Page 1
SINAMICS G180 Compact inverter units, cabinet systems, air-cooled and liquid-cooled cabinet units Installation and operating instructions Edition 05/2013 Answers for industry.
Page 3
Introduction Safety information Description Preparations for use Installation and operating Installation instructions Sinamics G180 Electrical connection Operating Instructions Commissioning Operation Maintenance Spare parts and accessories Diagnostics, faults and warnings Service & Support Quality documents Technical data List of abbreviations 05/2013...
Page 4
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Presentation of the display buttons in the operating instructions..........10 Specific features..........................10 Safety information............................13 The five safety rules........................13 Use of tested, certified and Siemens-approved components............14 Areas that are potentially and particularly hazardous..............14 Notes for operator protection.......................16 Notes on water cooling:.......................19 Safety precautions when handling anti-freeze................20 Standards and guidelines for proper use of inverters..............21...
Page 6
Connecting external control voltage for compact devices............68 6.7.6 Control voltage 230 V for cabinet units..................69 Commissioning............................71 Checks without mains power supply and without motor..............71 Checks with mains power supply and without motor..............73 Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 7
Connection for optional external display with RS 485...............107 Special functions........................108 8.5.1 Protective functions........................108 8.5.2 Multiple function of the analog and digital inputs...............112 Setpoint channel and closed-loop control..................116 8.6.1 Specifying source for speed setpoint..................116 Parameterization........................116 Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 8
Replacing fans for the compact device..................133 Maintenance and service of water cooling (option)..............133 Decommissioning........................133 Spare parts and accessories........................135 10.1 Use of tested, certified and Siemens-approved components............135 10.2 Peripheral boards 1 to 4......................136 10.2.1 General information about the peripheral boards 1 to 4............136 10.2.2...
Page 9
Tightening torques for power cables..................176 Technical data of the control cable terminals................176 Technical data and identification of the PTC thermistor input at peripheral boards 2 and 4..177 Technical data of the direct water cooling.................178 Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 10
Table of contents C.10 Permissible substance values for the cooling water..............180 C.11 Threshold values for fan control system..................180 C.12 Derating.............................181 C.12.1 Current derating.........................181 C.12.2 Voltage derating........................183 List of abbreviations..........................185 Index.................................187 Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
A Note is an important item of information about the product, handling of the product or the relevant section of the document. Notes provide you with help or further suggestions/ideas. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
<arrow up_arrow up> Press the button on the control panel twice. <S+I> Press both buttons simultaneously. Display text "P-SYSTEM_DATA" Text shown in the control panel display is presented like this. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 13
Thereby "P-EXTRAS" symbolizes the main menu and "Language" the submenu. In this case, you are configuring the language in the "P-EXTRAS" menu. The display shows "P-EXTRAS" at the beginning. If you change to this menu, the display only shows "Language" Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
● Ensure that only qualified and authorized personnel perform work on the inverter. ● Always observe the five safety rules specified above whenever you are carrying out any work on the device. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Components which are not approved It is dangerous to use components which are not tested, not certified and not approved by Siemens. This can result in death, serious injury or material damage. Use only components which are tested, certified and approved by Siemens.
Page 17
Depending on parameter settings and connection of external control devices, the inverter can start up automatically when the line voltage is connected. Figure 2-1 Areas that are potentially and particularly hazardous Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
They must be properly qualified for the tasks with which they are charged. Qualified personnel must also be thoroughly familiar with all the safety-related instructions and measures described in the product documentation. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 19
Off input which safely disconnects the inverter or the motor from the line supply. Safely and reliably disconnect the power supply before opening covers or terminal boxes at the inverter. For example, use a main switch. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 20
After you have switched off the main power supply, do not touch the device or carry out any maintenance work or repair work until the discharge time of 10 minutes (5 minutes for compact devices) have elapsed. Measure the voltage once the discharge time has elapsed. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
● Protect the cooling water circuits against excess pressure, e.g. by installing a relief valve. ● Make sure that the pipework installation and pressure testing procedures comply with local safety regulations and national safety guidelines. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
In any case, consult a doctor. In addition, observe the provisions of the EC safety data sheet in accordance with 91/155/EEC, as well as the generally applicable first aid rules. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
● Careful maintenance The unit must only be used for the applications specified in the catalog and only in conjunction with devices and components recommended and approved by Siemens. Note Familiarize yourself with the local safety requirements and national safety guidelines and always observe them.
