ABB investigate such ways. Anyone using service procedures or tools, whether or not recommended by ABB, must satisfy himself thoroughly that neither personal safety nor equipment safety will be jeopardized by the service method or tools selected.
Make sure that all materials described in the shipping note are included in the supply. If any damage or irregularity is seen in the supplied product after unboxing, notify ABB (directly or through the agent or distributor) as soon as possible within five days of receipt.
The AutoLink Electronic Sectionalizer is a protection device that operates at a permanent fault in the distribution line. It must be used together with a upstream recloser. Please take note that the AutoLink is not a fuse tripping device, therefore it cannot be used as a protection device by itself.
TEHI95094 – Rev. 2 6/ 12 6.3 Initial Setting or Previous Setting Modification Instructions Remove the top cap (Fig. 1 A) using a 34mm fork spanner holding the tube with the hand (Fig. 1 B). Check condition of O-ring (Fig. 2 E), and replace it if necessary, applying grease on it.
6.4 Dip-Switch Configuration Once the calibration current and counts are set, cover the dip-switch with silicon grease (Fig. 3), supplied with AutoLink. Check the condition of the O-Ring (Fig. 2 E) and apply silicon grease (Fig. 4 F) both inside...
Place the cap, holding the tube with the hand, and tighten it using a 34 mm fork spanner (torque between 8 and 10 Nm) without damaging the O-Ring (Fig. 5). 6.5 AutoLink Repositioning Push the interlocking bolt (Fig. 6) until blocked (it will rotate freely). Do not strike the bolt, nor use any type of tool to reset.
Page 9
TEHI95094 – Rev. 2 9/ 12 Turn the tripping pin 90°, until the lower contact is firmly blocked (Fig. 8) Place the pole in the tube inferior eyelet (Fig. 9) and position in the cutout-base.
Page 10
TEHI95094 – Rev. 2 10/ 12 Withdraw the pole and place it in the tube’s superior eyelet (Fig. 10). Push it until it remains in closing position.