG’s quality standards, a LATS refrigerant piping design must be provided with every Multi V order. Following the installation, if any changes or variations to the design are necessary, a new LATS file must be created and provided to LG prior to system commissioning to ensure the proper pipe size has not changed.
Page 103
V Piping Design software works when designing a Multi V HVAC In many buildings, to optimize system design, spaces on opposite system. It should not replace the use of LG’s LATS Multi V sides of the building are combined on a single pipe system served by complimentary selection software, but should instead be used in a common Multi V IV Heat Recovery outdoor unit.
Page 104
LATS . (For correction factors, see the separate ambient conditions are outside the cataloged range. Multi V IV Performance Data Manual on www.lg-vrf.com.) Select the Indoor Unit(s) Altitude Correction...
Page 105
If the corrected cooling capacity was found using corrected capacity tables found in the separate Heating Peak Load Multi V IV Performance Data Manual on www.lg-vrf.com, apply the CCR% appropriate elevation difference factor also found in the Performance...
Page 106
In some designs, over-sized indoor units may be unavoidable in the properly sized and the system’s performance should now be case where the smallest size indoor unit available from LG is larger optimized. The VRF system component size selections should be than what is necessary to satisfy the space load.
LG Electronics, U.S.A., Inc., In all cases, the designer, installer, and contractor should understand if the suggested method is used, it is used at their own risk. LG Electronics U.S.A., Inc., takes no responsibility and offers no warranty, expressed or implied, in law or in •...
Page 108
• Motorized dampers may be required to prevent outdoor air flow through the indoor unit when the indoor unit is not operating. • An LG Dry Contact adapter may be necessary to interlock the motorized damper with the indoor unit.
Page 109
• Motorized dampers may be required to prevent outdoor air from entering the indoor unit while the indoor unit has cycled off. • An LG Dry Contact adapter is necessary to interlock the motorized damper with the indoor unit fan operation.
PLACEMENT CONSIDERATIONS Outdoor Units Selecting the Best Location—Outdoor Units Select a location for installing the outdoor unit that will meet the following conditions: • Where the unit will not be subjected to direct thermal radiation from other heat sources. • Where operating sound from the unit will not disturb inhabitants of surrounding buildings. •...
PLACEMENT CONSIDERATIONS Outdoor Units Figure 11: Outdoor Unit—Mounting Methods General Mounting Securely attach the outdoor unit to a condenser pad, base rails, or other mounting platform that is securely anchored to the ground or building structure. Refer to dimensional drawings in the “Product Data”...
PLACEMENT CONSIDERATIONS Outdoor Units Installation Space Proper airflow through the outdoor unit coil is critical for proper unit operation. When installing the outdoor unit, consider service, inlet, and outlet, and minimum allowable space requirements as illustrated in the diagrams below. Figure 12: Minimum Space Requirements.
Page 113
Installing Outdoor Units Indoors LG Multi V outdoor units are engineered to be mounted outdoors and include technology designed to minimize the negative effects of winter weather’s freezing rain, sleet, and snow. Some building projects, however, necessitate placing the HVAC outdoor units indoors: •...
Page 114
For more detailed information on how to design indoor spaces for LG Multi V outdoor units, see the white paper "Air-Source VRF Mechanical Room Design Considerations for Outdoor Unit Placement in Enclosures"...
• Ensure there is enough space in the installation area for service access. • Refrigerant pipes must not exceed lengths specified by LG Electronics. • Do not install the heat recovery unit in a location where it would be subjected to strong radiation heat from heat sources.
Page 116
PLACEMENT CONSIDERATIONS Heat Recovery Units Figure 15: Heat Recovery Unit Types. PRHR022A (Two [2] ports) PRHR032A (Three [3] ports) PRHR042A (Four [4] ports) 1. Each heat recovery unit has a capacity up to 192,000 Btu/h. 2. Heat recovery units connected in series have a total capacity up to 192,000 Btu/h per series string. Series string is defined as heat recovery units piped in series.
Page 117
Pipe Sizing for ARUN Series Heat Pump Systems on page 120 Pipe Sizing for ARUB Series Heat Recovery Systems on page 124 LG Engineered Y-branch Kits on page 127 LG Engineered Header Kits on page 132 LATS Calculated Refrigerant Charge on page 134...