Note Siemens Service Centers The services and support provided by the Siemens service centers are recommended for planning, installation, commissioning, and servicing work. Note Engineering information Systems in which the inverters are installed must be fitted with additional monitoring and safety devices in order to comply with safety requirements (e.g.
The necessary ESD protective measures for the entire working range for electrostatically sensitive devices are illustrated once again in the following drawings. Precise instructions for ESD protective measures are specified in the standard DIN EN 61340‑5‑1. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
The plant operator is responsible for taking appropriate measures (labels and hazard warnings) to adequately protect operating personnel and others against any possible risk. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
The use of mobile telephones near the inverter when it is in operation can result in the generation of erroneous pulses and possibly give rise to physical injuries to personnel. Switch off mobile telephones when you are near the equipment. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
● Miniature fuse in accordance with EN 60127: 2 A … 6 A, slow, maximum 150 VA ● Miniature circuit-breaker: 2 A … 6 A, characteristic D, maximum 150 VA Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
3. If the inverter software is no longer current, then update the inverter software by using the software "IMS". Contact the Service Center of Siemens in Ruhstorf (Page 162) for more detailed information. Order numbers / Type designations The inverters have the following types of identification: ●...
Page 30
940 A, for example, the order number positions for the output current must be reduced. ⇒ 11th position = 3, 12th position = 8, 13th position = 8. This can mean that the order Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 31
Designation Option Meaning Device type SINAMICS G180 voltage-source DC link inverter Cabinet unit system with one or more inverters. The attainable shaft outputs of all installed inverters are added together. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 32
The other version designation of the inverter consists of the type code and seven other characters. This designation is specified on the rating plate. It is used in commercial written communication and is as follows: Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 33
With Profinet board With Profibus board With Modbus TCP-IP board Peripheral board Without peripheral board With peripheral board 1 With peripheral board 2 With peripheral board 3 With peripheral board 4 Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Consult the factory for this, for example for marine packaging. ● Never lift the compact devices at the plastic cover, but always from below according to the following diagrams. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 36
Risk of injury when lifting heavy loads Compact units, depending on the type, from frame size K3, weigh more than 30 kg. Do not try to manually lift devices more than 30 kg. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 37
Preparations for use 4.1 Transporting inverter Figure 4-1 Lifting with a crane Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Destruction of the inverters as a result of improper storage Observe the environmental conditions for storage in the technical data. The inverters will be destroyed if you store them outdoors. Store the inverters in enclosed, dry rooms. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
● Twist unshielded wires. This particularly includes analog signals of the same power circuit i.e. supply and return wires. Keep the area between supply and return wires as small as possible in order to avoid unnecessary loop antennas. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Control cable up to approx. 10 mm outside diameter ③ Signal cable You can also use EMC threaded connections instead of the metal cable ties. In this case, remove the sheet metal with the cable tie lugs. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 41
Preparations for use 4.3 EMC ① Signal cable ② Control cable ③ Motor and power supply cable Figure 4-3 EMC - wiring overview Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
You can read the radio interference class of the inverter at the version designation of the rating rate or from the order confirmation. Further information can be found in the "Type designations" (Page 27)section. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
"This is a product of category C2 acc. to EN 61800‑3. If not correctly installed and commissioned, this product can cause radio frequency interference in residential areas. In this case, it may be necessary for the company operating the unit to take corresponding measures." Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
(Page 57). ● Ensure that Ex e-motors are tested for increased safety together with the inverter at the manufacturer's factory. The system must not be operated without the test report. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 45
