7 Application examples for configuring the controller
7.3 Configuration examples
Configuration example
to the controller
w
from the
w
controller
wi
y
Drive
x
to the controller
Please read the foreword to chapter 7.1, page 193
Setting the structure switches of the process display:
S1 = 4, process display
S2 = 2, S-controller internal
feedback
S15 = 0,
x1 = 0
S16 = 3,
x2 ! AI3
S17 = 1,
we ! AI1
S19 = 2,
yR ! AI2
S80 = 6,
Alarms A1 to A4 in the process operation
mode can be displayed and adjusted
Slot 3
Limit value
not
used
1
2
3
4
5
1
1)
for further processing e.g. in another SIPART DR controller
208
L1
Process display
Structured as a process display, the SIPART DR21 controller can display and
monitor the process variables. If the manipulated variable y and yR is structu-
red, it can be monitored to the y display and can be adjusted with the keys (7)
and (8) with the appropriate wiring. The controlled variable x can be shown in
the red analog display (1) with structuring as x2. If the limit value A1 to A4 if
referred to x with S76, S77, S80 and shown in the green bar display (2), the
relation of the variable to be monitored to the limit values can be seen at a
glance. With the parameters dA, dE (oFPA) the variables w, x, A1 to A4 can be
displayed in their right physical variable in the w/x display (3). The y display is
made in 0 to 100%. See also fig. 3-16, page 82
S42 = 2, w: int $ ext
S54 = 1, yR display
S56 = 2, w ! AO
S57 = 1, ±Δy ! DO1/2
referred
S76 = 2, A1/A2
to x
S77 = 2, A3/A4
Slot 2
Slot 1
AI4
AI3
not
Option module
used
6DR2800-8J
--
R
GND
2
3
4
1
2
3
SIPART DR21 standard controller
6DR2100-5
(AC230 V/115 V)
6DR2100-4
(UC 24 C)
AI1
AI1
AI2
AI2
DI1 DI2 DO
+
--
+
--
+
1
2
3
4
5
6
4
yR
w
+Δy --Δy
E
x2
Manual
PE
UC 24 C
N
L
PE
AC 115 V
N
AC 230 V
L
DO
L+ AO
L
--Δy
GND GND
1
2
7
8
9
10
11
12
13
14
w
+
+
--
--
+
+
I
I
--
--
SIPART DR21
C73000-B7476-C143-08
+Δy
15
1)