Page 118
Piping Design Guideline Summary The proper design and installation of the refrigerant piping system is a critical element of a Multi V system. As detailed on page 102, LG provides engineers LG Air Conditioner Technical Solution (LATS) software to help design LG Multi V air conditioning systems. The following pages are examples of manual pipe size calculations for Multi V refrigerant piping systems.
Page 119
REFRIGERANT PIPING DESIGN Piping Design Guideline Summary Figure 16: Typical VRF Heat Pump System Building Layout Listing the Figure 17: Typical VRF Heat Recovery System Building Layout Listing Piping Limitations. the Piping Limitations.. Elevation Differential Two IDUs Connected to One HRU: 49' Max.
Page 120
REFRIGERANT PIPING DESIGN Piping Design Guideline Summary Pipe Sizing for ARUN Series Heat Pump Systems Figure 18: Heat Pump Triple-Frame Connections. Slave2 Slave1 Master ARCNN21 and ARCNN31 Outdoor Unit Connector Pipe Accessories D (main pipe ARCNN21 sized by LATS) To Indoor Units (Multi-frame Outdoor Unit Y-branch Connector) ARCNN31...
Page 121
REFRIGERANT PIPING DESIGN Piping Design Guideline Summary The following is an example of manual pipe size calculations. Designers are highly encouraged to use LATS instead of manual calculations. Y-branch Pipe Sizing When Installing a Triple-Frame System Example: Five (5) indoor units connected Slave2 ODU ODU: Outdoor Units.
Page 122
REFRIGERANT PIPING DESIGN Piping Design Guideline Summary The following is an example of manual pipe size calculations. Designers are highly encouraged to use LATS instead of manual calculations. Combination Y-branch Pipe and Header Pipe Sizing When Installing a Dual- Frame System Example: Five (5) indoor units connected Slave ODU ODU: Outdoor Units.
Page 123
REFRIGERANT PIPING DESIGN Piping Design Guideline Summary The following is an example of manual pipe size calculations. Designers are highly encouraged to use LATS instead of manual calculations. Table 37: Pipe Capabilities. Total pipe length Longest actual pipe length Equivalent pipe length Length Longest pipe length after first branch Elevation1...
REFRIGERANT PIPING DESIGN Piping Design Guideline Summary The following is an example of manual pipe size calculations. Designers are highly encouraged to use LATS instead of manual calculations. Pipe Sizing for ARUB Series Heat Recovery Systems Figure 19: Heat Recovery Triple-Frame Connections. Slave2 Slave1 Master...
Page 125
REFRIGERANT PIPING DESIGN Piping Design Guideline Summary The following is an example of manual pipe size calculations. Designers are highly encouraged to use LATS instead of manual calculations. Pipe Sizing for ARUB Series Heat Recovery Systems Example: Triple-frame system, four (4) heat recovery units, Slave2 Slave1 one (1) header, and twelve (12) indoor units connected...
Page 126
REFRIGERANT PIPING DESIGN Piping Design Guideline Summary The following is an example of manual pipe size calculations. Designers are highly encouraged to use LATS instead of manual calculations. Table 40: Refrigerant Pipe (B) Diameter between Y-branches and Y-branches / Heat Recovery Unit / Headers. Vapor pipe (inches OD) Downstream IDU total capacity (Btu/h) Liquid pipe (inches OD)
Page 127
Y-Branch Kits LG Y-branch and kits are highly engineered devices designed to evenly divide the flow of refrigerant, and are used to join one pipe segment to two or more segments. There are two types of Y-branches used in LG VRF systems: Y-branches that combine two or three outdoor units to make up one large-capacity outdoor unit (also known as multi-frame connectors), or Y-branches used with the indoor units in the refriger- ant piping system at each transition.
Page 128
REFRIGERANT PIPING DESIGN Indoor Unit Y-branches for ARUN Series Heat Pump Systems Unit: Inch Vapor pipe Liquid pipe Models I.D. 1/2 I.D. 3/8 I.D. 1/4 I.D. 1/2 I.D. 1/4 I.D. 3/8 I.D. 5/8 I.D. 5/8 I.D. 5/8 2-15/16 I.D. 1/4 2-15/16 I.D.