– In this case, loop the contact of the CALOMAT® directly into the coil circuit of the line contactor. ● Otherwise, perform the wiring of the line contactor according to the description of the main contactor function in section "Contactor functions" (Page 108). Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Take suitable measures to protect the unit against these environmental influences. Observe the specified environmental conditions in the technical data. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
All compact units have degree of protection IP20. The canopy with degree of protection IP21 is available as an accessory for all compact and compact Plus devices. The cover is 5 mm Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Foreign bodies in the cabinet If you drop washers or screws into the cabinet during installation, this can result in destruction of the device. Ensure that no washers or screws fall into the device. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Procedure Use the display in control panels or doors. Note the following dimensions for the opening: Width x Height [mm]: 138 × 92 +0.8 The degree of protection is IP54. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 51
1. Shorten the cable to the required length. 2. Connect up the cables using end sleeves as illustrated in the diagram below. Figure 5-4 Display - Installation in switch cabinet door Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 52
Installation 5.5 Installing external display Connection for external installation with maximum 1.000 meters connection cable length Figure 5-5 Display - external installation Use shielded connection cables. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
The equipment will be damaged as a result. Use special cable lugs which are designed for connecting aluminum and copper. Please contact the Siemens Service (Page 161) for advice about box terminals. Protecting the inverter When protecting the inverter a distinction must be made between the two cases.
● Instructions for correct EMC connection can be found in section "Correct EMC installation and connection" (Page 37). ● For more detailed information about control cable terminals, please refer to section "Technical data of control cable terminals" (Page 176). Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
– Determine the current of the mains power cable according to the inverter input current which you can find on the rating plate. – Use shielded mains power cables or cables with concentric protective earth conductor, type NYCWY, in order to reduce EMC interference. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
– The RCD circuit breakers used must be of type B "sensitive to all current types" with this label: 6.5.3 Connecting mains power cable to the inverter You do not need any N conductor. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Inverters with higher pulsed inputs are available for higher outputs from approx. 500 kW as they cause smaller circuit feedback on the mains power supply. Connect the inverter to the mains power supply depending on the pulse operation: Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
● Note that a motor without external ventilation will be cooled less at speeds less than the rated speed. Therefor, consult the motor manufacturer for the dimensioning of the motor. ● When using Siemens motors, refer to the list "UN03/UN04 Drehstrommotoren für drehzahlverstellbare Antriebe" to find the relevant inverter output.
● Use shielded mains power cables or cables with concentric protective earth conductor, type NYCWY, in order to comply with EMC directives. Note the information in section "Correct EMC installation and connection" (Page 37). Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
The data in the table specifies the typical cable length in the sense of the distance between the motor and the inverter when parameterizing the standard clock cycle frequency. Larger Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Connecting motor cable Connect the motor to terminals U2, V2, W2 of terminal strip -X1 of theinverter. Refer to the technical data for the correct tightening torques for the power cable connection. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
● Miniature circuit-breaker: 2 A … 6 A, characteristic D, maximum 150 VA 6.7.2 Use of external control voltage The inverter generates the control voltage from the DC link voltage in normal operation. Use external control voltage in the following cases: Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
2. Turn the two screws of the grey cover underneath by 90° and lift up the cover. 3. Undo all screws for the right-hand side panel which are visible from outside and one internal nut in the connection area. Lift off the side panel. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Preparing compact devices with frame size K4 with 400 V or 500 V This instruction applies to compact units with the frame size K4 with L x W 775 × 350 mm and 400 V or 500 V rated voltage. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Providing compact devices with the frame size K4 with 690 V This instruction applies to compact units with frame size K4 with L x W 775 × 350 mm and 690 V rated voltage. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
1. Turn the four fixing screws of the gray cover through 90° and lift up the cover. 2. Unscrew the blue cover at the screw above –X25 and lift up the cover. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
