GOOSE function blocks

GOOSE function blocks are used for connecting incoming GOOSE data to
application. They support BOOLEAN, Dbpos, Enum, FLOAT32, INT8 and INT32
data types.
Common signals
The VALID output indicates the validity of received GOOSE data, which means in
case of valid, that the GOOSE communication is working and received data quality
bits (if configured) indicate good process data. Invalid status is caused either by
bad data quality bits or GOOSE communication failure. See IEC 61850
engineering guide for details.
The OUT output passes the received GOOSE value for the application. Default
value (0) is used if VALID output indicates invalid status. The IN input is defined
in the GOOSE configuration and can always be seen in SMT sheet.
Settings
The GOOSE function blocks do not have any parameters available in LHMI or
PCM600.

GOOSERCV_BIN function block

Function block

GUID-44EF4D6E-7389-455C-BDE5-B127678E2CBC V1 EN
Figure 30:
Function block
Values (Range)
Unit
0=normal
1=high
2=low
3=high-high
4=low-low
-10000.0...10000
.0
0=normal
1=high
2=low
3=high-high
4=low-low
Section 3
Basic functions
Description
RTD input, Connectors
15-16-12c, range
RTD input, Connectors
17-18-12c, reported
value
RTD input, Connectors
17-18-12c, range
97