Page 129
REFRIGERANT PIPING DESIGN Indoor Unit Y-branches for ARUB Series Heat Recovery Units Unit: Inch Models Low-Pressure Vapor Pipe Liquid pipe High-Pressure Vapor Pipe I.D. 3/8 I.D. 1/2 I.D. 3/8 I.D. 1/2 I.D. 1/4 I.D. 1/2 I.D. 5/8 I.D. 1/4 I.D. 3/8 I.D.
Page 130
REFRIGERANT PIPING DESIGN Outdoor Unit Y-branches for ARUN Series Heat Pump Systems For Dual-Frame Heat Pump Systems Unit: inch Multi-Frame Combination Vapor pipe Liquid pipe Connector 16-3/8 13-1/16 16-1/16 12-3/8 I.D. 1-1/8 I.D. 1-1/8 I.D. 5/8 I.D. 5/8 I.D. 1/2 3-5/16 I.D.
Page 131
REFRIGERANT PIPING DESIGN Outdoor Unit Y-branches for ARUB Series Heat Recovery Units For Dual-Frame Heat Recovery Systems Unit: inch Multi-Frame Combination specification Low-Pressure Vapor Pipe Liquid Pipe High-Pressure Vapor Pipe Connector I.D.1-1/4 13-1/16 16-3/8 I.D.1-3/8 I.D. 1-1/8 I.D. 1 I.D. 1-1/4 12-3/8 I.D.
Page 132
Figure 24: Header Kit—Horizontal Rotation Limit (Must be Installed Level with No Rotation). Header Kits LG Header kits are highly engineered devices designed to evenly divide the flow of refrigerant, and Largest IDU...
Page 134
Consider refrigerant safety in all designs. LG Multi V IV outdoor units ship from the factory with a charge of R410A refrigerant. This charge serves as the base charge and will not be sufficient for the system to operate. A trim charge will need to be added after the system is installed that is based on system design. LATS Multi V piping design software will calculate the size of the refrigerant piping and calculate the refrigerant charge;...
Page 135
REFRIGERANT PIPING DESIGN Figure 26: LATS Tree Diagram for Multi V IV Heat Recovery System Test Update System No: 1/1 Example. Determining the Total System Charge (Refer to Table 49) 1. Using the LATS Tree diagram, document the linear feet of straight liquid piping and the quantity and type of each fitting by pipe diameter into System Refrigerant Charge Calculator.
Page 136
REFRIGERANT PIPING DESIGN Table 49: System Refrigerant Charge Calculator (lbs.). Job Name_______________________________________ Project Manager__________________________________ System Tag or ID____________________________________ Date___________________________________________ Line # Description Chassis I.D. Size Quantity CF (Ref.) Total (lbs.) Linear feet of 1/4" liquid line tubing — — 0.015 Linear feet of 3/8"...
Page 137
LG recommends soft copper use to be limited to 1/2". Use hard drawn for larger sizes to avoid sags and kinks that lead to oil trapping. Table 51: ACR Rated Piping Tube Thicknesses.
Page 138
LAYOUT BEST PRACTICES Selecting Field-Supplied Copper Tubing Table 52: Linear Thermal Expansion of Copper Tubing in Inches. Fluid Temperature °F Pipe Length 35° 40° 45° 50° 55° 60° 65° 70° 75° 80° 85° 90° 95° 100° 105° 110° 115° 120° 125° 130° 0.04 0.04 0.05...
Page 139
LAYOUT BEST PRACTICES Selecting Field-Supplied Copper Tubing Figure 27: Coiled Expansion Loops and Offsets (Plan View). Large Tubing U-bend (>3/4 in.) Loop Small Tubing U-bend (<3/4 in.) Table 53: Radii of Coiled Expansion Loops and Developed Lengths of Expansion Offsets. Anticipated Linear Nominal Tube Size (OD) inches Expansion (LE) (inches)
Page 140
Field-Provided Isolation Ball Valves LG maintains a neutral position on using isolation valves in VRF refrigerant piping systems. LG does not endorse any manufacturer of isola- tion valves. It is recognized that installing isolation valves may simplify future maintenance requirements, and, if used, considerations should be taken including, but not limited to, the following: •...