1. Turn the four fixing screws of the gray cover through 90° and lift up the cover. 2. Unscrew the blue cover at the screw above –X25 and lift up the cover. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
1. Turn the four fixing screws of the gray cover through 90° and lift up the cover. 2. Unscrew the blue cover at the screw above –X25 and lift up the cover. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
● Miniature fuse in accordance with EN 60127: 2 A … 6 A, slow, maximum 150 VA ● Miniature circuit-breaker: 2 A … 6 A, characteristic D, maximum 150 VA Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Control voltage 230 V for cabinet units Cabinet units access the control voltage for the electronics from the control transformer. Further information can be found in the wiring diagram of the unit. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Refer to the torque table in the section "Tightening torques for power cables" (Page 176) for the torques. 3. Also check the internal power connections for units with more than 160 kW. The connections can slacken during long transport. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 74
More detailed information can be found in the section "DIL switches S1 and S2" (Page 101). Performing insulation test 1. Take the necessary safety precautions such as covering neighboring system parts etc. 2. Connect terminals U1, V1, W1, U2, V2, W2. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
● The "peripheral board 2 / 4" option which can be recognized from the last position of the type designation on the rating plate has safety-oriented inputs. Check these inputs according to the "Safe halt" (Page 139) description. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 76
2. For additional information, refer to the section titled "Mains connection" (Page 53). Adapting motor data 1. Under "P-MOTOR DATA"/ first set the controller variant of the inverter or the motor type. You can enter the following control variants: Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 77
– Adjust the optimum control behavior of your system for load change and speed change under "P-CONTROL PARAMETER". – Set the values for "/P sp.ctr." and "/Tr sp.ctr." in rated operation. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 78
Speed regulator circuit - too high P-Controller The following applies to all motors: ● Enter the rating plate parameters of the motor for sine mode. ● This data can be found on the motor rating plate. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Checking the direction of rotation 1. Check the rotation direction at low speed directly at the motor. 2. In the case of "Rotation/both", check the rotation direction for both directions. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Documenting measured values, saving parameter file Document all measured values from the commissioning in a measurement report and save the parameters of the inverter with the "IMS" software. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
The inverter is operated using the display buttons as follows: Table 8-1 Inverter operation using the display buttons "Inverter On" "Inverter Off" The "Inverter On" and "Inverter Off" functions are only active if you select "Local Mode". Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
2. Switch on the line voltage. 3. Start up the inverter using the control command <On> or input the On command via an external control device (if one is connected). Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
The inverter is operated using various inputs, such as, e.g. control cable terminal block inputs, Profibus control words, signal generators etc. Further information can be found under "Configuring operating sources" (Page 83). Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 84
If you have realized the operating functions using controls, e.g. ON / OFF button, this command causes a shutdown using controller lock without deactivating the controls. No new ON command is necessary for the restart. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Further information can be found in the "Standard mode settings" (Page 87) section. Changes in the menu "P-OPERATION/" cause under "P-OPERATION/Opr." the addition "special" as information that something has been changed from the standard. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
LED from a list ("Bitpool"). More outputs might be available depending on the variants and quantity of installed power sections. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Further information about the operation of several inverters on one PC can be found in the PC tool "IMS". A communication network based on RS 485 limits the network to a further 63 nodes. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
● "Controller release, static " (NC) ‑X2:8: Enable the inverter using a permanent contact. The drive coasts to a stop if you open the contact. The inverter clears all self-holding functions. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
The operation "Speed On" for "Remote" mode is dynamic. Start the drive with an NO (normally open) contact at –X2:11. You change the inverter speed to 0 with an NC (normally closed) contact at ‑X2:10. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
