Relion
670 series
Transformer protection RET670 ANSI
Pre-configured
Product Guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB RET670

  • Page 1 ® Relion 670 series Transformer protection RET670 ANSI Pre-configured Product Guide...
  • Page 2: Table Of Contents

    20. Ordering.................83 Disclaimer © Copyright 2012 ABB. All rights reserved. Trademarks ABB and Relion are registered trademarks of ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders.
  • Page 3: Application

    IED the ideal solution operation for post-fault disturbance analysis. even for the most demanding applications. Since RET670 has very low requirements on the main Breaker failure protection for each transformer CTs, no interposing CTs are required.It is suitable...
  • Page 4 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 The wide application flexibility makes this product are available as template in the graphical an excellent choice for both new installations and configuration tool. An alternative for the refurbishment of existing installations.
  • Page 5 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 RET 670 50BF TRIP BKR1 WDG1 WDG2 51P/67P TRIP BKR3 50BF 51N/67N VT’s from WDG 2 side of XFRM ANSI10000087-2-en.vsd ANSI10000087 V2 EN Figure 1. A typical protection application for a two winding transformer in single breaker arrangements is shown on the figure.
  • Page 6 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Trip from 50-BF1, 50-BF2 50/51N 50BF2 50BF1 TRIP BKR1 94/86 50/51P BKR1 BKR2 50/51G TRIP BKR2 94/86 WDG1 WDG2 50/51G 50/51P 50BF4 TRIP BKR3 94/86 BKR4 BKR3 50BF3...
  • Page 7 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Trip from 50-BF1, 50-BF2 50/51P 50BF5 TRIP BKR5 94/86 50/51N 94/86 50BF2 50BF1 TRIP 50/51P BKR1 94/86 94/86 BKR1 BKR2 WDG3 TRIP BKR2 94/86 WDG1 WDG2 50/51G 50/51P...
  • Page 8: Available Functions

    Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 2. Available functions Main protection functions = number of basic instances 3-A03 = optional function included in packages A03 (refer to ordering details) IEC 61850 ANSI Function description...
  • Page 9: Current Protection

    Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Back-up protection functions IEC 61850 ANSI Function description Transformer Current protection OC4PTOC 51_67 Four step phase overcurrent protection EF4PTOC 51N_67 Four step residual overcurrent protection NS4PTOC 46I2 Four step directional negative phase sequence...
  • Page 10: Secondary System Supervision

    Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Control and monitoring functions IEC 61850 ANSI Function description Transformer Control SESRSYN Synchrocheck, energizing check and synchronizing APC30 Apparatus control for up to 6 bays, max 30 apparatuses (6CBs) incl.
  • Page 11: Monitoring

    Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 IEC 61850 ANSI Function description Transformer Configuration logic blocks 40-280 40-280 40-280 Fixed signal function blocks B16I Boolean 16 to Integer conversion B16IFCVI Boolean 16 to Integer conversion with Logic Node...
  • Page 12: Remote

    Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Designed to communicate IEC 61850 ANSI Function description Transformer Station communication SPA communication protocol LON communication protocol IEC60870-5-103 communication 20/1 20/1 20/1 protocol Operation selection between SPA and IEC60870-5-103 for SLM DNP3.0 for TCP/IP and EIA-485...
  • Page 13: Basic Ied Functions

    Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Basic IED functions IEC 61850 Function description Basic functions included in all products IntErrorSig Self supervision with internal event list TIME Time and synchronization error TimeSynch Time synchronization...
  • Page 14 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 3. Differential protection The low-impedance function is a percentage biased function with an additional zero sequence current Transformer differential protection T2WPDIF/ directional comparison criterion. This gives excellent T3WPDIF (87T) sensitivity and stability during through faults.
  • Page 15 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 The thermal overload protection estimates the Four step residual overcurrent protection, zero internal heat content of the transformer/generator sequence and negative sequence direction (temperature) continuously. This estimation is made...
  • Page 16 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 5. Voltage protection Overexcitation protection OEXPVPH (24) Two step undervoltage protection UV2PTUV (27) When the laminated core of a power transformer or Undervoltages can occur in the power system generator is subjected to a magnetic flux density during faults or abnormal conditions.
  • Page 17 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 generating plant, generator governor problems can restraining facility is available as well. At too low also cause over frequency. polarizing voltage the overcurrent feature can be either blocked, made non directional or ordered to...
  • Page 18 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 The fuse failure supervision function basically has SESRSYN (25) function includes a built-in voltage three different algorithms, negative sequence and selection scheme for double bus and breaker-and-a- zero sequence based algorithms and an additional half or ring busbar arrangements.
  • Page 19 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 with enhanced security, the command is processed transformer so that for example, the voltage control and the resulting position is supervised. can be blocked if the power reverses etc.
  • Page 20: Local

    Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Single command, 16 signals Supervision of mA input signals The IEDs can receive commands either from a The main purpose of the function is to measure and substation automation system or from the local process signals from different measuring HMI.
  • Page 21: Local

    Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 signals from start of pre-fault time to the end of The event recorder logs all selected binary input post-fault time will be included in the recording. signals connected to the Disturbance report function.
  • Page 22: Human Machine Interface

    Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 before the trigger instant can be saved in the be used as conditions in the configurable logic or disturbance file. for alarming purpose. The disturbance recorder information for up to 100 12.
  • Page 23: Station Communication

    ABB IED's and the new IED 670. SPA communication protocol A single glass or plastic port is provided for the ABB SPA protocol. This allows extensions of simple substation automation systems but the main use is IEC07000077 V1 EN for Substation Monitoring Systems SMS.
  • Page 24: Remote Communication

    Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 as status of primary switchgear apparatus or Multiple command and transmit intertripping signals to the remote IED. An IED can When 670 IED's are used in Substation Automation communicate with up to 4 remote IEDs.
  • Page 25: Remote

    Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 evaluation of operation of the IED and for all Line data communication module LDCM associated electrical circuits. Each module has one optical port, one for each remote end to which the IED communicates.
  • Page 26 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 resistor, is available in a single phase unit and a Layout and dimensions three phase unit. Both are mounted on a 1/1 19 Dimensions inch apparatus plate with compression type terminals.
  • Page 27 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Case size 6U, 1/2 x 19” 10.47 8.81 7.92 9.53 9.96 8.10 6U, 3/4 x 19” 10.47 13.23 7.92 9.53 9.96 12.52 6U, 1/1 x 19” 10.47 17.65 7.92...
  • Page 28: Connection Diagrams

    Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 18. Connection diagrams Table 1. Designations for 1/2 x 19” casing with 1 TRM slot Module Rear Positions BIM, BOM, SOM, IOM or X31 and X32 etc. to X51...
  • Page 29 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Table 2. Designations for 3/4 x 19” casing with 1 TRM slot Module Rear Positions BIM, BOM, SOM, IOM or X31 and X32 etc. to X101 and X102...
  • Page 30 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Table 3. Designations for 1/1 x 19” casing with 2 TRM slots Module Rear Positions BIM, BOM, SOM, X31 and X32 etc. to X131 IOM or MIM and X132...
  • Page 31 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 1MRK002802-AB-10-670-1.2-PG-ANSI V1 EN Figure 8. Transformer input module (TRM) ■ Indicates high polarity. See table Note that internal polarity can be adjusted by setting of analog input CT neutral direction and/or on SMAI pre- processing function blocks.
  • Page 32 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 1MRK002802-AB-7-670-1.2-PG-ANSI V1 EN Figure 9. Power supply module (PSM)
  • Page 33 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 1MRK002802-AB-11-670-1.2-PG-ANSI V1 EN Figure 10. Binary input module (BIM). Input contacts named XA corresponds to rear position X31, X41, etc. and input contacts named XB to rear position X32, X42, etc.
  • Page 34 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 1MRK002802-AB-8-670-1.2-PG-ANSI V1 EN Figure 15. IED with basic functionality communication interfaces...
  • Page 35 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 IED670 BUS A BUS B 87B-TRIP 189-OPEN 189b BLOCK LV 51P 189-CL 189a BFI 3PH 289b 289-OPEN 289a 289-CL SUDDEN PRESSURE TRIP OIL TEMP TRIP TRM1:1-3 WIND TEMP TRIP...
  • Page 36 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Figure 16. Typical connection diagram for two winding transformer in a single breaker arrangement. Note! Including IO for control option.
  • Page 37 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 IED670 BUS A 189-OPEN 189b 87B-TRIP 189-CL 189a 6289-OPEN 6289b BLOCK LV 51P 6289-CL 6289a 6289 BFI 3PH TRM1:1-3 SUDDEN TRM1:4-6 TO MAIN 2 PRESSURE TRIP OIL TEMP TRIP...
  • Page 38 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 BUS A IED670 BUS B 87B-TRIP 189-OPEN 189b 189-CL 189a BLOCK LV 51P 289-OPEN 289b 289-CL 289a BFI 3PH TRM1:1-3 SUDDEN PRESSURE TRIP TO MAIN 2 OIL TEMP TRIP...
  • Page 39 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Figure 18. Typical connection diagram for three winding transformer in a single breaker arrangement. Note! Including IO for control option.
  • Page 40 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 BUS A IED670 TO SECOND BAY 189-OPEN 189b 189-CL 189a 6289-OPEN 6289b 6289-CL 6289a 87B-TRIP 6289 TRM1:1-3 BLOCK LV 51P TRM1:4-6 BFI 3PH TO MAIN 2 TO MAIN 2...
  • Page 41: Technical Data

    Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 19. Technical data General Definitions Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the...
  • Page 42 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Table 6. TRM - Energizing quantities, rated values and limits for measuring transformer modules Quantity Rated value Nominal range Current = 1 or 5 A (0-1.8) × I...
  • Page 43 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Auxiliary DC voltage Table 9. PSM - Power supply module Quantity Rated value Nominal range Auxiliary dc voltage, EL (input) EL = (24 - 60) V EL ± 20% EL = (90 - 250) V EL ±...
  • Page 44 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Table 11. BIM - Binary input module with enhanced pulse counting capabilities Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ± 20% 48/60 V RL ±...
  • Page 45 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Table 13. IOM - Binary input/output module contact data (reference standard: IEC 61810-2) Function or quantity Trip and signal relays Fast signal relays (parallel reed relay) Binary outputs...
  • Page 46 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Table 14. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs Function of quantity Static binary output trip Rated voltage 48 - 60 VDC 110 - 250 VDC...
  • Page 47 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Table 15. SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs Function of quantity Trip and signal relays Max system voltage 250V AC/DC Number of outputs...
  • Page 48 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Influencing factors Table 17. Temperature and humidity influence Parameter Reference value Nominal range Influence Ambient temperature, +20 °C -10 °C to +55 °C 0.02% /°C operate value Relative humidity...
  • Page 49 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Type tests according to standards Table 20. Electromagnetic compatibility Test Type test values Reference standards 1 MHz Oscillatory burst disturbance 2.5 kV IEC 60255-22-1 100 kHz slow damped oscillatory wave immunity 2.5 kV...
  • Page 50 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Table 22. Environmental tests Test Type test value Reference standard Cold test Test Ad for 16 h at -25°C IEC 60068-2-1 Storage test Test Ad for 16 h at -40°C...
  • Page 51 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Differential protection Table 25. Transformer differential protection T2WPDIF, T3WPDIF (87T) Function Range or value Accuracy Operating characteristic Adaptable ± 1.0% of In for I < In ± 1.0% of In for I > In Reset ratio >95%...
  • Page 52 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Table 26. Restricted earth fault protection, low impedance REFPDIF (87N) Function Range or value Accuracy Operate characteristic Adaptable ± 1.0% of I for I < I ± 1.0% of I for I > I Reset ratio >95%...
  • Page 53 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Current protection Table 27. Four step phase overcurrent protection OC4PTOC (51/67) Function Setting range Accuracy Operate current (1-2500)% of lBase ± 1.0% of I at I ≤ I ±...
  • Page 54 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Table 28. Four step residual overcurrent protection EF4PTOC (51N/67N) Function Range or value Accuracy lBase Operate current (1-2500)% of ± 1.0% of I at I £ I ± 1.0% of I at I > I Reset ratio >...
  • Page 55 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Table 29. Four step negative sequence overcurrent protection NS4PTOC (46I2) Function Range or value Accuracy lBase Operate value, negative (1-2500)% of ± 1.0% of I at I £ I sequence current, step 1-4 ±...
  • Page 56 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Table 30. Thermal overload protection, two time constants TRPTTR (49) Function Range or value Accuracy IBase Base current 1 and 2 (30–250)% of ± 1.0% of I Operate time: = load current before overload IEC 60255–8, class 5 + 200 ms...
  • Page 57 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Voltage protection Table 33. Two step undervoltage protection UV2PTUV (27) Function Range or value Accuracy Operate voltage, low and high step (1–100)% of VBase ± 0.5% of V Absolute hysteresis (0–100)% of...
  • Page 58 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Table 35. Two step residual overvoltage protection ROV2PTOV (59N) Function Range or value Accuracy VBase Operate voltage, low and high step (1-200)% of ± 0.5% of V at V < V ±...
  • Page 59 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Table 37. Loss of voltage check LOVPTUV (27) Function Range or value Accuracy Operate voltage (0–100)% of VBase ± 0.5% of V Pulse timer (0.050–60.000) s ± 0.5% ± 10 ms Timers (0.000–60.000) s...
  • Page 60 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Frequency protection Table 38. Underfrequency protection SAPTUF (81) Function Range or value Accuracy Operate value, pickup function (35.00-75.00) Hz ± 2.0 mHz Operate time, pickup function 100 ms typically...
  • Page 61 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Table 39. Overfrequency protection SAPTOF (81) Function Range or value Accuracy Operate value, pickup function (35.00-75.00) Hz ± 2.0 mHz at symmetrical three- phase voltage Operate time, pickup function 100 ms typically at f -0.5 Hz to f...
  • Page 62 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Multipurpose protection Table 41. General current and voltage protection CVGAPC Function Range or value Accuracy Measuring current input Phase A, Phase B, Phase C, PosSeq, NegSeq, 3*ZeroSeq, MaxPh, MinPh,...
  • Page 63 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Table 41. General current and voltage protection CVGAPC , continued Function Range or value Accuracy Operate time, pickup overvoltage 25 ms typically at 0 to 2 x V...
  • Page 64 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Secondary system supervision Table 42. Current circuit supervision CCSRDIF (87) Function Range or value Accuracy Operate current (5-200)% of I ± 10.0% of I at I £ I ±...
  • Page 65 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Control Table 44. Synchronizing, synchronism check and energizing check SESRSYN (25) Function Range or value Accuracy Phase shift, j (-180 to 180) degrees line Voltage ratio, V (0.40-25.000) % of...
  • Page 66: Logic Smpptrc

    Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Logic Table 45. Tripping logic SMPPTRC (94) Function Range or value Accuracy Trip action 3-ph, 1/3-ph, 1/2/3-ph Minimum trip pulse length (0.000-60.000) s ± 0.5% ± 10 ms Timers (0.000-60.000) s...
  • Page 67 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Monitoring Table 47. Measurements CVMMXN Function Range or value Accuracy Frequency (0.95-1.05) × f ± 2.0 mHz Connected current (0.2-4.0) × I ± 0.5% of I at I £ I ±...
  • Page 68 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Table 50. Disturbance report DRPRDRE Function Range or value Accuracy Pre-fault time (0.05–9.90) s Post-fault time (0.1–10.0) s Limit time (0.5–10.0) s Maximum number of recordings 100, first in - first out...
  • Page 69 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Table 53. Event recorder Function Value Buffer capacity Maximum number of events in disturbance report Maximum number of disturbance reports Resolution 1 ms Accuracy Depending on time synchronizing Table 54.
  • Page 70 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Metering Table 56. Pulse counter PCGGIO Function Setting range Accuracy Input frequency See Binary Input Module (BIM) Cycle time for report of counter (1–3600) s value Table 57. Energy metering ETPMMTR...
  • Page 71 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Station communication Table 58. IEC 61850-8-1 communication protocol Function Value Protocol IEC 61850-8-1 Communication speed for the IEDs 100BASE-FX Table 59. LON communication protocol Function Value Protocol Communication speed 1.25 Mbit/s...
  • Page 72 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Table 63. SLM – SPA/IEC 60870-5-103/DNP3 port Quantity Range or value Optical connector Glass fiber: type ST Plastic fiber: type HFBR snap-in Fiber, optical budget Glass fiber: 11 dB (3000ft/1000 m typically *)
  • Page 73: Remote

    Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Remote communication Table 67. Line data communication module Characteristic Range or value Type of LDCM Short range (SR) Medium range (MR) Long range (LR) Type of fiber Graded-index Singlemode 9/125 µm...
  • Page 74 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Hardware Table 68. Case Material Steel sheet Front plate Steel sheet profile with cut-out for HMI Surface treatment Aluzink preplated steel Finish Light grey (RAL 7035) Table 69. Water and dust protection level according to IEC 60529...
  • Page 75 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Basic IED functions Table 73. Self supervision with internal event list Data Value Recording manner Continuous, event controlled List size 1000 events, first in-first out Table 74. Time synchronization, time tagging...
  • Page 76 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Table 77. IRIG-B Quantity Rated value Number of channels IRIG-B Number of channels PPS Electrical connector: Electrical connector IRIG-B Pulse-width modulated 5 Vpp Amplitude modulated – low level 1-3 Vpp –...
  • Page 77 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Inverse characteristic Table 78. ANSI Inverse time characteristics Function Range or value Accuracy Operating characteristic: td = (0.05-999) in steps of 0.01 unless otherwise stated æ ö ç...
  • Page 78 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Table 79. IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic: td = (0.05-999) in steps of 0.01 æ ö ç ÷ × ç ÷ è...
  • Page 79 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Table 80. RI and RD type inverse time characteristics Function Range or value Accuracy RI type inverse characteristic td = (0.05-999) in steps of 0.01 IEC 60255-3, class 5 + 40 ms ×...
  • Page 80 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Table 81. Inverse time characteristics for overvoltage protection Function Range or value Accuracy Type A curve: td = (0.05-1.10) in steps of 0.01 unless Class 5 +40 ms otherwise stated æ...
  • Page 81 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Table 82. Inverse time characteristics for undervoltage protection Function Range or value Accuracy Type A curve: td = (0.05-1.10) in steps of 0.01 unless Class 5 +40 ms otherwise stated æ...
  • Page 82 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Table 83. Inverse time characteristics for residual overvoltage protection Function Range or value Accuracy Type A curve: td = (0.05-1.10) in steps Class 5 +40 ms of 0.01 æ...
  • Page 83: Ordering

    To obtain the complete ordering code, please combine code from the tables, as given in the example below. Example code: RET670*1.2-A30A-A01A02B12C05D01D03E01F02H09-B1-X0-C-B-KA-B3X0-A-ABC-X-XD. Using the code of each position #1-11 specified as RET670*1-2 2-3-4-5-6-7 7-8-9 9 9 9-10 10 10 10 10 10-11 11 11 11 11 11 11-12 12 RET670*...
  • Page 84 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Casing Notes and Rules 1/2 x 19" case Note: Only for A30A 3/4 x 19" case 1TRM slot Note: Only for A30A 1/1 x 19" case 2 TRM slots Note: Only for B30A/B40A Selection for position #5.
  • Page 85 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Binary input/output module, mA and time Notes and Rules synchronization boards. Note: 1 BIM and 1 BOM included in A30A, 2 BIM and 1 BOM included in B30A/ B40A.
  • Page 86: Remote

    Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Remote end communication, DNP serial comm. and time Notes and Rules synchronization modules Slot position (rear view) Available slots in 1/2 case with 1 TRM █ █ █...
  • Page 87 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Test switch RHGS 6 Case or RHGS 12 Case with mounted The test system COMBITEST intended for use with RTXP 24 and the on/off switch for dc-supply are the IED 670 products is described in 1MRK 512 ordered separately.
  • Page 88 Transformer protection RET670 ANSI 1MRK 504 118-BUS A Pre-configured Product version: 1.2 Configuration and monitoring tools Front connection cable between LCD-HMI and PC Quantity: 1MRK 001 665-CA LED Label special paper A4, 1 pc Quantity: 1MRK 002 038-CA LED Label special paper Letter, 1 pc...
  • Page 89 670 series SPA and signal list 1MRK 500 092-WUS IEC 61850 Data objects list for 670 series 1MRK 500 091-WUS Engineering manual 670 series 1MRK 511 256-UUS Communication set-up for Relion 670 series 1MRK 505 260-UEN More information can be found on www.abb.com/substationautomation.
  • Page 91 ABB Inc. 3450 Harvester Road Burlington, ON L7N 3W5, Canada Phone Toll Free: 1-800-HELP-365, menu option #8 ABB Mexico S.A. de C.V. Paseo de las Americas No. 31 Lomas Verdes 3a secc. 53125, Naucalpan, Estado De Mexico, MEXICO Phone (+1) 440-585-7804, menu...