ABB
Motor Protection
REM610
Product version: C
Table 16. Electromagnetic compatibility tests
Description
EMC immunity test level meets the requirements listed below
1 MHz burst disturbance test,
class III
• Common mode
• Differential mode
Electrostatic discharge test,
class IV
• For contact discharge
• For air discharge
Radio frequency interference
tests
• Conducted, common mode
• Radiated, amplitude-
modulated
• Radiated, pulse-modulated
Fast transient disturbance
tests
• Power outputs, energizing
inputs, power supply
• I/O ports
Surge immunity test
• Power outputs, energizing
inputs, power supply
• I/O ports
Power frequency (50 Hz)
magnetic field
Power frequency immunity
test:
Type test value
2.5 kV
1.0 kV
8 kV
15 kV
10 V (rms), f = 150 kHz...80
MHz
10 V/m (rms), f = 80...2700
MHz
10 V/m, f = 900 MHz
4 kV
2 kV
4 kV, line-to-earth
2 kV, line-to-line
2 kV, line-to earth
1 kV, line-to-line
300 A/m continuous
1MRS756304 C
Issued: 30.10.2009
Reference
IEC 60255-22-1, IEC
61000-4-18
IEC 61000-4-2, IEC
60255-22-2 and ANSI
C37.90.3-2001
IEC 61000-4-6 and IEC
60255-22-6
IEC 61000-4-3 and IEC
60255-22-3
ENV 50204 and IEC
60255-22-3
IEC 60255-22-4 and IEC
61000-4-4
IEC 61000-4-5 and IEC
60255-22-5
IEC 6100-4-8
IEC 60255-22-7 and IEC
61000-4-16
17