● "Controller release dynamic". Enable the inverter using a normally open contact at ‑X2:9. The drive coasts to a stop if you open the contact at ‑X2:8. The inverter clears all self-holding functions. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
1 to "MPoti". The motor potentiometer function is now valid in "Normal" mode and not valid in test mode. "Reset" (NO): Reset errors and "Emerg. stop" using a 24 V pulse at –X2:14. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
The inverter display shows the message "Interlocking". ● "Off" (NC): You activate the controller inhibit if you remove the 24 V signal at ‑X2:11. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
The operation of the controller block for "Normal mode is dynamic. ● Start the drive with an NO (normally open) contact at –X2:10. ● You inhibit the inverter with a normally closed contact at ‑X2:11. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
The inverter display shows the message "Interlocking". ● "Off" (NC): You issue the command for "Speed Off" if you remove the 24 V signal at ‑X2:10. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
The operation "Speed On" for "normal" mode is dynamic. ● Start the drive with a normally open contact at ‑X2:10. ● Issue the command "Speed Off" with an NC contact at ‑X2:11. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
● "Off" (NC): You issue the command for "Speed Off" if you remove the 24 V signal at ‑X2:10. ● If you close the contacts "Interlocking" or "Off" again during the braking phase, the drive accelerates immediately to the configured setpoint value. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
The operation "Speed On" for "normal" mode is dynamic. ● Start the drive with a normally open contact at ‑X2:10. ● Issue the command "Speed Off" with an NC contact at ‑X2:11. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Connect devices and cables to the control cable terminals only if they conform to the relevant voltage class (DVC) described in this section. Control and power circuits have protective separation between them according to EN 61800‑5‑1. The following graphics show the principle structure: Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 100
Operation 8.4 Controlling the external connections of the inverter Figure 8-14 Overview of external connections and voltage classes Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 101
1.500 V > 1.000 V > 4.500 V > 1.500 V For more detailed information about control cable terminals, please refer to section "Technical data of control cable terminals" (Page 176). Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Devices that are connected, e.g. laptop with IMS, must have basic insulation between the USB interface and ground. In this case, the devices must offer this option, e.g. suitable for battery operation or the original power supply without ground connection. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
OFF: General fault in the closed-circuit principle, control cable terminals ‑2:34 … 36 S1:3 ON: Complete initialization in conjunction with S1:4 = ON OFF: S1:4 ON:Flashing: OFF: Switch S1:6 is not equipped. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 104
Voltage input ‑X2:54 - ‑X2:51 Switch S2: 8 / 9 / 10 configures the analog input AI 1 as a current/voltage input, PTC thermistor input, KTY84-130 input or PT100 input. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
The encoder connection on the inverter side is designed as a socket. ● Only use this encoder for field-oriented control with a speed accuracy < 1 %. ● Connect the encoder mechanically rigid to the motor. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 106
● Only use this encoder for field-oriented control with a speed accuracy < 1 %. ● Connect the encoder mechanically rigid to the motor. ● Do not place any gearbox between encoder and motor. Figure 8-19 TTL encoder at ‑X25 Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Personal injuries caused by a defective unit orinverter Read the connection instructions given in section "Electrical isolation of USB interfaces" (Page 100) and "Safe isolation in accordance with EN 61800-5-1" (Page 97). Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
● Using the "IMS" software, configure which COM port the cable on the PC will be connected – The default setting is COM1. ● Select the configuration under "Options/Drivers/RS232-485-Driver" . Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
In order to be able to issue commands via an external display connected at ‑X26 to the inverter , set the corresponding command source in the parameter assignment to "intern". Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
The inverter controls its own line contactor. Note that the supply voltage for the control electronics is tapped before the main contactor. Further information can be found in the section Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 111
External control voltage for the 230 V inverter 41, 42 Digital output for the main contactor control U1, V1, W1 Mains power connection switched via main contactor Main contactor feedback input 24 V DC supply voltage Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 112
● Perform the activation as for the line contactor. ● Different than for the line contactor, for "P-INV. BEHAVIOUR/MCfunc" as value select the parameters that have "MS" as prefix for motor contactor. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 113