Page 141
LAYOUT BEST PRACTICES General Information / Guidelines No Pipe Size Substitutions Use only the pipe size selected by the LATS Multi V pipe system design software. Using a different size is prohibited and may result in a system malfunction or failure to work at all. Pipe Supports Figure 29: Pipe Hanger Details.
Page 142
Pipe Sleeves at Penetrations LG requires that all pipe penetrations through walls, floors, and pipes buried underground be properly insulated and routed through an appropriate wall sleeve of sufficient size to prevent compression of refrigerant pipe insulation and promote free movement of the pipe within the sleeve.
LAYOUT BEST PRACTICES General Information / Guidelines Refrigerant Piping for Separated Outdoor Units Dual-frame and triple-frame systems should be installed with all outdoor units located next to each other. In conditions where the dual-frame or triple-frame outdoor units need to be separated, the following rules must be followed: Figure 36: Y-branch Measurement Location.
Page 144
LAYOUT BEST PRACTICES General Information / Guidelines 2. Inverted traps are required when: Figure 41: Examples of Inverted Traps. a. Piping in a horizontal direction from the outdoor Y-branch towards an out- door unit or another outdoor unit Y-branch is greater than 6.6'. The inverted trap should be installed close to the outdoor unit Y-branch (no To IDUs / HRUs more than 6.6' away).
Page 145
LAYOUT BEST PRACTICES General Information / Guidelines Refrigerant Piping Installation Proper system operation depends on the installer using best practices and utmost care while assembling the piping system as one of the main causes of refrigerant leaks is defective connections. For VRF systems, the installer needs to know how perform both flared and brazed connections successfully.
Page 146
Mark all pipes at the point where the insulation jacket ends. Remove the jacket. Install field provided insulation on the run-out and main trunk pipes first. Install the LG-provided insulation plugs on the ends of all unused header ports. Peel the adhesive glue protector slip from the insulation jacket and install the clam-shell jacket over the fitting.
ELECTRICAL CONNECTIONS ARUN Series Heat Pump Systems on page 148 ARUB Series Heat Recovery Systems on page 149 DIP Switch Settings for Gen4 Equipment on page 150...
Page 148
ARUN SERIES HEAT PUMP SYSTEMS Figure 45: Typical Multi V IV Heat Pump VRF System Power and Communications Wiring Schematic. 3 Phase 3 Wires Power supply 60Hz 208-230V or Master Slave1 Slave2 60Hz 460V Main Switch R(L1) S(L2) T(L3) R(L1) S(L2) T(L3) R(L1) S(L2) T(L3) Switch Switch...
Page 149
ARUB SERIES HEAT RECOVERY SYSTEMS Figure 46: Typical Multi V IV Heat Recovery VRF System Power and Communications Wiring Schematic. 3 Phase 3 Wires Power supply 60Hz 208-230V or Master Slave1 Slave2 60Hz 460V R( L 1) S( L 2) T( L 3 ( L 1) S( L 2) T( L 3 ( L 1) S( L 2) T( L 3) Main Switch...
Generation 4 Equipment The latest versions of LG’s indoor units and outdoor (air / water source) units are designated Generation 4 (Gen 4). For Gen 4 units to oper- ate with Gen 4 features, the air conditioning system must meet the following requirements: •...
Page 152
ISO 9001: 2008 LG ELECTRONICS INC. LG Electronics, U.S.A., Inc. EM_MultiVIV_OutdoorUnits_04_16 Commercial Air Conditioning Division Supersedes: EM_MultiVIV_OutdoorUnits_09_15 4300 North Point Parkway EM_MultiVIV_OutdoorUnits_06_15 Alpharetta, Georgia 30022 EM-MultiVIV-OutdoorUnits-05-15 www.lg-vrf.com LG Electronics Commercial Products Support 1-888-865-3026 USA Follow the prompts for commercial A/C products.