Chapter 6 - Parameter Description [I/O]
I/O-50: Auto (Sequence) Operation
I/O-51: Sequence Number Selection (Seq #)
I/O-52: The Number of Steps of Sequence #
I/O?
Auto mode
50
None
Factory Default:
None
There are two modes of ' Auto-A' and ' Auto-B' in Auto
mode. Auto operation is activated by the multi-function
input terminals set to [SEQ-L], [SEQ-M], [SEQ-H] and
[Go step] in I/O-12 ~ I/O-14.
I/O? Seq select
51
3
Factory Default:
1
This code selects the sequence to set frequency,
transient time, steady speed time and motor direction the
steps.
I/O? Step number
52
2
Factory Default:
2
This code sets the number of steps to use for the
sequence number selected in I/O-51.
[Auto -A]
This mode will allow the inverter to operate automatically
followed by its pre-programmed sequence. According to
this sequence, eight different steps of Frequency,
Transient Time, Steady Speed time and Motor Direction
can be initiated with only a single multi-function input
contact closure (I/O-12 ~ I/O-14). The sequence and
steps are set in I/O-51 ~ I/O-84.
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
50
0
0
51
1
1
52
2
2
134
Step
Parameter
Frequency
Code
Sequence 1
Sequence 2
I/O-50 ~
Sequence 3
I/O-84
Sequence 4
Sequence 5
0: OFF, 1: ON
Output Frequency
2D
(Forward)
Seq1 / 2F
1D
(Forward)
Seq1 / 1F
Seq1 / 3F
1T
1S
2T
2S
P1-CM
ON
' SEQ-L'
[Example 1 of ' Auto-A' operation]
Output Frequency
Sequence 1
Sequence 3
SEQ1 / 2F
SEQ2 / 2F
SEQ1 / 1F
SEQ3 / 2F
SEQ3 / 1F
P1-CM
ON
' SEQ-L'
P2-CM
' SEQ-M'
[Example 2 of ' Auto-A' operation]
Speed-H
Speed-M
Speed-L
(P3)
(P2)
(P1)
0
0
1
0
1
0
1
0
0
0
1
1
1
0
1
Time
3D
(Reverse)
3T
3S
Time
Sequence 2
Time
Time
ON
Time