Terminal / component Function -K11 Output side main contactor Design recommendation: AC3 current of the contactor is at least the inverter output current 41, 42 Digital output for the main contactor control Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
The digital inputs are interpreted as a normal digital input for control with a 24 V signal. If these control cable terminals are wired to 10 V potential using a PTC thermistor sensor, these Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 115
● Proximity switch with NAMUR output or with PNP-3 wire output ● Two-channel digital tachometer with HTL output Proximity switch with NAMUR output or with PNP-3 wire output Figure 8-27 PNP speed sensor Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 116
The frequency is available for further processing as "Freq.act." from 0 Hz to 100 Hz and as "Pulse act" from 0 % to 100 %. NPN sensors cannot be used. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 117
"25,600 Hz" "P-PULSE INPUT/Pulses/360" "1024" The frequency is available for further processing as "Freq.act." from 0 Hz to 25.6 kHz and as "Pulse act" from 0 % to 100 %. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Processing functions for the output are available, for example "P‑DigitalOutputs/Relays 1‑4", "LED 1‑2" or "P‑AnalogOutputs". Several functions are available for the processing, for example "P‑MESSAGE-GEN MESS" or "P‑PARAMETERSWITCH". The following graphic clarifies this processing method: Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
You can then use the same principle of operation in any other menu. 8.7.4 More documentation about parameterization You can find further documentation relating to parameterization on the Internet at www.siemens.com (http://www.siemens.com) Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
PTC inputs, suitable for motors in the Ex-zone or Non-Ex-Zone ③ Remove the 100 Ω resistor if these control cable terminals are in use. Figure 8-33 Control cable terminals for "peripheral board 2" application Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
In the case of an equipped peripheral board 3 / 4, the supply of the digital inputs ‑X2:8 … 16 is changed over. The digital inputs are supplied from ‑X2:1/3 instead of ‑X2:51/55. Figure 8-34 Control cable terminals for "peripheral board 3" application Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Control cable terminals for "peripheral board 4" application 8.8.1.6 Mode setting of the "Standard" application The mode setting for the "Standard" application is "siss". Further information can be found in section "Standard mode settings" (Page 87). Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
– The input range from 0 mA to 20 mA or from 0 V to 10 V is proportional to the output frequency from 0 Hz to 50 Hz. ● Analog input two, terminal ‑X2:53 and ‑X2:54: – Equivalent, additional analog input. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
"IMS". 8.8.1.11 Input "Safe halt" / PTC thermistor inputs on peripheral board Detailed information Detailed information can be found in the section "Peripheral boards 1 to 4" (Page 136). Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Control cable terminals for "NAMUR" application 8.8.2.2 Control cable terminals "peripheral board 4" NOTICE Non-compliance with NAMUR guideline NE-37 The NAMUR guideline NE-37 is only completely implemented with the "peripheral board 4" option. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
8.8.2.3 Mode setting of the NAMUR application The mode setting for the NAMUR application is "Namur 1". Refer to the section "NAMUR mode settings" (Page 90) for more detailed information. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
– More detailed information can be found in the section "DIL switches S1 and S2" (Page 101). – You can use the signal in the software for limit value comparisons or as display. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
"IMS". 8.8.2.7 Input "Mandatory mains power isolation" / PTC thermistor inputs on peripheral board Detailed information can be found in the section "Peripheral boards 1 to 4" (Page 136). Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
● Service the device after 5 years in accordance with a specified maintenance schedule. ● Check and clean the equipment and air filter mats (if present) depending on the accumulation of dust. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
7. Lift the inverter away so that the cabling remains with the cable entry plate. 8. Install the new inverter in reverse order. Observe the instructions for the transport of inverters in the section "Transporting inverter" (Page 33). Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Maintenance and service of water cooling (option) Visual inspection As part of the inspection of the complete system, Siemens recommends that the water cooling parts are visually inspected every 6 months and a leakage check performed. Perform the following checks on an annual basis: ●...
Components which are not approved It is dangerous to use components which are not tested, not certified and not approved by Siemens. This can result in death, serious injury or material damage. Use only components which are tested, certified and approved by Siemens.
2 PTC thermistor inputs, one ATEX-certified, one warning motor temperature monitoring for motors in the Ex- zone One "Safe halt" digital input according to EN 954-1, Category 3 9 digital inputs (DI) 3 relay outputs (DO) Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Principle of operation The peripheral board 2 / 4 evaluates the measure motor temperature using a PTC thermistor. The board ensures safety and reliability using the installed short-circuit detection. The "Safe Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
This must be taken into account for the implementation and operation of a system. In comparison to the shutdown using contactors, only the additional hazard die to dangerous shock currents occurred in the inverter. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Emergency Off input which safely disconnects the inverter or the motor from the mains power supply. Safely and reliably disconnect the power supply before opening covers or terminal boxes at the inverter. For example, use a main switch. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
NOTICE Malfunctions If the inverter is used in safety-relevant applications with visible transport damage, malfunctions and damage to property can occur. Do not use inverters with visible transport damage. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
1. Replace the 100 Ω resistor at control cable terminals ‑X3:90‑91 with a potentiometer with at least 10 kΩ. Set a value of approx. 100 Ω. 2. Ensure that 24 V is applied at control cable terminal ‑X2:8. When required, jumper ‑X2:8 and ‑X2:3. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
If the clearance between the resistors and the neighboring components is selected too small, fire can occur due to overheating. This can result in death, serious injury or material damage. Maintain a minimum clearance of 200 mm. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
10.4 Parameter overview A more detailed overview of all parameters can be found in the "IMS" software or in the parameterization guide. You can find both on the Internet (http://www.siemens.com). 10.5 "Factory settings" application Saved device settings which have been made during the internal factory device inspection can be found in this application.
For this option, the following dimensions are produced for the individual frame sizes: Table 10-2 Main switch option for different frame sizes BG K1 … BG K4 Standard device dimensions only BG K5 Option "Q" / "W" is not possible. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Example: Test station with load apparatus. In this case only the losses are supplied via the network. The generated energy is routed via the DC link. Refer to the following graphic for the electrical design: Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 148
● The mains power supply connection cables from –K1:2, 4, 6 to both inverters must be the same length and have the same cross-section. ● You can use a normal cable to connect the DC link, e.g. H07VK in the cabinet, or NYY outside the cabinet. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
The dimensions are unchanged for compact devices. The dimensions of cabinet units increase if an RFI suppression filter category C1 (class B) is installed. Additional data is provided in the unit documentation. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Type code _ _ _ _ P _" on the rating plate that a Profibus circuit board has the description "… been integrated. More details about the circuit board and the Profibus parameters can be found in the separate Profibus description. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 151
Flashing at 2 Hz, 0.25 s On, 0.25 s Off Error in the length of the Profibus telegram Flashing at 4 Hz, 0.12 s On, 0.12 s Off Error in the initialization of the Profibus No bus fault Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Board receives a request and produces a response Board is not currently processing any requests LED "Bus error" Red, lit Bus error Normal operation or circuit board not initialized Modbus connection Sub-D female connector for Modbus Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 153
0.5 s on, 0.5 s off removed) Flashing green at 2 Hz, Initialization of the Modbus board has errors: Contact the service department. 0.25 s on, 0.25 s off Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
The board can be retrofitted. You recognize from the description "… code _ _ _ _ T _" on the rating plate that a Modbus TCP board has been integrated. Figure 10-6 Modbus TCP board Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 155
At the configuration switch, the last byte of the IP address is set as binary number. The set IP address in the example of the diagram on the left is: 192.168.0.42 Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
The "Water cooling" section describes the design of the direct water cooling with open cooling circuit. Recooling of the coolant is not performed. Provide corresponding cooling of the water on-site. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Electromagnetic valve NO ⑤ Stop valve, regulation of the flow rate ⑥ Flow rate regulation valve ⑦ Filter ⑧ Bypass - The version is optional Figure 10-9 Diagram - Direct water cooling Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
● Hose bushings and hose clamps are required to establish the connection: Table 10-8 Hose sizes Hose sizes ½ " ¾ " 1 " 1 ½ " Outer hose 24 mm 30 mm 37 mm 51 mm diameter Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Use a cooling water additive for the closed cooling system of the inverter. Siemens recommends the agent "Antifrogen N" made by Clariant as a cooling water additive. The concentration of this additive can be adjusted to provide the required level of frost protection.
The "READY" and "WORKING" information, refer to the section titled "Reading event LEDs are not lit. log" (Page 159). Siemens provides a list with all messages which are shown on the display and possible remedies on the Internet. 11.1 Reading event log If a fault occurs, the event log of the inverter stores the following data: ●...
Page 162
Read out all data of the last event using the software "IMS" before you contact the Service Center for assistance with an error message. In this way, you significantly simplify the error localization. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
You can find this data on the rating plate of the device. Answers to frequently asked questions and the possibility of sending your questions to the service department can be found here (http://www.siemens.com/automation/support-request). You can find your local contact partner here (Link: http://support.automation.siemens.com/...
0.06 €/min. from land lines of the German Telekom, mobile phone prices may differ. +49 8531 39 569 Technical support: driveservice.rhf.de@siemens.com Spare parts: drivespares.rhf.de@siemens.com Repair: driverepair.rhf.de@siemens.com Spare parts on the Internet: Spares on Web (www.siemens.com/sow) Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
EN 6180‑5‑1, Class2K3 according to EN 60721‑3‑2: Environmental conditions for inverter transport Atmospheric pressure 700 mbar … 1060 mbar, corresponds to max. 3000 m above sea level Ambient temperature - 25 °C … + 70 °C Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Frame sizes of compact units Please refer to the following diagrams and tables for the frame size of your inverter. Compact device 1 dimension drawing Compact device 2 dimension drawing Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
2T3A-87601-250 … 2T3A-87691-400 2T3A-87401-400 BG SL21 2T3A-87501-500 2T3A-87601-500 2T3A-87401-500 … 2T3A-87401-630 BG SL3 2T3A-87501-560 … 2T3A-87501-800 2T3A-87601-560 … 2T3A-87691-910 The corresponding dimension drawings can be found in the following illustrations. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 176
Technical data C.4 Frame sizes of cabinet units Dimension drawing BG SL2 Dimension drawing BG SL21 Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
The units can be operated under different environmental conditions if derating is applied. For further information, refer to section "Derating" (Page 181). For further technical data, refer to the technical data sheet or the CD supplied with the product. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
> 60 V … 250 V DC / 60 mA With peripheral board 3 or 4 only: Minimum switching load: 12 V / 100 mA Relay outputs –X2:43 … 49 Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Identification EX II (2) GD maximum number of sensors 6 sensors according to DIN VDE 0660 Teil 303 OK state < 1.5 kΩ … 1.8 kΩ Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
The water flowrate for type 2T 6 A‑7 5 69 4‑925 with four inverter systems is e.g. 4×2000 l/h. The water-cooled units BG SW2 and SW21 have the same cabinet width as the air-cooled units. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 181
13 ^ ½ " 13 ^ ½ " 19 ^ ¾ " Venting DN "…^…" 13 ^ ½ " 13 ^ ½ " 13 ^ ½ " Cabinet height [mm] 2000 2200 2200 Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
FAST. ● FAST: The fans operate fast if one of the relevant temperatures is higher than the threshold for FAST irrespective of whether or not the unit is turned on. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Voltage derating must also be implemented for cabinet units at an installation altitude of > 3000 m. The following current derating values apply to water-cooled inverters. Refer to the technical data sheet or the CD supplied with the product for the maximum water inlet temperature. Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
NYY, Cable types NYCWY polychlorinated biphenyls: toxins. Relevant for the disposal. PELV "Protective Extra Low Voltage", protective extra-low voltage (PELV). previously function extra-low voltage with safe isolation permanent magnet machine Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...
Page 188
"Universal Serial Bus": serial bus system Uninterruptible power supply Association for Electrical, Electronic & Information Technologies Fully de-ionized water ionized water Supplementary supply agreements for inverter drives in power plants Installation and operating instructions Sinamics G180 Operating Instructions, 05/2013, 4BS0751-001...